HomeMy WebLinkAbout311306_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101117881
PROJECT ADDRESS:
1040 W MacArthur Blvd Unit# 23
PLAN CHECK ENGINEER:
Huang, GaryTEL:714
647-5862
EMAIL:
Ghuang@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/11/2024
INITIAL REVIEW
2/13/2024
EXPIRATION
7/9/2024
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
George Martinez
3.
TEL:
(714)533-7300
FAX:
VALUATION: $6,500.00
EMAIL:
George@mccservices-socal.com
FLOOD ZONE: X-0602320258J
GUIDELINES:
Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies
This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2022 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES)
The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws
All listed plan review comments must be adequately addressed before a building permit can be issued
Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
PLAN REVIEW COMMENTS:
Applicant shall address all the checked‘☒’ correction comments below before resubmitting plans to Building Safety for recheck.
☒1. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☐Police Department approval on the corrected/final set of drawings (647-5840).
☒Public Works Agency approval (647-5039).
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).
Sheet S2
Detail A: provide construction detail of (N) 6x beam to (E) 6x beam at deck level
[Comment not complete –
1. Provide connection for how (E) 4x to (N) 6x beam,
2. Provide connection for how does the (E) post connect to (N) and (E) floor beam]
Detail B: provide construction detail of (N) 6x beam to (E) 6x beam at roof level
[Comment not complete – provide connection for (E) 4x rafter to (N) 6x beam]
Sheet S4
Detail A: provide construction detail for how (N) 6x beam to (E) wall at each end of the deck at the deck level
[Comment not complete – detail 13/D1 does not fully represent the actual situation. The (N) beam should be fully bear on the post and it should be using column cap instead of T strap tie. Provide detail and show actual condition]
Detail B: provide construction detail for how (N) 6x beam to (E) wall at each end of the deck at the roof level
[Comment not complete – detail 13/D1 does not fully represent the actual situation. The (N) beam should be fully bear on the post and it should be using column cap instead of T strap tie. Provide detail and show actual condition]
Sheet D1
Detail 6: Provide connection from roof rafter to 6x10 or indicate the (E) connection
[Comment not resolve – provide connection. Updated drawing does not show the connection]
Detail 11:
Tongue and groove does not have the shear value to transfer lateral loads per SDPWS. Provide plywood diaphragm and indicate plywood thickness and nailing pattern
[Comment complete]
Provide connection from floor joist to bearing wall
[Comment not resolve – provide connection from floor joist to bearing wall]
Detail 18: provide connection for 4x floor joist to (N) 6x beam
[Comment resolved]
Prior to submit the hard-copy drawings for approval and permit issuance. It is at applicant’s discretion, as an option, to submit a full-set electronic drawing (in pdf format) for a courtesy review. Please include the original red-marked comment drawing set, red-marked calculation, and all supporting document (revised calculation, etc.) for an expedite review.
Red marked comment set is available to pick-up at the City Hall.(End of Comment)