Loading...
HomeMy WebLinkAbout313577_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101118564 PROJECT ADDRESS: 1423 N Louise St PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830 EMAIL: aso@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 3/13/2024 INITIAL REVIEW 3/13/2024 EXPIRATION 9/9/2024 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Todd Duncan 3. TEL: (714)916-3289 FAX: VALUATION: $100,000.00 EMAIL: duncan.designandbuild@gmail.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.The applicant shall obtain clearances/approvals for the following, prior to building permit issuance Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. Public Works Agency approval (647-5039).Note on plan: All concealed work installed without permits must be exposed for inspection to the satisfaction of the Building Inspector. This includes methods of attachment and all footings, structural members, mechanical, electrical, plumbing and insulation.Provide the following design data on the first sheet (R106.1.1) Automatic Fire Sprinkler (YES or NO) Number of stories Flood Zone: XNote on plan: Mechanical, electrical and plumbing are not part of this plan review and approval. MEP are subject to building field inspection.Smoke Alarms – Provide smoke alarm(s) in each sleeping room; in each area giving access into each sleeping room; in basement and habitable attics. (R314) Carbon Monoxide Alarms – Provide carbon monoxide alarms at outside of each sleeping area, in the immediate vicinity of the bedroom(s); on every level of a dwelling unit including basements. (R315) Kitchen shall be vented to the outside. On the plan, please show exhaust fan(s) in kitchen (100 cfm minimum). Provide notes: Plumbing fixtures flow rate limitation: Water closet – 1.28 gallon per flush Shower head – 1.8 gallons per minute at 80 psi. Lavatory faucets – 1.2 gallon per minute at 60 psi. Kitchen faucet – 1.8 gallon per minute at 60 psi.Plan Review Comments on the Plans:Sheet T1.0: Please specify “North” on the address: “1423 North Louise Street, Santa Ana, CA 92706” on the title sheet and title block.Sheet T1.0: Under the Special Inspection notes, it does not appear any of the items are applicable to this project. Engineer shall verify the Special Inspection Notes.Sheet T1.0: Under Building Data, revise the jurisdiction to “City of Santa Ana”.Sheet T1.0: Under Building Data, Revise the occupancy group to “R3” only.Sheet S1.0: Under Design Criteria, verify the value for the Response Modification Coefficient.Sheet S1.0: Under Design Criteria, verify the seismic force resisting system.Sheet S2.0: provide details where BM1 connects to exterior wall and 4x8 girder.Plan Review Comments on Structural Calculations:There are review comments on structural calculations.[The end of comment]