HomeMy WebLinkAbout306028_4_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101116293
PROJECT ADDRESS:
1230 S Garnsey St
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/22/2023
INITIAL REVIEW
9/21/2023
EXPIRATION
2/18/2024
RECHECKS:
1.11/7/2023
PROJECT APPLICANT CONTACT PERSON:
2.12/19/2023
Frank Mitchell
3.
TEL:
(714)492-9779
FAX:
VALUATION: $41,140.00
EMAIL:
Frankfacts@yahoo.com
FLOOD ZONE: X-0602320257J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a).
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
PLAN CHECK COMMENTS
Energy calculation requires minimum 2x10 floor joists with R-30 insulation between joists at the raised-floor framing. However, structural framing plan has only 2x6 will not fit the insulation. Please revise design.
Revise cavity insulation between ceiling joist: R-38 instead of R-30 per Energy calculation.
Provide (10) 6x14 vents for the under-floor space ventilation per designer’s calculation on plan.
Provide (15) 14”x4” vents per designer’s attic ventilation calculation on plan. (CRC R806.2)
STRUCTURAL
The “cover page” of the structural calculation shall be stamped and signed by the Registered Design Professional and shall include the date of signing below the stamp. (California Business & Professions Code 5537, 5538, 6737.1, and 6745)
We do not find the floor beam hanger “HUTF” in detail 17/SD1 as approved nailer and concrete wall application from manufacturer. Provide Simpson catalog page or ICC report to prove the application is valid or change design.
(2) Copies of updated structural calculation are required. City received one copy on this submittal.
END OF COMMENTS