HomeMy WebLinkAbout339787_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101126914, 16-18
PROJECT ADDRESS:
320 S Orange Ave
PLAN CHECK ENGINEER:
Huang, GaryTEL:714
647-5862
EMAIL:
Ghuang@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
U, R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
3/20/2026
INITIAL REVIEW
4/21/2026
EXPIRATION
9/16/2026
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Eric Pennington
3.
TEL:
(714)309-5843
FAX:
VALUATION: $9,000.00
EMAIL:
eric@penningtonTNC.com
FLOOD ZONE: X-06059C0276J
GUIDELINES:
Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies
This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2025 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES)
The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws
All listed plan review comments must be adequately addressed before a building permit can be issued
Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
Applicant shall obtain clearance/approvals from following departments after obtaining approval from Building and Safety Division, prior to building permit issuance
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☐Police Department approval on the corrected/final set of drawings (647-5840).
☐Public Works Agency approval (647-5039).
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).
Applicant must pick up red marked sheet from the City prior to resubmittal and return the marked up set with resubmittal
PLAN REVIEW COMMENTS:Sheet 1Update building occupancy classification to R-2Sheet 3 Provide construction detail for how (N) 5 ¼ x 16 psl is connected to (E) 3” pipeVerify general project information of the green building standard code. Delete if not applicable Update the plumbing fixture rate; delete if not applicable to project
Water closet – 1.28 gallon per flush
Shower head – 1.8 gallons per minute at 80 psi.
Lavatory faucets – 1.2 gallon per minute at 60 psi.
Kitchen faucet – 1.8 gallon per minute at 60 psi.Sheet 5Provide construction detail for wall infill under the (N) window sillCoordinate guardrail height between details 1, detail 3, and detail 4T-24Provide updated Title 24 based on 2025 California Building Code, typical for all units Provide updated single-family residential mandatory requirement summary complying with current building code cycle, or delete if it is not applicable Provide updated residential mandatory measure under current building code cycle, or delete if it is not applicable. (End of Comment)