HomeMy WebLinkAbout328369_1_Corrections.docxPLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101123439 PROJECT ADDRESS: 1010 N Tustin Ave PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 4/23/2025 INITIAL REVIEW 6/2/2025 EXPIRATION 10/20/2025 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Phil Stien 3. TEL: (909)222-2601 FAX: VALUATION: $40,000.00 EMAIL: phil@matlockdb.com FLOOD ZONE: X-06059C0164J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance - Information Technology equipment rooms require a completed electrical plan check prior to issuance of the building permit to ensure compliance with the 2022 California Electrical Code (CEC) Article 645, Electronic Computer/Data Processing Equipment. CEC Article 645 may require fire-rated walls, floors, and ceilings for the computer room(s). For additional information, contact Mr. Scott Davis, Electrical Plan Check at (714) 647- 5822.Sheet T-1, Scope of Work: Reminder - Please update scope work in the electronic file prior to reprinting. Sheet A0.0: For clarity, please show property line between the worship building and the north parking lot. Sheet A0.0: It appears that there was only one accessible parking stall located at the north side of the worship center building. Please verify and revise plan accordingly. Sheet A2.0: On the plan, please show an accessible route from the one accessible parking stall to the building entrances. Sheet A2.0: Provide detail for the accessible parking. Show all required dimensions, marking and signage. Sheet A2.0: On the plan, please show an accessible route from the proposed trash enclosure to building(s) where the trash enclosure is serving. Sheet A2.0: New walkway with the slope of 8% ramp - Please revise plan to provide 5% maximum slope; otherwise, provide ramp details complying with Section 11B-405. Sheet A2.0, zero curb facing the existing north side driveway/parking: Please provide/show truncated dome along the zero curb. Sheet A2.1: Pedestrian gatePlease provide elevation the push side to show smooth surface for the portion locate within 10” from the working surface. Door/gate hardware: Please show openable parts of such hardware shall be 34 inches minimum and 44 inches maximum above the finish floor or ground.Sheet A2.1, Pedestrian gate: Please provide the following notes on the plan – Egress doors/gates shall be readily openable from the egress side without the use of a key or special knowledge or effort. (1010.1.9) The force for pushing or pulling open a door shall be 5-lb maximum. Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. Sheet A3.0, Enlarged Plan 1: Please show 24” clear from the door/gate trike edge, on the pull side. Structural calculation/design was not provided for the trash enclosure and roof cover structure. Please provide structural calculation and details for the trash enclosure and roof structure. Please coordinate with details provided on sheet A3.0. Provide calculation for CMU wall and footing Provide calculation for wood beams Provide calculation for post connection to CMU wall. Detail 3/A3.0: Show minimum embedment of post base to CMU wall. Verify with structural calculation. (End of Comment)