HomeMy WebLinkAbout332297_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101124606
PROJECT ADDRESS:
120 W Carriage Dr Unit# H
PLAN CHECK ENGINEER:
Huang, GaryTEL:714
647-5862
EMAIL:
Ghuang@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/8/2025
INITIAL REVIEW
8/16/2025
EXPIRATION
2/4/2026
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
YosiRachamim
3.
TEL:
(747)955-7655
FAX:
VALUATION: $25,000.00
EMAIL:
info@look-wow.com
FLOOD ZONE: X-06059C0278J
GUIDELINES:
Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies
This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2022 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES)
The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws
All listed plan review comments must be adequately addressed before a building permit can be issued
Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
Applicant shall obtain clearance/approvals from following departments after obtaining approval from Building and Safety Division, prior to building permit issuance
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☐Police Department approval on the corrected/final set of drawings (647-5840).
☒Public Works Agency approval (647-5039).
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).
Applicant must pick up red marked sheet from the City prior to resubmittal and return the marked up set with resubmittal
PLAN REVIEW COMMENTS:
Sheet A-1
Insert the handwritten note in scope of work into the typed note
Note on plan: Mechanical, electrical and plumbing are not part of this plan review and approval. MEP are subject to building field inspection.
Please update sheet index including each structural sheet and the Title 24 energy calculation
Sheet S1.1
EOR to update seismic coefficient per calculation
Sheet S2.1
Floor Framing Layout, note #5:
specify manufacture and model of post installed screw anchor bolt.
EOR should consider critical edge distance per manufacture’s ICC report. where screw anchor is used less than the critical edge distance, a reduction of bolt capacity shall be evaluated. EOR to provide calculation justify of post installed screw anchor for tension due to the reduced for shear wall length and edge distance.
Post installed anchor design and their attachment in both shear and tensile loading shall comply with ACI section 17.10.5.3 and section 17.10.6.3.
Prior to submit the hard-copy drawings for approval and permit issuance. It is at applicant’s discretion, as an option, to submit a full-set electronic drawing (in pdf format) for a courtesy review. Please include the original red-marked comment drawing set, red-marked calculation, and all supporting document (revised calculation, etc.) for an expedite review. (End of Comment)