<br />Ordinance No. NS-XXX <br />Page 28 of 30 <br />(4) Section 10.4.1.1 is hereby revised as follows: <br /> <br />10.4.1.1 All bolted joint accessories shall be cleaned and thoroughly coated with <br />asphalt or other corrosion-retarding material after installation. <br /> <br />Exception: Bolted joint accessories made from 304 or 316 stainless steel. <br /> <br />(5) Section 10.4.1.1.1 is hereby added as follows: <br /> <br />10.4.1.1.1 All bolts used in pipe-joint assembly shall be 316 stainless steel. <br /> <br />(6) Section 10.4.3.2 is hereby added as follows: <br /> <br />10.4.3.2. Where fire service mains enter the building adjacent to the foundation, <br />the pipe may run under a building to a maximum of 24 inches, as measured from <br />the interior face of the exterior wall to the center of the vertical pipe. The pipe <br />under the building or building foundation shall be 304 or 316 stainless steel and <br />shall not contain mechanical joints or it shall comply with 10.4.3.2.1 through <br />10.4.3.2.4. <br /> <br /> <br />Section 29. Section 14-47 of the Santa Ana Municipal Code is hereby amended to <br />read as follows: <br /> <br />Sec. 14-47. - Appendices. <br /> <br />Appendix A is deleted in its entirety. <br /> <br />Appendix B is adopted in its entirety. <br /> <br />Appendix BB is adopted in its entirety. <br /> <br />Appendix C is adopted in its entirety. <br /> <br />Appendix CC is adopted in its entirety. <br /> <br />Appendix D is deleted in its entirety. <br /> <br />Appendix E is deleted in its entirety. <br /> <br />Appendix F is deleted in its entirety. <br /> <br />Appendix G is deleted in its entirety. <br /> <br />Appendix H is deleted in its entirety. <br />