HomeMy WebLinkAbout337067_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101126074 PROJECT ADDRESS: 1207 S Center St PLAN CHECK ENGINEER: Huang, GaryTEL:714 647-5862 EMAIL: Ghuang@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/24/2025 INITIAL REVIEW 1/9/2026 EXPIRATION 6/22/2026 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. James Mac 3. TEL: (714)482-5809 FAX: VALUATION: $80,000.00 EMAIL: ad.plandesign@gmail.com FLOOD ZONE: X-06059C0257J GUIDELINES: Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2022 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES) The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws All listed plan review comments must be adequately addressed before a building permit can be issued Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. Applicant shall obtain clearance/approvals from following departments after obtaining approval from Building and Safety Division, prior to building permit issuance ☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. ☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). ☐Police Department approval on the corrected/final set of drawings (647-5840). ☒Public Works Agency approval (647-5039). ☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. ☒School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work. ☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). Applicant must pick up red marked sheet from the City prior to resubmittal and return the marked up set with resubmittal PLAN REVIEW COMMENTS: Sheet A1: Note on plan: Mechanical, electrical and plumbing are not part of this plan review and approval. MEP are subject to building field inspection. Exterior walls without Automatic Residential Fire Sprinkler – (Table R302.1(1)) where Provide construction detail for exterior walls located less than 5-ft from a property line shall be of one-hour construction. Provide construction detail for eaves projection – Provide one-hour protection on the underside of eave when eaves projected into the 5-ft of fire separation distance. Sheet A2 Proposed floor plan: provide overall dimension, column spacing for the (N) porch Proposed roof plan: provide the extend of the (N) roof construction Sheet A3 Detail 5: Remove non-bearing wall detail and reference structural drawings which it had already shown Sheet A4 Identify ceiling height on plan for the new addition area Sheet SD2 Detail 8: specify/ reference detail on plan where occurs(End of Comment)