Laserfiche WebLink
11 of 19 <br />Environmental Impact Report (EPD Solutions. 2020), reports in Appendix I, Table 8-2, that <br />the exterior traffic noise levels will range from 68.6 to 73.2 dBA CNEL. <br /> <br />As a result of the high outdoor noise levels, the current project will require the need for <br />mechanical supply of outdoor air ventilation air to allow for a habitable interior environment <br />with closed windows and doors. Such a ventilation system would allow windows and doors <br />to be kept closed at the occupant’s discretion to control exterior noise within building <br />interiors. <br /> <br />PM2.5 Outdoor Concentrations Impact. An additional impact of the nearby motor vehicle <br />traffic associated with this project, are the outdoor concentrations of PM2.5. According to <br />the Draft Environmental Impact Report (EPD Solutions. 2020), this Project is located in <br />South Coast Air Basin, which is a State and Federal non-attainment area for PM2.5. <br /> <br />An air quality analyses should to be conducted to determine the concentrations of PM2.5 in <br />the outdoor and indoor air that people inhale each day. This air quality analyses needs to <br />consider the cumulative impacts of the project related emissions, existing and projected <br />future emissions from local PM2.5 sources (e.g. stationary sources, motor vehicles, and <br />airport traffic) upon the outdoor air concentrations at the project site. If the outdoor <br />concentrations are determined to exceed the California and National annual average PM2.5 <br />exceedence concentration of 12 µg/m3, or the National 24-hour average exceedence <br />concentration of 35 µg/m3, then the buildings need to have a mechanical supply of outdoor <br />air that has air filtration with sufficient PM2.5 removal efficiency, such that the indoor <br />concentrations of outdoor PM2.5 particles is less than the California and National PM2.5 <br />annual and 24-hour standards. <br /> <br />It is my experience that based on the projected high traffic noise levels, the annual average <br />concentration of PM2.5 will exceed the California and National PM2.5 annual and 24-hour <br />standards and warrant installation of high efficiency air filters (i.e. MERV 13 or higher) in <br />all mechanically supplied outdoor air ventilation systems. <br /> <br />