HomeMy WebLinkAbout316039_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101119364
PROJECT ADDRESS:
713 N Newhope St
PLAN CHECK ENGINEER:
Huang, GaryTEL:714
647-5862
EMAIL:
Ghuang@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
A-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/22/2024
INITIAL REVIEW
7/3/2024
EXPIRATION
11/18/2024
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Giep Van Le
3.
TEL:
(323)537-5874
FAX:
VALUATION: $4,000.00
EMAIL:
legiep49@gmail.com
FLOOD ZONE: A-0602320143J
GUIDELINES:
Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies
This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2022 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES)
The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws
All listed plan review comments must be adequately addressed before a building permit can be issued
Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
Applicant shall obtain clearance/approvals from following departments after obtaining approval from Building and Safety Division, prior to building permit issuance
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☐Police Department approval on the corrected/final set of drawings (647-5840).
☐Public Works Agency approval (647-5039).
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).
Applicant must pick up red marked sheet from the City prior to resubmittal and return the marked up set with resubmittal
PLAN REVIEW COMMENTS:
Sheet A-1
Project information:
Revise occupancy to A3
Revise applicable code to 2022 CBC
Sheet S1
General comment:
Remove steps (detail 3/S1 and on foundation plan, section A) or provide accessible ramp comply with 11B-405 and provide warning curb comply with 11B-303.5
Design parameter
Include medication factor, Rp & amplification factor ap, on plan per calculation
Revise total design weight. Design weight is 55116 lb per calculation
Detail 2
Provided post-installed anchor bolt (item #2) minimum embedment depth into footing
Per calculation footing based depth below soil surface starts at 1.5 ft. Revise 8” as indicated per detail to 1.5 ft
Per calculation footing depth is 24 inches deep. It is consider from footing base depth per item 2aii (above). Revise footing depth
Detail note #4, specify minimum 7 rebar required per calculation
Foundation Plan
Specify anchor bolt size, spacing and provide structural calculation for justification
Show line of footing based (detail 2/S1) on foundation plan
Red marked comment set is available to pick-up at the City Hall.(End of Comment)