Laserfiche WebLink
10.4.3.2. Where fire service mains enter the building adjacent to the foundation, <br />the pipe may run under a building to a maximum of 24 inches, as measured from <br />the interior face of the exterior wall to the center of the vertical pipe. The pipe <br />under the building or building foundation shall be 304 or 316 stainless steel and <br />shall not contain mechanical joints or it shall comply with 10.4.3.2.1 through <br />10.4.3.2.4. <br />Section 29. Section 14-47 of the Santa Ana Municipal Code is hereby amended to <br />read as follows: <br />Sec. 14-47. -Appendices. <br />Appendix A is deleted in its entirety. <br />Appendix B is adopted in its entirety. <br />Appendix BB is adopted in its entirety. <br />Appendix C is adopted in its entirety. <br />Appendix CC is adopted in its entirety. <br />Appendix D is deleted in its entirety. <br />Appendix E is deleted in its entirety. <br />Appendix F is deleted in its entirety. <br />Appendix G is deleted in its entirety. <br />Appendix H is deleted in its entirety. <br />Appendix I is deleted in its entirety. <br />Appendix J is deleted in its entirety. <br />Appendix K is deleted in its entirety. <br />Appendix L is deleted in its entirety. <br />Appendix M is deleted in its entirety. <br />Appendix N is deleted in its entirety. <br />Appendix O is deleted in its entirety. <br />Ordinance No. NS-3032 <br />Page 27 of 29 <br />