Laserfiche WebLink
An approved products list is available through the Police <br />Department which supplies information on tested products approved <br />for use in compliance with the City's Building Security Ordinance. <br />Should you have any questions please call Community Services at 834- <br />4956. <br /> <br />Fire <br /> <br />The proposed 79 unit motel shall comply with all applicable <br />sections of the 1982 Uniform Fire Code, California <br />Administrative Code and City of Santa Aha Municipal Code which <br />shall include but not be limited to: <br /> <br />a) <br /> <br />All portions of exterior walls on the first floor shall <br />be within 150 feet of Fire Department access. Access <br />shall consist of two separate but interconnected means of <br />ingress and egress. Access shall be at least 20 feet in <br />clear width. A 40 foot outside and 20 foot inside radius <br />shall be provided. The total width must be continuously <br />paved to accon~odate 40,000 pounds and shall not exceed <br />the angle of departure for fire apparatus on any slope. <br />Access roadways shall have a vertical clearance of not <br />less than 13 feet 6 inches above the finished driveway <br />surface. <br /> <br />b) All portions of exterior walls on the first floor shall <br /> be within 15D feet of an accessible fire hydrant. <br /> <br />c) A manual alarm system per 1982 UFC Appendix III c shall <br /> be provided. <br /> <br />d) <br /> <br />Portable fire extinguishers {minimum 2-A:IO-B:C) shall be <br />provided. <br /> <br /> <br />