HomeMy WebLinkAbout322770_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101121585 PROJECT ADDRESS: 2530 S Birch St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: II B, SPK OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/14/2024 INITIAL REVIEW 11/18/2024 EXPIRATION 5/13/2025 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Sosi Bardakjian 3. TEL: (714)496-3095 FAX: VALUATION: EMAIL: sosi@gnkauto.com FLOOD ZONE: X-06059C0278J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process.Sheet A-0: Please transfer the handwritten cloud area onto the electronic file prior to printing for resubmittal. Professional engineer steam/seal: Please provide updated engineering seal/stamp with a valid expiration date. Provide wet stamp, signature and signing date. Electronic stamp may be allowed but cannot be reproduced or scanned. Sheet A-1: Detail 6 – Accessible All-Gender restroom plan Please remove the existing bidet to provide minimum floor clearance for the toilet. Toilet location shall be located at a distance of 17”-18” (not 16”-18”), measured from the centerline of the fixture to the adjacent wall.