HomeMy WebLinkAbout324156_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101122044
PROJECT ADDRESS:
2720 S Orange Ave
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/7/2025
INITIAL REVIEW
1/30/2025
EXPIRATION
7/6/2025
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Arde Shirazi
3.
TEL:
(949)383-5211
FAX:
VALUATION: $42,000.00
EMAIL:
arde@twinstepsarch.com
FLOOD ZONE: X-06059C0278J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2022 California Residential Code (CRC); 2022 California Building Code (CBC); CMC = 2022 California Mechanical Code; CPC = 2022 California Plumbing Code; CEC = 2022 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
Sheet AS 400. Access aisles shall be marked with a blue painted borderline around their perimeter.
Sheet AS 400.Cross-reference Parking identification sign detail C2/AS500 and tow-away sign detail C3/AS500 into the applicable location on the site plan.
Sheet AS 400.Signs identifying van parking spaces shall contain additional language or an additional sign with the designation “van accessible.” Signs shall be 80 inches minimum above the finish floor or ground surface measured to the bottom of the sign.
Sheet AS400. Provide detectable warning details on the architectural drawings and cross-reference into the site plan.
Sheet AS 400.Note on plan. Detectable warning surfaces shall be yellow and approximate FS 33538 of Federal Standard 595C.
Sheet AS400. 24” minimum maneuvering clearance is required on the pull side of the exterior door of the building. Only 18” provided on the design. Please revise.
Sheet AS400. Provide pedestrian gate specification. Minimum 36” clear opening width is required at the gate when open.
END OF COMMENTS