Loading...
HomeMy WebLinkAbout300616_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101114569 PROJECT ADDRESS: 1818 E First St Unit# 500 PLAN CHECK ENGINEER: Ahangian, KathyTEL:714 647-5812 EMAIL: Kahangian@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V A, SPK OCCUPANCY CLASSIFICATION(S): R-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 1/4/2024 INITIAL REVIEW 1/19/2024 EXPIRATION 7/2/2024 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Sandy Zundell 3. TEL: (949)929-7611 FAX: VALUATION: $15,000.00 EMAIL: sandy@brandywine-homes.com FLOOD ZONE: X-0602320277J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.Please remove all the MEP drawings from the architectural set.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceOn sheet LC-1.01 provide minimum 24” clearance to the strike edge of entry door for 60” long.Remove base cabinet from the bathroom sink on sheet S-01.Provide bathroom sign on sheet S01.Show detail 7 on floor plan 2 on sheet S-1.Show zero curb from access Aisle to the sidewalk.Please provide I-hr fire rated with detail for the wall between garage and new office.