Laserfiche WebLink
Section 403.4.7.2 is amended to read as a follows: <br />403.4.7.2 Standby power loads. The following are classified as standby <br />power loads: <br />a. Power and lighting for the fire command center required by Section <br />403.4.5; and <br />b. Standby power shall be provided for elevators in accordance with <br />Sections 1007.4, 3003, 3007, and 3008. <br />SECTION 10: That section 8 -101 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -101. Emergency power loads (Section 403.4.8.1). <br />Section 403.4.8.1 is amended to read as a follows: <br />403.4.8.1 Emergency power loads. The following are classified as <br />emergency power loads: <br />1. Exit signs and means of egress illumination required by Chapter 10; <br />2. Elevator car lighting; <br />3. Emergency voice /alarm communications systems; <br />4. Automatic fire detection systems; <br />5. Fire alarm systems; <br />6. Electrically powered fire pumps; and <br />7. Ventilation and automatic fire detection equipment for smokeproof <br />enclosures. <br />SECTION 11: That section 8 -102 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -102. Location of Calls I standpipe hose connections (Section 905.4). <br />Section 905.4 is amended to read as a follows: <br />[F] 905.4 Location of Class I standpipe hose connections. Class I <br />standpipe hose connections shall be provided in all of the following <br />locations: <br />Ordinance No. NS -XXXX <br />11 A -4 Page 4 of 43 <br />