LIGHT FIXTURE SCHEDULE
<br />FBAB535.037
<br />LIGHT FCRUFE
<br />SYMBOL
<br />TYPE
<br />LIGHT FIXTURE DESCRIPTION
<br />5
<br />WiG
<br />_
<br />Fl%NRE MOUNTING
<br />a
<br />Sc
<br />_
<br />$
<br />SINGLE HEAD LED FIXTURE, POLE MOUNTED AT F29'-7' ABOVE
<br />SI
<br />GRWNI. TYPE IV BISTRIWTION, PROVIDE TRUNNION MOUNT.
<br />CONCRCTE POLE ROUND 29'-1'TALL WITH ANTI -GRAFFITI COAi1NG
<br />884
<br />106
<br />POLE NOUNT, SEE POLE
<br />BASE DETAIL
<br />LED
<br />5000
<br />-
<br />-
<br />93529
<br />-
<br />PROVIDE ANTI -GRAFFITI COAT ON POLE BASE.
<br />g
<br />VISIONAIRE LIGHTING
<br />MBLx-I I-B-i4-256LC-10-5K-UNV-iN
<br />ANERON POLE 06B1-29
<br />3-03 REBAR, 210.
<br />FOUR III R BOLTS o
<br />EACH WITH iV0 NUTS
<br />AND WASHERS TO
<br />ANCHOR AND ALIGN
<br />POLE AND PER POLE m
<br />MANORACEURER'S
<br />SPECS.)
<br />CONDUIT, TYPICAL
<br />PER PLANS
<br />BASE PLATE ANB ANCHOR
<br />BOLTS FURNISH VI IN POLE.
<br />DRY PACK UNDER BASE
<br />I' RADIUS
<br />PROVIDE ANTI -GRAFFITI
<br />COATING
<br />. A➢E
<br />-IIF 6#5 VERTICAL REBAR
<br />AND p3 CIRCULAR TIES
<br />@ 12'O C.
<br />CONCRETE BASE
<br />-I (FT-4500 PSI)
<br />PROVIDE CONTINUOUS ID8 BARE COPPER) — R"ARERi, 36' MIN,
<br />6RCONDING-STRAP' DE CONDUCTOR
<br />IMBED DEPTH
<br />IN CONCRETE, PROVIDE CONDUCTOR,
<br />I 3' CLEAR
<br />COMPRESSION TYPE GROUND CLAMP ON i0 TIES
<br />ONE OF THE VERTICAL REBAR IN THE 30 DIAMETER
<br />POLE BASE CONNECT THE GROUNDING
<br />CONDUCTOR FROM THE REBAR OR ONE i2
<br />CLAMP TO THE GROUND -DUG INSIDE THE
<br />LIGHTING POLE HAND HOLE COVER.
<br />ALLOW A MINIMUM OF 24-INCHES OF q3 CIRCULAR TIES
<br />FREE -END' ABOVE TOP OF CONCRETE WITH I L/2 TURNS
<br />BASE
<br />FLUSH COMPOSITE BOLT
<br />19N COVER
<br />COURT POLE BASE DETAIL Nr<I121 PULL BOX DETAIL
<br />PANCRETE COLLAR
<br />AROUND BOX FRAME
<br />FLUSH WITH TIP OF BOX.
<br />COMPOSITE PILLBOX,
<br />CHRISTY FIBRELYTE
<br />RR09 10'x IS', DEPTH
<br />AS REWIRED.
<br />47Lf�XbJI�XN:1'Iwl
<br />GENERALNOTES
<br />THESES ➢RAVINGS AND NOTES ARE INTENDED TO
<br />OVER A COMPLETE INSTALLATION OF SYSTEMS THE
<br />OMISSION OR EXPRESSED REFERENCE TO ANY ITEM OF LA30R
<br />OR MATERIALS REQUIRED FOR THE PROPER EXECUTION OF THE
<br />VOW IN ACCORDANCE WITH PRESENT PRACTICE OF THE
<br />TRADE SHALL NOT RELIEVE THE CONTRACTOR FROM
<br />PROVIDING SUCH ADDITIONAL LABOR AND MATERIALS,
<br />THESE PLANS AND NOTES AND ALL WORK AND
<br />MATERIALS SHALL BE IN FULL ACCORDANCE WITH ALL LEGAL
<br />AND INDUSTRY REQUIREMENTS AND STANDARDS INCLUDING
<br />VI THOUT LIMITATION THE FOLLOWING
<br />o. CALIFORNIA CURE OF REGULATIONS TITLE 24, PARTS I AND
<br />2 (CALIFORNIA BUILDING CODE), 2019 EDITION,
<br />H. CALIFORNIA CODE OF REGULATIONS TITLE 24, PART 3
<br />(CALIFORNIA ELECTRICAL CODE), 2019 EDITION.
<br />c. CALIFORNIA CODE OF REGULATIONS TITLE 24, PART 6
<br />(CALIFORNIA ENERGY CODE), 2019 EDITION
<br />d. CALIFORNIA COEE OF REGULATIONS TITLE 24, PART 9
<br />(CALIFORNIA FIRE CODE), 2U19 EDITION,
<br />P, OTHER REGULATING AGENCIES WHICH MAY HAVE
<br />AID HORITY OVER ANY PORTION OF THE WORK, INCLUDING
<br />THE STATE OF CALIFORNIA DIVISION OF INDUSTRIAL
<br />SAFETY, AND THOSE CODES AND STANDARDS LISTED IN THESE
<br />NOTES AND SPECIFICATIONS.
<br />P. THC ELECTRICAL SYSTEMS FUNCTIONALITY STANDARDS
<br />SET FORTH IN TITLE 7 OF THE CALIFORNIA CIVIL CODE
<br />(THE 'RIGHT TO REPAIR ACT').
<br />g, THE MANUFACTURER'S REQUIREMENTS OR RECOMMENDATIONS
<br />FIR ANY INCORPORATED PRODUCTS.
<br />h, IN C MOST CURRENT APPROVED ISSUES OF ANY NOTED
<br />SPECIFICATIONS, CODES AND STANDARDS, INCLUDING
<br />SUPPLEMENTS, UNLESS NOTED OTHERWISE
<br />THE PLANS REPRESENT ONLY THE FINISHED ELECTRICAL
<br />SYSTEMS, ANB ARE NOT INTENDED TO INDICATE OR REQUIRE ANY
<br />CONSTRUCTION MEANS, METHODS TECHNIQUES, SEQUENCES OR
<br />PROCEDURES.
<br />IN USING THE PLANS FOR BIDDING OR CONSTRUCTION
<br />PURPOSES, THE CONTRACTOR IS REQUIRED TO REVIEW ALL
<br />OF THE PROJECT'S CONSTRUCTION DOCUMENTS AS A WHOLE
<br />IN ORDER TO IDENTIFY ALL REQUIREMENTS THAT DIRECTLY OR
<br />NDIRECTLY AFFECT ITS PORTION OF THE ELECTRICAL WORK,
<br />EVEN REQUIREMENTS LOCATED IN SECTIONS DESIGNATED
<br />AS APPLICABLE TO UTTER TRADES. IN CASE OF CONFLICTS,
<br />THE CONTRACTOR SHALL EITHER OBTAIN DIRECTION FROM
<br />AN APPROPRIATE OWNER REPRESENTATIVE OR OTHER-
<br />WISE APPLY THE MORE STRINGENT REQUIREMENT.
<br />IN INTERERETATING THE PLANS, THE FOLLOWING GENERAL
<br />RULES APPLY:
<br />o. WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER
<br />SCALED DRAWINGS,
<br />b, SCALED DIMENSIONS AND GRAPHICALLY SHOWN LOCATIONS
<br />ARE TO BE CONSIDERED ONLY APPRnXINATIC FIELD VERIFY
<br />DIMENSIONS PRIOR TO BID.
<br />c. BECAUSE TRE PLANS ARE INTENDED TO SET FORTH THE
<br />REQUIREMENTS FOR COW TRUCTION IN ONLY AN INDUSTRY -
<br />STANDARD LEVEL OF OLNLITY AND DETAIL, AND THEREFORE
<br />ARC INTENDED TO BE SUPPLEMENTED BY APPROPRIATE
<br />REAUESTS FOR CLARIFICATION AND INFORHAT ION, ERRORS
<br />AND OMISSIONS AND TO BRING THESE ERRORS AND
<br />OMISSIONS TO THE ATTENTION OF AN APPROPRIATE OWNER
<br />REPRESENTATIVE IN A TIMELY MANNER AND ASSUMES THE
<br />RISK OF THE CONSEQUENCES OF FAILING TO DO SO BEFORE
<br />BIDDING OR OTHERWISE PROCEEDING,
<br />d, THC CONTRACTOR SHALL REVIEW AND VERIFY ALL DIMENSIONS
<br />PRIOR TO STARTING CONSTRUCTION, AND NOTIFY THE
<br />ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES OR
<br />INCONSISTENCIES,
<br />SOBOUITTALS WILL BE REVIEWED BY THE ELECTRICAL ENGINEER,
<br />IF AT ALL, ONLY PURSUANT TO THE INDUSTRY -STANDARD
<br />PRDTOCDL SET FORTH IN III DOCUMENT ACLU AND IN NO
<br />EVENT WILL THE THE SUBMITTAL REVIEW PROCESS RELIEVE
<br />OR LESSEN THE SUBMITTING CONTRACTOR'S RESPUNSIBILITY
<br />FOR AN INAPPROPRIATE SUBMITTAL
<br />IN NO EVENT WILL ANY SITE VISITS BY THE ELECTRICAL
<br />ENGINEER CONCERN CONSTRUCTION MEANS AND METHODS OR
<br />CONSTRUCTION SAFETY, AND ALL SUCH MATTERS SHALL REMAIN
<br />THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
<br />COPIES OF THE THE PLANS PROVIDED IN ANY ELECTRONIC FORM
<br />ARE SUBJECT TO THE SAME PROVISIONS AS THE OTHER
<br />INSTRUMENTS OF SERVICE PREPARED BY OR ON BEHALF OF
<br />ELECTRICAL ENGINEER FOR THE PROJECT, INCLUDING WITHOUT
<br />LIMITATION TIE ENGINEER'S COMMON LAW, STATUTORY OR
<br />OTHER RESERVED RIGHTS, INCLUDING COPYRIGHTS. A RECIPIENT
<br />IS GRANTED AT MOST A TRANSFERABLE NONEXCLUSIVE LICENSE
<br />TO FIE E THE PLANS SOLELY FOR PROJECT PURPOSES AND
<br />NO RECIPIENT IS AUTHORIZED TO USE OR TO ALLOW THE USE OF
<br />ALL OR ANY PIRT IBM OF THESE PLANS FOR ANY OTHER PURPOSE,
<br />AND ANY USE FOR ANY OTHER PURPOSE
<br />URE O E WOULD
<br />CONSTITUTE
<br />ACTIONABL PLAGIARISM. ELECTRICAL CHIC WE
<br />PR VIES
<br />DOCUMENTS IN AN ELECTRONIC FORM ONLY IN ITS STANDARD
<br />FORMATS AN CONVENTIONS AND WITH NO GUARANTEE OF
<br />COMPATIBILITY WITH ANY RECIPIENT'S SOFTWARE OR HARDWARE
<br />AND ANY USE WITH OR CONVERSION TO OTHER FORMATS OR
<br />CONVENTIONS, OR THE USE WITH ANY PARTICULAR SOFTWARE
<br />OR HARDWARE: AT THE RECIPIENT'S SOLD RISK,
<br />9. LOCATIONS OF EXISTING UTILITIES ARE NUT SHOWN AND
<br />CONTRACTOR SHALL EXERCISE EXTREME CAUTION IN EXCAVATING
<br />AND TRENCHING ON THIS SITE TO AVOID EXISTING DUCTS,
<br />PIPING OR CONDUIT, ETC. AND TO PREVENT HAZARD TO
<br />PERSONNEL AND/OR BAA461 TO EXISTING UNDERGROUND
<br />UTILITIES OR STRUCTURES WHETHER OR NOT SHOWN AND
<br />INSTALLED BY ANY OTHER CONTRACTS. THE ENGINEER IS NOT
<br />RESPONSIBLE FOR THE LOCATION OF UNDERGROUND UTILITIES
<br />OR STRUCTURES WHETHER OR NOT SHOWN OR DETAILED BY ANY
<br />OTHER CONTRACTS, TIE CONTRACTOR SHALL IMMEDIATELY
<br />NOTIFY THE ENGINEER SHOULD SUCH UNIDENTIFIED CONDITIONS
<br />BE DISCOVERED. THESE DRAWINGS AND NOTES DO NOT INCLUDE
<br />NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY,
<br />10, REFER TO THE ➢RAVINGS AND SHIP DRAWINGS OF OTHER TRADES
<br />FOR ADDITIONAL DETAILS WHICH AFFECT THE PROPER
<br />INSTALLATION OF THIS VOW,
<br />II. THE ➢RAVINGS INDICATE, IN A DIAGRAMMATIC MANNER, THE
<br />DESIRED LOCATIONS AND ARRANGEMENT OF THE COMPONENTS OF
<br />ELECTRICAL WORK, DETERMINE EXACT CONDUIT ROUTING,
<br />CONDUIT BENDS, AUXILIARY JUNCTION BOXES, SUPPORTS
<br />AND UNDEFINED CONSTRUCTION DETAILS AS A JOB CONDITION
<br />TO BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE COO
<br />REQUIREMENTS. PROPER JUDGEMENT MUST BE ESPRIT SEE
<br />IN
<br />EXECUTING THE WORK SO AS TO SECURE THE BEST POSSIBLE
<br />INS ELATION IN THE AVAILABLE SPACE AND In OVERCOME
<br />LOCAL DIFFICULTIES DUE TO SPACE LIMITATIONS OR
<br />INTERFERENCE OF CONDITIONS ENCOUNTERED,
<br />12, IN THE EVENT CHANGES IN THE INDICATED LOCATIONS OR
<br />ARRANGEMENTS ARE NECESSARY, DUE TO DEVELOPED CONDITIONS
<br />IN THE BUILDING CONSTRUCTION OR REARRANGEMENT OF
<br />EQUIPMENT, SUCH CHANGES SHALL BE MADE WITHOUT COST
<br />PROVIDING THE CHANGE IS ORDERED BEFORE THE CONDUIT RUNS,
<br />ETC., AND VURK DIRECTLY CONNED TEE TO SAME IS INSTALLED
<br />AND NO EXTRA MATERIALS ARE REQUIRED.
<br />13. PROVIDE AL EQUIPMENT WITH ENCLOSURES LISTED IR LABELED
<br />FOR USE AND LOCATION WHERE SUCH LOUT PHENT IS INSTALLED,
<br />14. GROUNDING SHALL BE EXECUTED IN ACCURD4NCE WITH ALL
<br />APPLICABLE CODES AND REGULATIONS, BOTH OF THE STATE OF
<br />CALIFORNIA AND LOCAL AUTHORITIES HAVING JURISDICTION.
<br />15. PROVIDE 6F,OUWE WIRE IN EACH CONDUIT CONTAINING CIRCUITS
<br />FEEDING RECEPTACLES. THE CONDUIT SHALL NOT BE PERMITTED
<br />TO SERVE AS THE ONLY ELECTRICAL GROUND RETURN PATH,
<br />16. PROVIDE HANDLE TIES AT CIRCUIT BREAKERS TO
<br />SIMULTANEOUSLY BI SCONNECT ALL UNGROUNDED CONDUCTORS OF
<br />MULTI -WIRE BRANCH CIRCUITS WITH A SHARED NEUTRAL,
<br />17. UNLESS NOTED OTHERWISE ALL 120 VOLT NINEPINS OVER 100
<br />FEET SHALL BE 110 AA MINIMUM, OVER 175 FEET SHALL BE DB
<br />AVG MINIMA. ADJUST CON➢UHT SIZE ACCORDINGLY.SEE WIRE AND
<br />CABLE NOTE ON SHEET E-G 01 FOR ADDITIONAL INFORMATION
<br />18. NOTIFY TIE ARCHITECT IN WRITING WHEN INSTALLATION IS
<br />COMPLETE ANN THAT A FINAL INSPECTION OF THIS WORK CAN
<br />BE PERFORMED. IN THE
<br />EVENT BE CUTS IRE DEFICIENCIES
<br />ARE FOUND DURING THIS FINAL INSPECTION, THEY SHALL BE
<br />CORRECTED TO THE SATISFACTION OF THE AREHITECT BEFORE
<br />FINAL ACCEPTANCE CAN BE ISSUED,
<br />19. PANELBOARDS ARE EXISTING UNLESS NOTED OTHERWISE, NEW
<br />CIRCUIT BEAKERS SHALL BE THE SAME TYPE AND INTERRUPTING
<br />RATING AS EXISTING BREAKERS IN PANEL
<br />20, WHERE CIRW IT CHANGES OR ADDITIONS OCCUR IN PANELROARDS
<br />UPDATE PANEL DIRECTORY CARDS WITH NEW TYPE WRITTEN CARDS
<br />INDICATION DESCRIPTION OF ALL CIRCUITS,
<br />2L PERFORM CUTTING AND PATCHING OF CONCRETE/HARDSCAPE AREAS
<br />WHICH MAY BE REQUIRED FOR THE PROPER INSTALLATION AND/OR
<br />DEMOLITION OF ELECTRICAL WORK. PATCHING SHALL BE OF THE
<br />SAME MATERIAL, WORKMANSHIP AND FINISH TO ACCURATELY
<br />MATCH S
<br />U
<br />MONDING WORK TO SATISFACTION OF THE CITY
<br />REPRESENTATIVE.
<br />SYMBOL LIST
<br />ALL SYMBOL DESCRIPTIONS ARE SUBJECT TO MODIFICATION AS NOTED ON THE DRAWINGS. VERIFY EXACT LOCATIONS
<br />ANB HEIGHTS OF OUTLETS WITH ARCHITECTURAL INTERIOR ELEVATIONS PRIOR TO ROUGH -IN.
<br />E- DESIGNATION
<br />ADJACENT LINE INDICATES PANEL FRONT, ADJACENT BALLOON INDICATES PANEL
<br />_ DESIGNATION 'A', SEE DRAWING E-3 FIR PANEL SCHEDULE.
<br />o CIRCUIT BREAKER STATIONARY (NON-DRAWOUT), SECONDARY VOLTAGE,
<br />CONDUIT, INSTALLED CONCEALED IN VALE OR IN CEILING SPACE,
<br />1/2'C-2412 iH+B 3/4'C-6012
<br />�3/2'C-3812 F1'C-7 q1I
<br />/4C - 4 Ii{H-HFF 1' C - 8 Al2
<br />�H#FULL-3/4'' C - 5 MMI22 -HHPfH 1 1/4' C - 9 RIC
<br />— — — CONDUIT, INSTALLED CONCEALED IN OR UNDER FLOW OR BELOW GRADE, 3/4' CONDUCT MINIMUM,
<br />- --E- -- EXISTING RACEWAY
<br />9 HONERIR TO PANEL 'B' FOR CIRCUITS 1 1, 9 WITH SEPARATE NEUTRALS.
<br />+W'
<br />MDUNTIN6 HEIGHT TO CENTER LINE
<br />IG
<br />ISOLATED GROUND AND ISOLATED NEUTRAL
<br />OF DEVICE FROM FINISH FLOOR OR
<br />EXTERIOR GRADE
<br />J-DJX
<br />JUNCTION BOX
<br />O--
<br />KEY NOTE CALLOUT. REFER TO
<br />kYA
<br />KILOVOLT AMPERES
<br />CURESP RONDING NOTE IN
<br />GRAVING WHERE CALLOUT OCCURS.
<br />KN
<br />KILOWATT
<br />AFF.
<br />ABOVE FINISH FLOOR
<br />UAL
<br />LONG CONTINUOUS LOAD
<br />A.F.C.
<br />ABOVE FINISH GRADE
<br />LTG. LTS
<br />LIGHTING
<br />ARD
<br />AMERICAN WIRE GAUGE
<br />YCB
<br />MAIN CIRCUIT BREAKER
<br />OUP, A
<br />AMPERE
<br />MUD
<br />MAIN LUGS ONLY
<br />X.D.C.
<br />AMPERES INTERRUPTING
<br />NEC
<br />NATIONAL ELECTRICAL CODE
<br />CAPACITY (SYMMETRICAL)
<br />NM
<br />NOT IN CONTRACT
<br />CIAC.,00.
<br />CIRCUIT
<br />PH. or (C
<br />PHASE
<br />CB
<br />CIRCUIT BREAKER
<br />PAONDE
<br />FURNISH, INSTALL AND CONNECT,
<br />c
<br />CONDUIT
<br />REC. BECOME
<br />RECEPTACLE
<br />OECD
<br />CURRENT LIMITING CIRCUIT BREAKER
<br />ADS
<br />RIGID GALVANIZED STEEL
<br />C.O.
<br />CONDUIT ONLY,
<br />SE[ONAIBY
<br />600 VOLTS AND LESS
<br />CORM
<br />CONNECTED
<br />IYP
<br />TYPICAL
<br />Du
<br />DIAMETER
<br />UNDO.
<br />UNLESS NOTED OTHERWISE
<br />END
<br />ELECTRICAL METALLIC TUBING
<br />Y
<br />VOLTS
<br />IF
<br />EXHAUST FAN
<br />VA
<br />VOLT AMPERES
<br />(E)
<br />EXISTING EQUIPMENT TO REMAIN
<br />wP
<br />WEATHERPROOF
<br />f1A
<br />FULL LOAD AMPS
<br />w
<br />WIRE
<br />GM
<br />GROUND FAULT CIRCUIT INTERRUPTER
<br />NP
<br />SINGLE POLE
<br />GFP
<br />GROUND FAULT PROTECTION
<br />qP
<br />DOUBLE POE
<br />CAD
<br />GROUND
<br />3P
<br />TRIPLE PRE
<br />SHEET INDEX
<br />E-0 01 GENERAL NOTES, SYMBOL LIST, FIXTURE SCHEDULE AND DETAILS
<br />E-D 02 SINGLE LINE DIAGRAMS, PANEL SCHEDULES
<br />E-I.OI BASKETBALL COURT
<br />E-2. 01 PHOTOMETRIC PLAN
<br />E-3. 01 ELECTRICAL NOTES
<br />Underground Service Alert
<br />� wswllNn,cNllror„IA E
<br />FBA Engineering Nm�rw.BeDPIOw. j
<br />IDEA CBIlunaeYwNlq.
<br />* OR 'BO * „o NOTICE TO CONTRACTOR
<br />P
<br />��A'f,H-IF "' ������:w� rsvulol ss wicormucraa Acarr crs�iaNFls
<br />ADIGAIERi iICMETAWBIBffl, GALLBit AT1f/Si TWlOTONAB
<br />pREVISIONS REFERENCES ir EUPP€RW516x 04izO21 GENERAL NOTES, SYMBOL UST, FUTURE SCHEDULE AND DETAILS `-
<br />: ELECTRICAL ENGINEER
<br />NUMB A D E w PPAo fD N6, LLEN FNAH.AMK No xx-x -xx NN NN NAro --_ --N ---- --K DESIGNED: XX DRAM. CP CHECKED. RZ EL SALVADOR PARK BASKETBALL COURT LIGHTING j
<br />RDNS
<br />HE
<br />CEO TRUCTADILITY O FOR PROJECT LIMITS
<br />`v RU
<br />u AND REMCONSTRU TIO
<br />FOR CON6T DEDN:
<br />% PUBLIC WORKS AGENCY
<br />a aM/zozl
<br />JASDN CABAIEL PRINCIPAL CIYIL ENGINEER RCE N0.: 6296 CITY OF SANTA ANAL SNEFFN OF 1
<br />
|