Laserfiche WebLink
• Battery standby operational <br />• AC power feeds correct <br />?. Annunciator Panels <br />• All indicators operate <br />• All auxiliary functions operate <br />• Labeling I correct and definitive <br />3. Peripheral Devices <br />• All indicating devices tested for alarm, including sprinkler switches <br />• All indicating devices tested for trouble, including sprinkler switches <br />• All signaling devices tested for operation <br />• All signaling devices tested for trouble <br />• Audibility test <br />4. Auxiliary Functions <br />• All door holders/closures operate <br />• City connection/monitoring center connection oper <br />• Elevator capture operates <br />• Fan controbUVAC shutdown operates <br />5. Standards <br />• Detectors properly spaced <br />• Proper detector placement <br />VI. AUDIT REPORT <br />Upon completion of the above inspection, a summary of the findings shall be provided to the <br />Facilities Maintenance Superintendent_ This report shall include detailed system background <br />information and a detailed list of the equipment inspected and tested. The report shall include <br />audibility and visual tests of all signaling devices. <br />If any repairs are required they shall be listed in the report. Upon owner request the Company <br />shall provide budget for any repair work. <br />All reports in this section shall comply with NFPA 72. Payment of services will not be processed <br />until this report is submitted in a timely manner and signed off by the Facilities Maintenance <br />Superintendent. <br />Rn,: smrzoos <br />