Laserfiche WebLink
· Cleaning <br />· Cleaning <br />· Cleaning <br /> <br />filter dryer. <br /> <br />orifice in the liquid feedline to coil <br />solenoid valves <br /> <br /> · Cleaning purge drum, checking and cleaning float valve; replacing gaskets <br /> <br /> · Checking heater operation <br /> <br /> · Checking all other components for proper condition and operation; recording <br /> pressure control set point <br /> <br />6. ' ~hecking the Condense~ for the following items: <br /> <br /> · Checking the water flow <br /> · Checking flow switch operation <br /> · Removing condenser head and inspecting end sheets <br /> · Mechanically brush cleaning ~ondenser water tubes <br /> <br />7. Checking the Cooler for the following items: <br /> <br /> · Checking the water flow <br /> · Checking flow switch operation <br /> · Checking refrigerant level <br /> <br />8. Checking the System for the following items: <br /> <br /> · Conducting a leak check and identifying leak sources for repairs <br /> · Recording condition of sight glasses <br /> · Checking the refrigerant cycle to verify the proper operating balance <br /> · Perform a vibration analysis and repod <br /> - · Perform a refrigerant analysis and report <br /> · Checking condenser wa[er and chilled water heat transfer <br /> <br />9. General items included: ....... _ <br /> <br /> · Repairing insulation removed for inspection and maintenance procedures <br /> <br /> · Cleaning equipment and surrounding area upon completion of work <br /> <br /> · Consulting with the.operator <br /> <br /> <br />