Loading...
HomeMy WebLinkAbout308669_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101117096 PROJECT ADDRESS: 1831 E Carnegie Ave PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 10/16/2023 INITIAL REVIEW 10/19/2023 EXPIRATION 4/13/2024 RECHECKS: 1.12/17/2023 PROJECT APPLICANT CONTACT PERSON: 2. David Bailey 3. TEL: (949)573-1050 FAX: VALUATION: $25,000.00 EMAIL: david@dlbarch.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840)An application for a permit for any proposed work shall be deemed to have abandoned / expired after 180 days of the date of filing, unless such application has been issued.*PLAN WAS INCOMPLETE. THE FOLLOWING ARE REQUIRED. ADDITIONAL PLAN CHECK COMMENTS AND FEE MAY BE REQUIRED AT TIME OF RESUBMITTAL. Sheet A-1: Sheet T-1: Partial Floor Plan was insufficient. Please provide a complete floor plan of the existing building, show all rooms/spaces. 2nd Review Comment: Existing Floor plan – Plan shall be legible. Please provide an additional sheet for the existing floor plan. Restrooms: Restrooms shall be made accessible to the persons with disabilities. Please provide restroom floor plans and details to show compliance with Chapter 11B, Division 6. 2nd Review Comment: Response was incomplete. Please provide enlarged restroom floor plan for the restroom(s) that serving the improvement area (nearest to the altered area). Restrooms shall be made accessible to the persons with disabilities. Where existing toilet rooms or bathing rooms do not comply with Section 11B-603, directional signs indicating the location of the nearest toilet room or bathing room complying with Section 11B-603 within the facility shall be provided. Signs shall comply with Section 11B-703.5. (11B-216.8)Reminder: Plan shall be legible. Details shall be clearly cross-referenced onto the plan.*Plan was incomplete. Additional comments may be required.