Laserfiche WebLink
c. An additional story is added above the second floor <br />regardless of fire areas or allowable area. <br />Exception: Group R-3 occupancies shall comply with Section <br />903.2.8. <br />(b) Section 903.3.5.3 Hydraulically calculated systems is hereby added as follows: <br />903.3.5.3 Hydraulically calculated systems. The design of hydraulically calculated fire <br />sprinkler systems shall not exceed 90% of the water supply capacity. <br />Exception: When static pressure exceeds 100 psi, and required by the Fire Code <br />Official, the fire sprinkler system shall not exceed water supply capacity specified by <br />Table 903.3.5. <br />Order fXXX 7 — 18 12/20/2022 <br />Page"1�o <br />