3. Outlets. Ail interior wet standpipes shall be equipped <br />with a one and one-half-inch (1 1/2") valve in each story, <br />including the basement or cellar of the building and located not <br />less than three feet (3') nor more than six feet (6') above the <br />floor. <br /> <br /> 4. Water supply. The wet standpipe system shall deliver not <br />less than 35 gallons of water per minute at not less than 25 <br />pounds per square inch residual pressure from each of any two <br />outlets flowing simultaneously for 30 minutes. When more than <br />one interior wet standpipe is required in the building, such <br />standpipes may be connected at their bases or highest points by <br />pipes of equal size. Where combination standpipes are installed <br />the one and one-half-inch (1 1/2") outlet system may be supplied <br />from the combination system with a two-inch (2") connecting line. <br /> <br /> 5. Pressure and gravity tanks. Pressure or gravity tanks <br />shall have a capacity sufficient to furnish at least 70 gallons <br />of water per minute for 30 minutes. Other such tanks shall be <br />located so as to provide not less than 25 pounds per square inch <br />residual pressure from each of two outlets flowing simultaneously <br />for 30 minutes. Discharge pipes from pressure tanks shall extend <br />two inches (2") from and into the bottom of such tanks. All <br />tanks shall be equipped with a manhole, ladder and platform, <br />drainpipe, water and pressure gauges, and a pressure relief valve. <br />Each pressure tank shall be tested in place after installation <br />and proved tight at a hydrostatic pressure 50 per cent in excess <br />of the working pressure required, but not less than 150 pounds per <br />square inch. W/aere such tanks are used also for domestic purposes, <br />the supply take-off for such purposes shall be located above the <br />required capacity of such tanks. Supply tanks shall be supported <br />on incombustible construction with not less than three-foot (3') <br />clearances over the top and under the bottom to adjacent construc- <br />tion. Approved pressure gauges shall be provided at pressure <br />tanks and at the air pump. <br /> <br /> 6. Fire pumps. Fire pumps shall be approved and shall <br />deliver not less than the required fire flow and pressure. Such <br />pumps shall be supplied with adequate power source and shall be <br />automatic in operation, Where the wet standpipe system is <br />supplied with water from the domestic supply of the building, <br />approved fire pumps shall not be required provided the domestic <br />pump used delivers the required fire flow. <br /> <br /> 7. Hose and hose reels. Each wet standpipe outlet shall be <br />supplied with a hose not less than one and one-half inches (1 1/2") <br />in diameter. Such hose shall be equipped with an approved <br />variable fog nozzle. An approved hose reel rack or cabinet <br />shall be located so as to make the hose accessible. The hose <br />reel rack or cabinet shall be recessed in the wall or protected <br />by suitable cabinets. <br /> <br /> 8. Connection to fire-extinguishing systems. Wet standpipe <br />systems may be supplied from a fire-extinguishing system comply- <br />ing with U.B.C. Standard No. 38-1-67 and shall be connected as <br />required in Section 3801. <br /> <br /> 9. Pressure reduction. Where the static pressure at any stand- <br />pipe outlet exceeds 100 pounds per square inch, an approved pres- <br />sure reduction device shall be permanently installed at the outlet <br />to reduce the water flow so that the nozzle pressure does not <br />exceed 80 pounds per square inch in accordance with Table No.38A. <br /> <br />Combination Standpipes <br /> <br /> Sec. 3805. (a) General. Ail combination standpipes shall <br />comply with the requirements of this Section. Design and in- <br />stallation shall be in accordance with U.B.C. Standard No. 38- <br />3-70. Where a combination standpipe system is installed in <br />accordance with this Section, a separate dry standpipe system <br />need not be installed. <br /> <br />-8- <br /> <br /> <br />