HomeMy WebLinkAbout307270_4_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101116614
PROJECT ADDRESS:
1404 E St Gertrude Pl
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
F-1, S-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
9/12/2023
INITIAL REVIEW
9/26/2023
EXPIRATION
3/10/2024
RECHECKS:
1.11/28/23
PROJECT APPLICANT CONTACT PERSON:
2.1/10/24
Mariano Canillas
3.
TEL:
(714)655-6184
FAX:
VALUATION: $636,480.00
EMAIL:
mario.greenforest@gmail.com
FLOOD ZONE: X-0602320276J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
An application for a permit for any proposed work shall be deemed to have abandoned / expired after 180 days of the date of filing, unless such application has been issued.
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Orange County Sanitation District (714) 593-5756Sheet A3.11: One-hour wall and ceiling assembly as required for the exit passage way – Please provide ICC or UL listing report number for the fire-rated thermal fiber panel; otherwise, provide construction detail for a one-hour fire-rated wall and ceiling assembly. Provide details on plans and provide verification of a tested assembly to achieve the required fire-rating. 2nd Review Comment: New one-hour ceiling assembly above the exit passageway – minimum ½” plywood sheathing is required on top of the steel C ceiling joists. Please provide details to show how the ½” will be installed on the steel ceiling joist, where the existing floor joist is located directly above it; the one-hour wall may need to extended to the underside of the existing floor sheathing. Please provide details and clearly cross-reference details onto the plan. 3rd Review Comment: Response was incomplete. Revise detail 19/A9.31 to show roof deck material (plywood and its thickness to make up the one-hour full roof assembly. Show fire-blocking between existing non-fire-rated roof assembly and proposed fire-rated roof assembly portion. Details shall be clearly cross-referenced onto the plan. For clarity, called out details on building section on sheet A8.11 so that it can be easily located. 3rd Review Comment: Sheet A1.91 – Additional exit signs shall be provided at the following location. At door D7, on both sides of door for occupants travel in both directionsAt door D10, on both sides of door for occupants travel in both directionsDoor D11, on the interior side of the exit doorway3rd Review Comment: Sheet A1.92, Exiting from the second story – Please revise plan to show the exit access travel distance of 75-ft maximum, measure to the bottom landing of the stairway, where the two exit accesses are available. 3rd Review Comment: Duplicate plan sheets A9.41 were provided. Please remove the old sheet. 3rd Review Comment: Final plans shall be stamped and wet sign and dated by the architect of record (all sheets). PLEASE PROVIDE TWO (2) COMPLETE SETS OF FINAL PLANS FOR FINAL REVIEW AND APPROVAL. (End of Comment)