PLAN CHECK NO:
101118548
PROJECT ADDRESS:
450 E Fourth St Unit# 329
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V-A
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
3/12/2024
INITIAL REVIEW
3/13/2024
EXPIRATION
9/8/2024
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Luis Guzman
3.
TEL:
(714)791-4398
FAX:
VALUATION: $14,000.00
EMAIL:
Genryz17@gmail.com
FLOOD ZONE: X-0602320276J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
Sheet A2.0:
Existing 3rd Floor Plan: Plan indicated “Install 6-2x12 sister joist” – Please provide 3rd Floor Framing Plan to show floor joists and details of sister joist.
4th Floor Framing Plan:
Please clarify floor joist vs. roof rafters as stated on the plan. Coordinate and revise plan accordingly.
Please clarify the framing is occurred on 3rd floor or on 4th floor.
For clarity please correct typo for “Framing” (not “Praming”)
3th Floor Framing Plan
Correct typo for “Framing” (not Praming).
Please clarify floor joist sizes. Is it 2x10 or 2x12?
Structural calculation showed 2x12 floor joist. Please coordinate and revise plans and calculation accordingly.
Replaced sliding door: Please specify U-factor of 0.3 max and SHGC of 0.23 max.
The existing building is a type V-A construction (one-hour fire-rated construction) –
Please provide detail to show one-hour floor assembly at the repaired floor and deck.
Provide detail to show one-hour protection for the replaced 6x10 header.
(End of Comment)