HomeMy WebLinkAbout338010_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101126361
PROJECT ADDRESS:
2020 E First St
PLAN CHECK ENGINEER:
Lo, JonathanTEL:714
647-5822
EMAIL:
Jlo@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/28/2026
INITIAL REVIEW
2/24/2026
EXPIRATION
7/27/2026
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Efrem Joelson
3.
TEL:
(949)299-3848
FAX:
VALUATION: $11,500.00
EMAIL:
efrem.joelson@meritagehomes.com
FLOOD ZONE: X-06059C0277J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5822 for an appointment.
The applicant shall obtain clearances/approvals for the following after obtaining approval from Building and Safety Division, prior to building permit issuance (CHECKED BOXES REQUIRED ONLY):
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☒Public Works Agency approval (647-5039).
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☐Police Department approval on the corrected/final set of drawings (647-5840).
☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).Comments have been provided on drawing and calculation hard copies in relation to all comments below. Applicant must pick up red marked sets from city prior to resubmittal and return marked up set with resubmittal.DocumentationAdd address to building on cover sheet and title block on all sheets.DrawingsSheet C1Grading plan used as reference only is not to be used for approved construction document with this drawing set by the Building and Safety Department. However, the Building and Safety Department reviews all site accessible code requirements per Chapter 11B. If grading sheet is to be utilized for accessibility construction, it may not be for reference only. Else, architect to provide full site plan with site accessible requirements shown. Sheet shall be stamped and signed by professional taking responsibility of all code required items. Initial review of Grading Sheet has been done for accessibility, additional comments may occur.Add full detailed Scope of Work.Sheet A-1Interior door location to office does not match shell building drawing set for proposed Plan 1638X.2 Adaptable. It is unclear if door and walls for sales office are temporary or proposed to remain. Please identify all proposed temporary items on plans.Sheet Grading PlanProvide accessible sign requirements, referencing City Standard does not suffice. Provide temporary bathroom information and accessibility.Provide accessible route from public access way to sales office.(End of Comment)