Loading...
HomeMy WebLinkAbout316014_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101119357 PROJECT ADDRESS: 1806 W Occidental St Unit# 2 PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/22/2024 INITIAL REVIEW 6/12/2024 EXPIRATION 11/18/2024 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Quoc Do 3. TEL: (714)458-5374 FAX: VALUATION: $55,000.00 EMAIL: doquocpl@yahoo.com FLOOD ZONE: X-0602320257J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. PLAN CHECK COMMENTS ARCHITECTURAL Sheet A-001. Remove the “stud wall reinforcement” page on plan that do not comply with CRC R327. See redlines on plan for reference. Provide 1-hour minimum fire separation with STC 50 minimum sound rating assembly between detached ADU and Main house from surface of floor to the underside of roof sheathing. Detail shall be tested and approved by approval agencies (e.g. ICC, UL, IAPMO, GA manual and etc…).Provide fire rated assembly details on plan and cross-reference to the floor plan. Sheet A-201. Provide building section notes on plan. The notes shown in the building cross-sections are not available. ENERGY REQUIREMENTS Sheet T-24. The energy calculation is design for JADU. E.g. refer to column 2 on page 5 of CF1R form and other pages. Please clarify and revise energy calculation for an attached ADU, not a JADU. Revise energy calculation to include north side windows in the building envelope. Energy review is pending to the revised energy calculation on the next submittal. STRUCTURAL Provide top and bottom lateral support of the interior non-load bearing partition wall design and details on plan. Provide connection and shear transfer details per redmarks on plan. END OF COMMENTS