HomeMy WebLinkAbout326714_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101122820
PROJECT ADDRESS:
4012 W Garry Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
B, F-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
3/11/2025
INITIAL REVIEW
4/28/2025
EXPIRATION
9/7/2025
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Brad Kenson
3.
TEL:
(949)228-5687
FAX:
VALUATION: $35,000.00
EMAIL:
brad@fastrackpower.com
FLOOD ZONE: X-06059C0258J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Public Works Agency approval (647-5039)
- County of Orange Health Department approval on the corrected/final set of drawings ((714)433-6000)Sheet TS: Please remove note “NOT FOR CONSTRUCTION” on all plan sheet for plan review and approval. Plans shall be stamped, signed and dated by the architect of record. On the plan, please specify the business type and use of the tenant space. Sheet CG-1 through CG-3: Please provided updated Calgreen Sheets for the July 1st, 2024 Supplement. Please check/mark in “Y” or “N/A” for each Sections. Sheet ST1.0: It appears that the accessible route on the North side (right) of the building was not accurate. Please coordinate with the enlarged detail ST1.1. Revise plan to show concrete walkway outside of the building element (wall/columns). Sheet ST1.1: Please revise detail 10 to show concrete curb separating the walkway and parking space. Show curb ramp. Detail 10 was not consistence with the site plan. Please coordinate and revise plan according. The accessible path of travel shall be match. Detail 10: Revise detail to provide/show 5-ft maneuver space on the pull side of door.Detail 10: Provide wheel-stop on the parking spaces adjacent to the accessible path of travel so that the parked car would not project into the require accessible route. Sheet A0.1: Please coordinate with site plan and detail 10/ST1.1 for accessible entrance on the north side of the building (right side). Existing restroom locate at gridline B: one of the restroom appear not complying with the accessibility requirement. Please provide enlarged floor plan with the accurate dimensions to show compliance with the accessibility requirement (Chapter 11B, Division 6). Sheet ID1.0:Wall Type: Wall W2 – referenced to sheet ID2.3 for wall details was not applicable. Please coordinate and revise references accordingly. Door D1: Note referenced to sheet ID2.3 for door schedule was not applicable. Please coordinate and revise plan accordingly. General Note #4: Please revise note to specify 2022 CBC / 2021 IBC. (End of Comment)