Loading...
HomeMy WebLinkAbout327530_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101123137 & 101123165 PROJECT ADDRESS: 3721 & 3723 S Bristol St PLAN CHECK ENGINEER: Lo, JonathanTEL:714 647-5822 EMAIL: Jlo@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 4/3/2025 INITIAL REVIEW 4/14/2025 EXPIRATION 9/30/2025 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Khanh Nguyen 3. TEL: (714)443-1668 FAX: VALUATION: $1,500.00 EMAIL: pioneerock@gmail.com FLOOD ZONE: X-06059C0259J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5822 for an appointment. The applicant shall obtain clearances/approvals for the following after obtaining approval from Building and Safety Division, prior to building permit issuance (CHECKED BOXES REQUIRED ONLY): ☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. ☐Public Works Agency approval (647-5039). ☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). ☐Police Department approval on the corrected/final set of drawings (647-5840). ☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work. ☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. ☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).Comments have been provided on drawing and calculation hard copies in relation to all comments below. Applicant must pick up red marked sets from city prior to resubmittal and return marked up set with resubmittal.DocumentationProvide party responsible for drawings on Title Block including company name, contact info, and designer name. Typ all sheets.Revise address on title block with affected addresses only (3721 and 3723). Typ all sheets.DrawingsSheet A1 Provide the following design data on the first sheet (R106.1.1) ☒Sheet Index ☒Occupancy groups for each unit ☒Type of construction ☒Automatic Fire Sprinkler (YES or NO) ☒Number of stories. ☒Flood Zone: X ☐Flood Zone: A ☐Flood Zone: AE ☐Floor area per occupancy group, including the existing structure(s) ☒Construction shall comply with the 2022 CRC, CBC, CPC, CMC, CEC, California Green Building Code, and California Energy Efficiency Standards Code editions. Provide a project description with a complete and detailed scope of work on the cover sheet of the plans.Sheet A3Show path of travel distance in new separate units to exiting on plan.Provide plumbing occupant load to required fixture calculation on drawing set.Verify note on each unit “(N) Sales”. It is unclear if occupancy to be permitted.Verify if existing booths are to remain or be demolished as shown on the Floor Plan. Verify how new wall will interact with existing booths as shown on planSpecify room use in room south of existing conference room in 3721 Bristol.(End of Comment)