HomeMy WebLinkAbout315948_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101119337 PROJECT ADDRESS: 2781 W MacArthur Blvd Unit# F-1 PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830 EMAIL: aso@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/20/2024 INITIAL REVIEW 5/21/2024 EXPIRATION 11/16/2024 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Tony Rocha 3. TEL: (949)328-9270 FAX: VALUATION: $18,000.00 EMAIL: tonyaarochaco.com FLOOD ZONE: X-0602320258J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Provide note on the title sheet: “Building/Suite/Unit shall not be occupied until a permit for tenant improvements is issued and finaled.”Permits for interior demolition work for commercial and industrial buildings (for example: demolition of partition walls and ceiling) are considered an “alteration” requiring improvements for disabled accessibility in accordance with CBC Section 11B-202.3.Compliance may be accomplished by one of the following:1.The legal property owner of the building to write a letter to the building official acknowledging that the building will not be occupied until a permit for a tenant improvement (T.I.) has been obtained and finalized.2.As part of the demolition permit, the owner spends at least 20% of the valuation of improvements on priority items listed under CBC Section 11B-202.4. This requires plans to be prepared and submitted for plan check. Add note below to the demolition plan.3.If tenant improvement plans have been submitted, reference the plan check number on the partial demolition permit. Add note below to the demolition plans.[The End of Plan Review Comments]