Laserfiche WebLink
that, unlike wire installed in conduit or raceways, non - metallic sheathed cable does not <br />provide the degree of protection that is needed in the event of an earthquake; that <br />exposed non - metallic sheathed cable is particularly hazardous; and that this <br />amendment is necessary to assure that adequate protection is provided in the <br />workplace and in other places of public gathering. <br />SECTION 33: That section 8 -942 of the Santa Ana Municipal Code is hereby amended <br />such that it reads as follows: <br />Sec. 8 -942. Uses not permitted (Section 334.92). <br />Section 334.12 of the California Electrical Code is amended to read as follows: <br />Sec. 334.12. Uses Not Permitted. <br />(A) Types NM, NMC and LAMS. Types NM, NMC and NMS cables shall <br />not be permitted as follows: <br />. • • _ _ T .rrr.�rrrT <br />r. <br />habitable floor level in an existing one family dweRiF@-. <br />2. Exposed in dropped or suspended ceilings in other than one - <br />and two- family and multifamily dwellings <br />3. As service - entrance cable <br />4. In any nonresidential building or structure <br />5. In heisiways theatres and similar locations except where <br />permitted in 518.4(8) <br />motion <br />picture studios <br />7. In storage battery rooms <br />Ordinance No. NS -XXXX <br />75A -41 Page 27 of 84 <br />