HomeMy WebLinkAbout329270_3_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101123710
PROJECT ADDRESS:
3700 W Segerstrom Ave Unit# B
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812
EMAIL:
Kahangian@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/15/2025
INITIAL REVIEW
5/23/2025
EXPIRATION
11/11/2025
RECHECKS:
1. 6/23/25
PROJECT APPLICANT CONTACT PERSON:
2.
Saeid Shantiyai
3.
TEL:
(909)860-1010
FAX:
VALUATION: $50,000.00
EMAIL:
sshantiyai@ladesigngroup.net
FLOOD ZONE:
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.CBC Sections A106.1 and A106.3.4.1, All drawings and supporting documents shall be prepared, stamped and signed by a California licensed architect or registered civil engineer.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceSubmit a signed copy of the contract showing labor and materials for all work to be done under the subject building permit application. The plan check engineer may accept the contract price as the valuation of improvements for unique/unusual projects in lieu of using a cost per square foot basis.Provide the following:Ok 6/23/25
- Provide a fully dimensioned site plan on each set of plans.
- Disabled access compliance must be shown on the site plan.Provide path of travel from the parking to the altered area. Ok 6/23/25Sheet A1.01, Show exits and entrances doors on the site plan. Pending 6/23/25, remove unpermitted gates and fences , keynotes #4 and 32.Sheet A1.01 remove “ Proposed Use for unit B “.OK 6/23/25Sheet AD2.01, please verify where the stairways are connected to. Is there mezzanine or second floor.OK 6/23/25Provide detail for in filling the skylights and roof mounted equipment openings.OK 6/23/25Sheet Ad2.01, keynote # 5 , Provide detail for rollup door infill .