Laserfiche WebLink
SECTION 10: Section 8 -942 of the Santa Ana Municipal Code is hereby amended such <br />that it reads as follows: <br />Sec. 8.942. Uses not permitted (Section 334.12). <br />Section 334.12 of the California Electrical Code is amended to read as follows: <br />Sec. 334.12. Uses Not Permitted. <br />(A) Types NM, NMC and NMS. Types NM, NMC and NMS cables shall <br />not be permitted as follows: <br />1. In any multifamily dwelling or other structure not specifically <br />permitted in 334.10(1), (2), and (3). <br />2. Exposed in dropped or suspended ceilings in other than one - <br />and two- family and multifamily dwellings <br />3. As service - entrance cable <br />4. In any nonresidential building or structure <br />5. In theatres and similar locations <br />6. In motion picture studios <br />7. In storage battery rooms <br />8. In hoist ways or on elevators or escalators <br />9. Embedded in poured cement, concrete, or aggregate. <br />10. In hazardous (classified) locations, except where specifically <br />permitted by other articles in this Code. <br />(B) Types NM and NMS, Types NM and NMS cables shall not be <br />installed in the following: <br />1. Where exposed to corrosive fumes or vapors <br />2. Where embedded in masonry, concrete, adobe, fill, or plaster <br />3. In a shallow chase in masonry, concrete, or adobe and covered <br />with plaster, adobe, or similar finish <br />Ordinance No. NS -XXXX <br />Page 6 of 31 <br />11 A -8 <br />