Laserfiche WebLink
OBJECTID Diameter <br />Notes <br />Text OperatedBy <br />Material <br />PipelinelD UpstreamManhole <br />DownstreamManhole <br />879 8" <br />J. Rodriguez <br />Vitrified Clay <br />H10-052 <br />H10-053 <br />1417 8" <br />EML caused by slope issues. Look into redesign, alot of hair and alot of grease <br />A. Morales <br />Vitrified Clay <br />N08-024 <br />N08-025 <br />1425 12" <br />J. Rodriguez <br />Vitrified Clay <br />N09-022 <br />N09-020 <br />1426 12" <br />J. Rodriguez <br />Vitrified Clay <br />N09-065 <br />N09-022 <br />1794 8" <br />J. Rodriguez <br />Vitrified Clay <br />N09-042 <br />N09-043 <br />1907 4" <br />Roots <br />Roots G. Montez <br />Vitrified Clay <br />C10-076 <br />C10-075 <br />2361 8" <br />alot of debrea <br />J. Rodriguez <br />Vitrified Clay <br />E10-001 <br />E10-002 <br />2371 6" <br />-owner problem at1712 n. spurgeon <br />J. Rodriguez <br />Vitrified Clay <br />E10-011 <br />E10-010 <br />2980 8" <br />90% sag from 270 to 290 feet intruding taps <br />J. Rodriguez <br />Vitrified Clay <br />F08-005 <br />F08-006 <br />3018 6" <br />Sag at 322' downstream of MH F09-013 causes EML, Grease Cleared <br />J. Rodriguez <br />Vitrified Clay <br />F09-013 <br />F09-014 <br />3941 6" <br />J. Rodriguez <br />Vitrified Clay <br />H10-056 <br />H10-052 <br />3960 6" <br />EML caused by hard change in pipe slope. Design issue. Need to look into relaying run.,heavy grease <br />J. Rodriguez <br />Vitrified Clay <br />Hll-007 <br />Hll-014 <br />4654 6" <br />bad sag hole in lateral red flag <br />J. Rodriguez <br />Vitrified Clay <br />J09-050 <br />J09-049 <br />5120 6" <br />J. Rodriguez <br />Felt Liner <br />K09-032 <br />K09-031 <br />5121 6" <br />lined around 10/29/2010 <br />J. Rodriguez <br />Felt Liner <br />K09-033 <br />K09-032 <br />5169 6" <br />multipule cracks in line grease and debris; pushed debris to Mcfadden <br />J. Rodriguez <br />Vitrified Clay <br />K10-038 <br />K10-037 <br />5177 6" <br />Sag in pipe or flat line at intersection of McFadden causes FOG accumulation <br />J. Rodriguez <br />Vitrified Clay <br />K10-051 <br />K10-050 <br />7339 6" <br />Very flat line, almost reverse slope. Need to raise starter and redesign segment / severe sag in pip <br />J. Rodriguez <br />Vitrified Clay <br />N08-032 <br />N08-021 <br />8964 8" <br />USED GRENADE AND FORWARD SPINNER HEAD,large sag in line near dwnstrm mh used vactor to reduce water <br />J. Rodriguez <br />Vitrified Clay <br />C08-030 <br />C08-029 <br />8975 6" <br />sag in line at —174' downstream of starter causes EML <br />J. Rodriguez <br />Vitrified Clay <br />H08-016 <br />H08-057 <br />8979 8" <br />Heavy FOG accumulation from FSEs. <br />J. Rodriguez <br />Vitrified Clay <br />J08-027 <br />J08-028 <br />8980 6" <br />J. Rodriguez <br />Vitrified Clay <br />H08-057 <br />H08-014 <br />9334 6" <br />J. Rodriguez <br />Vitrified Clay <br />J09-055 <br />J09-054 <br />