HomeMy WebLinkAbout308863_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101117157
PROJECT ADDRESS:
307 S Susan St
PLAN CHECK ENGINEER:
Lo, JonathanTEL:714
647-5822
EMAIL:
Jlo@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/20/2023
INITIAL REVIEW
12/5/2023
EXPIRATION
4/17/2024
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Mike Abbas
3.
TEL:
(818)442-4455
FAX:
VALUATION: $15,000.00
EMAIL:
souria24@yahoo.com
FLOOD ZONE: X-0602320256J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5822 for an appointment.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance (CHECKED BOXES REQUIRED ONLY):
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☐Public Works Agency approval (647-5039).
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☐Police Department approval on the corrected/final set of drawings (647-5840).
☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).Comments have been provided on drawing and calculation hard copies in relation to all comments below. Applicant must pick up red marked sets from city prior to resubmittal and return marked up set with resubmittal.DrawingsSheet SP
Provide the following design data on the first sheet (R106.1.1)
☒Occupancy groups (R-2) Sheet SNew guardrail posts shall be placed and shown throughout entire deck span and all sides of deck for clarity. Currently looks to show only four posts needed for guardrail extension in entire length.Sheet S1Detail 1 – Plan View – It is unclear how intended A35 clips are to be installed at new blocking. Please revise to show clips at sides or tops as intended. It is recommended to provide two clips on each side of blocking as marked up.Detail 2 – It is unclear how bottom post is to be anchored or connected. It is noted to see Detail X for plate weld, but Detail X does not look to work at bottom post condition. Provide detail as needed.Detail 2a X – Provide weld type on weld symbol shown in Detail X.Detail 5 – Grab bar on side with return shall slope out tread length minimum (1014.6).(End of Comment)