HomeMy WebLinkAbout313502_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101118536 &101118538,101118539, 101118540
PROJECT ADDRESS:
303 N Mountain View St
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812
EMAIL:
Kahangian@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
3/12/2024
INITIAL REVIEW
4/15/2024
EXPIRATION
9/8/2024
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Huy Tran
3.
TEL:
(714)383-0322
FAX:
VALUATION:
EMAIL:
htran@nextcons.net
FLOOD ZONE: A-0602320256J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).
The engineer of record shall indicate that the design has been reviewed before submitting to the building department. The truss design shall be approved by the building department before the trusses are installed."
For Unit 1 and 2 (303& 305 Mountain view) provide calculation to show 2-4x6 post can carry 30524 # load from girder truss #CC1.
For unit 3and 4 (307 & 309 Mountain View ) provide calculation to show 2-4x6 posts can carry 26831 # load from girder truss #CC1.
For unit 5 and 6 (311& 313) provide calculation to show 2-4x6 post can carry 26631lb and 4x4 post can carry 696 lb , 4x6 post can carry 8086# from girder truss #CC1.
For unit 7 and 8(315 & 317) provide calculation to show 4x4 post can carry 6968 # and 8086 # load and 2-4x6 can carry 26631lb from girder truss #CC1.