HomeMy WebLinkAbout330009_3_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101123939
PROJECT ADDRESS:
2730 S Harbor Blvd Unit# J
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812
EMAIL:
Kahangian@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/9/2025
INITIAL REVIEW
6/15/2025
EXPIRATION
12/6/2025
RECHECKS:
1.7/30/25
PROJECT APPLICANT CONTACT PERSON:
2.
Michelle Vorachack
3.sdfdfww
TEL:
(949)679-6456
FAX:
VALUATION: $15,000.00
EMAIL:
plancheck@coldesigngroup.com
FLOOD ZONE: X-06059C0258J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide the following:Ok7/30/25
- Disabled access compliance must be shown on the site plan.Is there any elevator in the building?Ok7/30/25Provide dimension and signage detail for existing standard and van accessible parking to show comply with accessibility.Ok7/30/25Show all entrances and exit doors on the siteplan.Ok7/30/25Provide typical section view detail of all new partitions and ceilings showing:Ok7/30/25
- Heights of partition, suspended ceiling, structure above.Sheet D-1, detail 4, show spacing for woodscrew. Show bottom track gauge.Ok7/30/25Provide complying exiting plan for the area.Ok7/30/25Sheet A.03, Verify if door in room 103 is an exit door.Ok7/30/25CBC Section 1022.2.2., Exterior exit doors shall lead directly to the exit discharge or the public way.Ok7/30/25Provide on the drawings a complete door schedule, showing:Ok7/30/25
- Door sizes (CBC Sections 11B-404)
- Hardware complying with exiting and disabled accessibility requirement.CBC Section 11B404.2.7, Hand-activated door opening hardware shall be centered between 34” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction.Ok7/30/25CBC Section 11B404.2.9, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automaticdoor operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds. Ok 7/30/25Exit illumination and exit sign requirements in accordance with CBC Section 1013 shall be shown on the drawings. Be specific as to the type of exit signs to be installed.Pending 7/30/25, show inside the unit.Tactile exit signs shall be required at the following locations:. Ok 7/30/25
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”
- Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be
identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN”“EXIT STAIR UP”
- Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Section 11B-202.4
- An accessible entrance
- An accessible route to the altered area
- Accessible restroomsPending 7/30/25 Note on the drawings doesn’t comply
- Accessible telephone (if any)
- Accessible drinking fountains, and
- Parking, signage and alarmsIf a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 11B-247.1.2.5. Ok 7/30/25CBC Section 11B-208.2.4 One in every six accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible as required by Section 11B502. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. Ok 7/30/25Provide dimension and signage detail for existing standard and van accessible parking to show comply with accessibility.. Ok 7/30/25Show complete second floor and show location of the bathrooms.. Ok 7/30/25Sanitary facilities serving the area of new work shall be disabled accessible. Revise the drawings to show compliance with CBC Section11B-603 and 11B-604.3.1. Ok 7/30/25Provide completely dimensioned floor plans, elevations and sections of sanitary facility insuring wheelchair clearances complying with CBCSection11B-603 and 11B-604.3.1Pending 7/30/25 Make a note on the drawingsShow breakroom sink complies with accessibility. Pending 7/30/25, new work shall comply , provide detail.Complete the attached Disabled Accessibility Documentation Form. Ok 7/30/25