PLAN CHECK NO:
101117652
PROJECT ADDRESS:
1423 N Mar-Les Dr
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812
EMAIL:
Kahangian@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/12/2023
INITIAL REVIEW
1/2/2024
EXPIRATION
6/9/2024
RECHECKS:
1.1/31/24
PROJECT APPLICANT CONTACT PERSON:
2.2/13/24
Xavier Velasco
3.
TEL:
(714)335-1522(714)745-4407
FAX:
VALUATION:
EMAIL:
xavierjordi@posteo.net
FLOOD ZONE: X-0602320143J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).
Truss plan doesn’t match approved framing plan, please revise truss plan with calculation to match to match the framing plan or revise approved framing plan and the foundation plan with calculation to match the truss drawings.Pending 1/31/24
1/31/24
Please see the red marks on the truss drawings that doesn’t match the roof framing plan.( There is no bearing wall on the 2nd floor, Drawings show Girder truss supported over another girder truss,…
Truss #D01G, calculated for 11 feet span, on sheet S3, it is 18’ long, please clarify.
Please bring the red mark back.
2/13/24
It appears that roof framing design is changed, please submit revised roof framing plan and engineering calculation for review. Separate permit number is required, please fill out revision application and see permit counter.