Laserfiche WebLink
access, a separate zone by floor shall be provided for all of the following <br />types of alarm- initiating devices where provided: <br />1. Smoke detectors. <br />2. Sprinkler waterflow devices. <br />3. Manual fire alarm boxes <br />4. Other approved types of automatic detection devices or <br />suppression systems. <br />SECTION 15: That section 8 -106 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -106. Sprinkler buildings (Section 910.3.2.2). <br />Section 910.3.2.2 is amended to read as a follows: <br />[F] 910.3.2.2 Sprinkler buildings. Where installed in buildings provided with <br />an approved automatic sprinkler system, smoke and heat vents shall be <br />designed to operate automatically by actuation of a heat - responsive <br />device rated at least 100° F above the operating temperature of the <br />sprinkler, unless otherwise approved. <br />SECTION 16: That section 8 -109 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -109. (Section 1505.5). <br />Section 1505.5 of the building code is deleted. <br />SECTION 17: That section 8 -110 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -110. (Section 1505.7). <br />Section 1505.7 of the building code is deleted. <br />SECTION 18: That section 8 -112 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -112. Certificate of occupancy (Section 110). <br />Section 110 of the building code is amended to read as follows: <br />Ordinance No. NS -2810 <br />Page 8 of 43 <br />