I(4 CITY OF SANTA ANA <br /> feet above grade in aluminum enclosures. The enclosures shall be touch-safe and include <br /> drivers and fusing with indicator lights on fuses to notify when a fuse is to be replaced for <br /> each luminaire. Disconnect per circuit for each pole structure will be located in the <br /> enclosure. Integral drivers are not allowed. <br /> b. Manufacturer shall provide surge protection at the pole equal to or greater than 40 kA for <br /> each line to ground (Common Mode) as recommended by IEEE C62.41.2_2002. <br /> 5. Wire harness complete with an abrasion protection sleeve, strain relief and plug-in connections <br /> for fast, trouble-free installation. <br /> 6. All luminaires, visors, and cross-arm assemblies shall withstand 150 milh winds and maintain <br /> luminaire aiming alignment, <br /> 7. Control cabinet to provide remote on-off control, monitoring, and entertainment features of the <br /> lighting system. See Section 2.3 for further details. <br /> 8. Manufacturer shall provide lightning grounding as defined by NFPA 780 and be UL Listed per <br /> UL 96 and UL 96A. <br /> a. Integrated grounding via concrete encased electrode grounding system. <br /> b. If grounding is not integrated into the structure, the manufacturer shall supply grounding <br /> electrodes, copper down conductors, and exothermic weld kits. Electrodes and conductors <br /> shall be sized as required by NFPA 780.The grounding electrode shall be minimum size of <br /> 518 inch diameter and 8 feet long, with a minimum of 10 feet embedment. Grounding <br /> electrode shall be connected to the structure by a grounding electrode conductor with a <br /> minimum size of 2 AWG for poles with 75 feet mounting height or less, and 210 AWG for <br /> poles with more than 75 feet mounting height. <br /> 9. Enhanced corrosion protection package: Due to the potentially corrosive environment for this <br /> project, manufacturers must provide documentation that their products meet the following <br /> enhanced requirements in addition to the standard durability protection specified above: <br /> a) Exposed carbon steel horizontal surfaces on the crossarm assembly shall be <br /> galvanized to no less than a five (5) mil average thickness. <br /> b) Exposed die cast aluminum components shall be Type II anodized per MIL-STD- <br /> 8625 and coated with high performance polyester. <br /> c) Exposed extruded aluminum components shall be Type II anodized per MIL-STD- <br /> 8625 and coated with high performance polyester. <br /> D- Safety: All system components shall be UL listed for the appropriate application. <br /> 2.2 ELECTRICAL <br /> A. Electric Power Requirements for the Exterior Atheletic Lighting Equipment: <br /> 1. Electric power: 240 Volt, 1 Phase <br /> 2. Maximum total voltage drop: Voltage drop to the disconnect switch located on the poles shall <br /> not exceed three(3) percent of the rated voltage. <br /> B. Energy Consumption: The kW consumption for the field lighting system shall be 1.62 kw. <br /> 2.3 CONTROL <br /> A. Instant On/Off Capabilities: System shall provide for instant on/off of luminaires. <br /> B. Lighting contactor cabinet(s)constructed of NEMA Type 4 aluminum, designed for easy installation <br /> with contactors, labeled to match field diagrams and electrical design. Manual off-on-auto selector <br /> switches shall be provided. <br />