Ordinance No. NS-XXX <br />Page 25 of 30 <br /> <br /> Section 5608.3 Application for Permit. A diagram of the grounds on <br /> which the display is to be held showing the point at which the fireworks are <br /> to be discharged, the fallout area based on 100 feet per inch of shell size, <br /> the location of all buildings, roads, and other means of transportation, the <br /> lines behind which the audience will be restrained, the location of all <br /> nearby trees, telegraph or telephone line, or other overhead obstructions <br /> shall be provided to OCFA. <br /> <br />Section 26. Section 14-39 of the Santa Ana Municipal Code is hereby amended <br />to read as follows: <br /> <br />Sec. 14-39 - Flammable and combustible liquids (Chapter 57). <br /> <br />Flammable and Combustible Liquids (Chapter 57) Adopt Chapter 57, as adopted <br />and amended by SFM. <br /> <br />Section 27. Section 14-40 of the Santa Ana Municipal Code is hereby amended <br />to read as follows: <br /> <br /> Sec. 14-40. - Flammable Gases and Flammable Cryogenic Fluids (Chapter <br />58). <br /> <br />Chapter 58 Flammable Gases and Flammable Cryogenic Fluids Adopt Chapter 58 <br />in its entirety as amended by SFM. <br /> <br /> <br /> <br />Section 28. Section 14-41 of the Santa Ana Municipal Code is hereby amended to <br />read as follows: <br /> <br /> Sec. 14-41 - Referenced standards (Chapter 80). <br /> <br /> (a) NFPA 13, 2022 Edition, Standard for the Installation of Sprinkler <br />Systems is hereby amended as follows: <br /> <br /> (1) Section 16.12.3.3 is hereby revised as follows: <br /> <br />16.12.3.3 Fire department connections (FDC) shall be of an approved type. The <br />location shall be approved and be no more than 150 feet from a public hydrant. <br />The FDC may be located within 150 feet of a private fire hydrant when approved <br />by the fire code official. The size of piping and the number of 2½” inlets shall be <br />approved by the fire code official. If acceptable to the water authority, it may be <br />installed on the backflow assembly. Fire department inlet connections shall be <br />painted OSHA safety red or as approved. When the fire sprinkler density design