HomeMy WebLinkAbout314540_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101118888
PROJECT ADDRESS:
1028 N Mar-Les Dr
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
4/15/2024
INITIAL REVIEW
5/2/2024
EXPIRATION
10/12/2024
RECHECKS:
1.06/05/2024
PROJECT APPLICANT CONTACT PERSON:
2.
Quoc Do
3.
TEL:
(714)458-5374
FAX:
VALUATION: $153,000.00
EMAIL:
doquocpl@yahoo.com
FLOOD ZONE: X-0602320143J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
Sheet A-101. Call out length of each new partition wall. See redlines on plan.
Sheet A-102. Callout attic vent locations, sizes and types on roof plan.
Sheet A-102. Show high/low vent locations on plans and comply with the net opening area limitation and location:
The total net free ventilating area shall not be less than 1/300 when at least 40% and not more than 50% of the required ventilating area is provided by ventilators located not more than 3 feet below the ridge or highest point of the space, measured vertically with the balance of the required ventilation located by the bottom one-third of the attic space. (CRC R806.2).
PC2: Insufficient low vent free area.Recommend to place all roof vent (288 in square) to be located by the bottom one-third of the attic space or provide more ventilators to meet min 1/150 ratio.
END OF COMMENTS