Laserfiche WebLink
ORDINANCE NS-2274 153 <br />Page 9 <br /> <br />hydrant. <br /> <br /> (b) Subsection 1003.2.3 of the Uniform Fire Code is amended <br />to read as follows: <br /> <br />1003.2.3 Places of Publlo Assemblage <br /> <br /> An automatic sprinkler system must be installed in any <br />portion of a building, whether newly constructed or preexist- <br />ing, in or into which the following use is initiated or <br />expanded: A place of public assemblage which provides for <br />the gathering together of one hundred (100) or more persons, <br />for such purposes as deliberation, education, instruction, <br />worship activities, entertainment, amusement, or the awaiting <br />of transportation, or in a dining or drinking establishment. <br /> <br /> (c) Subsection 1003.2.5 of the Uniform Fire Code is amended <br />to read as follows: <br /> <br />1003.2.5 Group H Oeoupaneies <br /> <br /> An automatic sprinkler system must be installed in any <br />portion of a building, whether newly constructed or preexist- <br />ing, in or into which the following use is initiated or <br />expanded: A Group H occupancy, as defined in the building <br />code of the city of Santa Ana. <br /> <br /> (d) Subsection 1003.2.9 is added to the Uniform Fire Code, to <br />read as follows: <br /> <br />1003.2.9 Special Hazards. <br /> <br /> An automatic sprinkler system must be installed in <br />buildings hereafter constructed, or when additions, alter- <br />ations, or repairs are such as to require the building to <br />comply with all the requirements of the building code of the <br />city of Santa Ana for new buildings, in either of the follow- <br />ing circumstances: <br /> <br />(a) <br /> <br />The building would require a fire flow of more than <br />three thousand five hundred (3,500) gallons per <br />minute if such system were not installed; <br /> <br />(b) <br /> <br />The building exceeds two (2) stories in height, <br />unless the building is designed for Group R occu- <br />pancies, as defined in the building code of the <br />City of Santa Ana, or is a building or structure <br />accessory thereto. <br /> <br />EXCEPTION: Open, freestanding parking structures, whether <br />or not such structures exceed two (2) stories in height, <br />constructed of noncombustible materials above grade, and <br /> <br /> <br />