ORDINANCE NO. NS-2981
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY
OF SANTA ANA AMENDING CHAPTERS 8 AND 14 OF
THE SANTA ANA MUNICIPAL CODE TO ADOPT AND
AMEND THERETO THE MOST RECENTLY ENACTED
CALIFORNIA BUILDING CODE, CALIFORNIA
RESIDENTIAL CODE,—CALIFORNIA GREEN BUILDING
STANDARDS CODE,—CALIFORNIA ELECTRICAL CODE,
CALIFORNIA MECHANICAL CODE, CALIFORNIA
PLUMBING CODE, CALIFORNIA ENERGY CODE,
CALIFORNIA FIRE CODE, CALIFORNIA EXISTING
BUILDING CODE, AND INTERNATIONAL PROPERTY
MAINTENANCE CODE
THE CITY COUNCIL OF THE CITY OF SANTA ANA DOES HEREBY ORDAIN
AS FOLLOWS:
SECTION 1: Section 8-43 of the Santa Ana Municipal Code is hereby amended
such that it reads as follows:
Sec. 8-43. Adoption by reference.
There is adopted by the city that certain code known as the California Building
Code, 2019 Edition, based on the 2018 International Building Code as published by the
International Code Council, (hereinafter referred to in this article as the 'Building Code,"
"building code," or "California Building Code"), consisting of "Volume I", "Volume 2" and
the 2019 California Existing Building Code (together with subsequent supplements or
amendments to any volume, each of which shall become effective, adopted, and
incorporated by reference into this Code on the date specified by the state building
standards commission, unless otherwise specified), of which not less than one (1) copy
of said Code has been and is now on file in the office of the clerk of the council of the
city pursuant to Health and Safety Code Section 18942(d)(1) and are made available for
public inspection. The building code is adopted and incorporated by reference as
though fully set forth at length herein as provided for in section 419 of the Charter of the
city, except for the changes to the building code set forth in this chapter that specifically
amends the Building Code. Any previously enacted, unrepealed provision of the Santa
Ana Municipal Code that amended a pre-2019 edition of the 'Building Code" shall also
be construed as amending the applicable provision of the 2019 or later edition of the
building code. The building code, as thus amended, together with all other provisions of
this article, shall be known as the city building code.
Appendices which are adopted pursuant to this section are as follows:
Ordinance No. NS-2981
Page 1 of 33
Appendix I, Patio Covers
Appendix J, Grading
SECTION 2: Section 8-93 of the Santa Ana Municipal Code is hereby amended
and added such that it reads as follows:
Secs. 8-92. - Reserved.
Sec. 8-93. Permit expiration (Volume 1, Chapter 1, Division II, Section 105.5).
Chapter 1, Division II, Section 105.5 of the building code is amended to read as a
follows:
Sec. 105.5 Expiration. Every permit issued shall become invalid unless the
work on the site authorized by such permit is commenced within 12
months after its issuance, or if the work authorized on the site by such
permit is suspended or abandoned for a period of 180 days after the time
the work is commenced. The building official is authorized to grant, in
writing, one or more extensions of time, for periods not more than 180
days each. The extension shall be requested in writing and justifiable
cause demonstrated.
SECTION 3: Section 8-85 of the Santa Ana Municipal Code is hereby added such
that it reads as follows:
Sec. 8-85. Seismic loads (California Existing Building Code, Chapter 5,
Section 506.4.3).
Chapter 5, Section 506.4.3 of the California Existing Building Code is amended
by adding the following paragraph thereto:
The conversion of any portion of an existing building to residential use
shall be analyzed for 75 percent of the Design Earthquake Ground motion,
as defined in Section 1613.2 of the California Building Code, but in no
event shall there be a reduction in the capacity of the seismic force
resisting system where such system provides a greater level of protection
than the minimum requirements established by this code. Performance -
based engineering analysis and design procedures may be used to
evaluate the existing structure and the design of strengthening elements
when approved by the Building Official. All new structural elements shall
meet current detailing requirements of Section 1604 of the California
Building Code.
SECTION 4: Section 8-290 of the Santa Ana Municipal Code is hereby amended
such that it reads as follows:
Ordinance No. NS-2981
Page 2 of 33
Sec. 8-290. Adoption by reference.
There is adopted by the city that certain code known as the California
Plumbing Code, 2019 Edition, including the following appendices thereto:
A, B, D, I and J, (hereinafter referred to in this article as the "Plumbing
Code"), together with subsequent supplements or amendments, which
shall become effective, adopted and incorporated by reference into this
Code on the date specified by the state building standards commission,
unless otherwise specified. The plumbing code is adopted and
incorporated by reference as fully set forth at length herein as provided for
in section 419 of the Charter of the city, except for the changes to the
plumbing code set forth in this chapter of this Code that specifically amend
the plumbing code. Any previously enacted, unrepealed provision of this
Code that amended a pre-2019 edition of the "Plumbing Code" shall also
be construed as amending the applicable provision of the 2019 or later
edition of the plumbing code. The plumbing code as amended, together
with all other provisions of this article, shall be known as the city plumbing
code.
SECTION 5: Section 8-340 of the Santa Ana Municipal Code is hereby amended
such that it reads as follows:
Sec. 8-340. Underground Installation (California Plumbing Code Section
313.5).
Section 313.5 of the Plumbing Code is amended to read as follows:
313.5. Underground Installation. Piping in the ground shall be laid on a firm bed
for its entire length. Building drains, sewers and storm drain piping systems in the
ground, and designed and approved at less than one (1) percent grade, shall be laid on
a continuous firm bed, certified by a registered soils engineer as having a compaction
level of not less than ninety (90) percent density. Where support is otherwise provided,
it shall be approved per Section 301.2 of this code.
SECTION 6: Section 8-556 of the Santa Ana Municipal Code is hereby amended
such that it reads as follows:
Sec. 8-556. Adoption by reference.
There is adopted by the city that certain code known as the California
Mechanical Code, 2019 edition (hereinafter referred to in this article as the
"California Mechanical Code" "Mechanical Code" or "mechanical code"),
together with subsequent supplements, amendments, or editions, which
shall become effective, adopted, and incorporated by reference into this
Code on the date specified by the state building standards commission,
unless otherwise specified. The mechanical code is adopted and
Ordinance No. NS-2981
Page 3 of 33
incorporated by reference as though fully set forth at length herein as
provided for in section 419 of the Charter of the city, except for the
changes to the mechanical code set forth in this chapter of this Code that
specifically amend the mechanical code. Any previously enacted,
unrepealed provision of this Code that amended a pre-2019 edition of the
"Mechanical Code" shall also be construed as amending the applicable
provision of the 2019 or later edition of the mechanical code. The
mechanical code as amended, together with all other provisions of this
article, shall be known as the city mechanical code.
SECTION 7: Section 8-570 of the Santa Ana Municipal Code is hereby removed in
its entirety.
Sec.8-570. Reserved.
SECTION 8: Section 8-667 of the Santa Ana Municipal Code is hereby amended
such that it reads as follows:
Sec. 8-667. Adoption by reference.
There is adopted by the city that certain code known as the California
Electrical Code 2019 Edition and the administrative provisions set forth
herein, (hereinafter referred to in this article as the "Electrical Code")
together with subsequent supplements, amendments, or editions, which
shall become effective, adopted, and incorporated by reference into this
Code on the date specified by the state building standards commission,
unless specifically adopted prior to that date, of which not less than one
(1) copy of said Code has been and is now on file in the office of the clerk
of the council of the city pursuant to Health and Safety Code Section
18942(d)(1) and are made available for public inspection. The electrical
code is adopted and incorporated by reference as though fully set forth at
length herein as provided for in section 419 of the Charter of the city,
except for the changes to the electrical code set forth in this chapter of this
code that specifically amend the electrical code. Any previously enacted,
unrepealed provision of this Code that amended a pre-2019 edition of the
"Electrical Code" shall also be construed as amending the applicable
provision of the 2019 or later edition of the electrical code. The electrical
code as amended, together with all other provisions of this article, shall be
known as the city electrical code.
Annex which are adopted pursuant to this section are as follows:
Informative Annex A, Product Safety Standards
SECTION 9: The City Council of the City of Santa Ana hereby finds, determines
and declares that adoption of section 8-942 amending California Electrical Code Section
Ordinance No. NS-2981
Page 4 of 33
334.12 is necessary because earthquakes are a common occurrence in the local area;
that, unlike wire installed in conduit or raceways, non-metallic sheathed cable does not
provide the degree of protection that is needed in the event of an earthquake; that
exposed non-metallic sheathed cable is particularly hazardous; and that this
amendment is necessary to assure that adequate protection is provided in the
workplace and in other places of public gathering.
SECTION 10: Section 8-2000 of the Santa Ana Municipal Code is hereby
amended such that it reads as follows:
Sec. 8-2000. Adoption by reference.
There is adopted by the city that certain code known as the 2018 International
Property Maintenance Code (hereinafter referred to as the 'Property
Maintenance Code"), together with subsequent supplements, amendments, or
editions, which shall become effective, adopted, and incorporated by reference
into this Code on each new official publication date of the International Property
Maintenance Code, of which not less than one (1) copy of said Code has been
and is now on file in the office of the clerk of the council of the city pursuant to
Health and Safety Code Section 18942(d)(1) and are made available for public
inspection. The said Code is adopted and incorporated as fully as if set forth at
length herein as provided for in section 419 of the Charter of the city, except for
the changes to the property maintenance code set forth in this chapter of this
Code that specifically amends the property maintenance code. Any previously
enacted, unrepealed provision of this Code that amended a pre-2018 edition of
the 'Property Maintenance Code" shall also be construed as amending the
applicable provision of the 2018 or later edition of the property maintenance
code. The property maintenance code, as thus amended, together with all other
provisions of this article, shall be known as the city property maintenance code.
SECTION 11. Section 8-2800 is amended in Chapter 8 of the Santa Ana
Municipal code to read in full as follows:
Sec. 8-2800. Adoption by reference.
There is adopted by the city that certain code known as the California
Residential Code, 2019 Edition, based on the 2018 International
Residential Code as published by the International Code Council,
(hereinafter referred to in this article as the 'Residential Code" or
"California Residential Code"), (together with subsequent supplements or
amendments shall become effective, adopted, and incorporated by
reference into this Code on the date specified by the state building
standards commission, unless otherwise specified), of which not less than
one (1) copy of said Code has been and is now on file in the office of the
Clerk of the Council of the city pursuant to Health and Safety Code
Section 18942(d)(1) and are made available for public inspection. The
Ordinance No. NS-2981
Page 5 of 33
Residential code is adopted and incorporated by reference as though fully
set forth at length herein as provided for in section 419 of the Charter of
the city, except for the changes to the Residential code set forth in this
chapter that specifically amends the Residential Code. The Residential
code, as thus amended, together with all other provisions of this article,
shall be known as the city residential code.
Appendices which are adopted pursuant to this section, are as follows:
Appendix H, Patio Covers
Appendix J, Existing Buildings and Structures
SECTION 12: Section 8-2810 of the Santa Ana Municipal Code is hereby
amended such that it reads as follows:
Sec. 8-2810. Climatic and Geographic Design Criteria (Table R301.2(1)).
Table R301.2(1) is revised to read:
TABLE R301.2(1)
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
WIND DESIGN
SEISMIC
SUBJECT TO DAMAGE
FROM
ICE
BARRIER
Frost
GROUND
Speed
Topo-
Special
indborn
DESIGN
line
WINTER
UNDERLAY-
FLOOD
AIRTNGANN
SNOW
d
graphic
wind
debris
CATEGORY
Weathering
Depth
Termite
DESIGN
MENT
HAZARDS
FREEZLOAD
m h
effects"
re ion'
zone-
'
b
TEMP•
REOUIREDh
n
INDE
Very
See
Zero
110
No
No
No
Ds or E
Negli this
12-24"
Heav
43
No
Exhibit B
0
BO
For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.
a. Weathering may require a higher strength concrete or grade of masonry
than necessary to satisfy the structural requirements of this code. The
weathering column shall be filled in with the weathering index (i.e., "negligible,"
"moderate" or "severe") for concrete as determined from the Weathering
Probability Map [Figure R301.2(3)]. The grade of masonry units shall be
determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C
652.
b. The frost line depth may require deeper footings than indicated in Figure
R403.1(1). The jurisdiction shall fill in the frost line depth column with the
minimum depth of footing below finish grade.
C. The jurisdiction shall fill in this part of the table to indicate the need for
protection depending on whether there has been a history of local subterranean
termite damage.
Ordinance No. NS-2981
Page 6 of 33
d. The jurisdiction shall fill in this part of the table with the wind speed from
the basic wind speed map [Figure R301.2(A)].Wind exposure category shall be
determined on a site -specific basis in accordance with Section R301.2.1.4.
e. Temperatures shall be permitted to reflect local climates or local weather
experience as determined by the building official.
f. The jurisdiction shall fill in this part of the table with the seismic design
category determined from Section R301.2.2.1.
g. The jurisdiction shall fill in this part of the table with (a) the date of the
jurisdiction's entry into the National Flood Insurance Program (date of adoption of
the first code or ordinance for management of flood hazard areas), (b) the date(s)
of the Flood Insurance Study and (c) the panel numbers and dates of all currently
effective FIRMS and FBFMs or other flood hazard map adopted by the authority
having jurisdiction, as amended.
h. In accordance with Sections R905.2.7.1, R905.4.3.1, R905.5.3.1,
R905.6.3.1, R905.7.3.1 and R905.8.3.1, where there has been a history of local
damage from the effects of ice damming, the jurisdiction shall fill in this part of
the table with "YES." Otherwise, the jurisdiction shall fill in this part of the table
with "NO."
i. The jurisdiction shall fill in this part of the table with the 100-year return
period air freezing index (BF -days) from Figure R403.3(2) or from the 100-year
(99%) value on the National Climatic Data Center data table "Air Freezing Index -
USA Method (Base 320)" at www.ncdc.noaa.gov/fpsf.htrnl.
j. The jurisdiction shall fill in this part of the table with the mean annual
temperature from the National Climatic Data Center data table "Air Freezing
Index -USA Method (Base 320F)" at www.ncdc.noaa.gov/fpsf.html.
k. In accordance with Section R301.2.1.5, where there is local historical data
documenting structural damage to buildings due to topographic wind speed-up
effects, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the
jurisdiction shall indicate "NO" in this part of the table.
I. In accordance with Figure R301.2(5)A, where there is local historical data
documenting unusual wind conditions, the jurisdiction shall fill in this part
of the table with "YES" and identify any specific requirements. Otherwise,
the jurisdiction shall indicate "NO" in this part of the table.
M. In accordance with Section R301.2.1.2 the jurisdiction shall indicate the
wind-borne debris wind zone(s). Otherwise, the jurisdiction shall indicate
"NO" in this part of the table.
Ordinance No. NS-2981
Page 7 of 33
n. The jurisdiction shall fill in these sections of the table to establish the design
criteria using Table 1 a or 1 b from ACCA Manual J or established criteria
determined by the jurisdiction.
o. The jurisdiction shall fill in this section of the table using the Ground Snow Loads
in Figure R301.2(6).
SECTION 13. Section 8-2900 of the Santa Ana Municipal Code is hereby
amended such that it reads as follows:
Sec. 8-2900. Adoption by reference.
There is adopted by the city that certain code known as the California
Green Building Standards Code, 2019 Edition, as published by the
International Code Council, (hereinafter referred to in this article as the
"California Green Building Standards Code"), (effective, adopted, and
incorporated by reference into this Code on the date specified by the state
building standards commission, unless otherwise specified), of which not
less than one (1) copy of said Code has been and is now on file in the
office of the clerk of the council of the city pursuant to Health and Safety
Code Section 18942(d)(1) and are made available for public inspection.
The Green Building Standards code is adopted and incorporated by
reference as though fully set forth at length herein as provided for in
section 419 of the Charter of the city. The California Green Building
Standards code, as thus amended, together with all other provisions of
this article, shall be known as the city Green Building Standards code.
SECTION 14: Section 8-3000 of the Santa Ana Municipal Code is hereby added
such that it reads as follows:
ARTICLE. XVIII — CALIFORNIA ENERGY CODE
Sec. 8-3000. Adoption by reference.
There is adopted by the city that certain code known as the California
Energy Code, 2019 Edition, as published by the International Code
Council, (hereinafter referred to in this article as the "California Energy
Code"), (effective, adopted, and incorporated by reference into this Code
on the date specified by the state building standards commission, unless
otherwise specified), of which not less than one (1) copy of said Code has
been and is now on file in the office of the clerk of the council of the city
pursuant to Health and Safety Code Section 18942(d)(1) and are made
available for public inspection. The California Energy Code is adopted and
incorporated by reference as though fully set forth at length herein as
provided for in section 419 of the Charter of the city. The California Energy
Ordinance No. NS-2981
Page 8 of 33
Code, as thus amended, together with all other provisions of this article,
shall be known as the city Energy code.
SECTION 15: Section 14-1 of the Santa Ana Municipal Code is hereby amended
such that it reads as follows:
Sec. 14-1. Adoption by reference.
There is adopted by the city that certain code known as the California Fire
Code 2019 Edition, based on the 2018 International Fire Code as
published by the International Code Council, (hereinafter referred to in this
article as the "California Fire Code" or "fire code") and the whole thereof
including the Appendices therein, errata issued during and after the
publishing date, save and except such portions as are hereinafter deleted
or amended, of which code not less than one (1) copy has been and is
now on file in the office of the clerk of the council of the city pursuant to
Health and Safety Code Section 18942(d)(1) and are made available for
public inspection. Said code is adopted and incorporated as fully as if set
forth at length herein and, subject to all amendments set forth in this
article, shall be in effect within the city from the effective date of this
article. Any provision of this article amending the above mentioned codes
shall be construed as amending the 2018 and 2019 editions thereof
including such provisions enacted prior to this adoption of the said 2018
and 2019 editions and not thereafter repealed. The International Fire
Code, 2018 edition and the California Fire Code 2019 edition, as thus
amended, together with all other provisions of this article, shall be known
as the "Fire Code of the City of Santa Ana."
SECTION 16: Section 14-3.1 is hereby amended and revised as follows
Sec. 14-3.1. - Violation penalties (Section 110.4).
Section 110.4 Violation penalties.
110.4 Violation penalties. Persons who shall violate a provision of this code or
shall fail to comply with any of the requirements thereof or shall fail to comply
with any issued orders or notices or who shall erect, install, alter, repair or do
work in violation of the approved construction documents or directive of the fire
code official, or of a permit or certificate used under provisions of this code, shall
be subject to penalties assessed as prescribed in the OCFA Prevention Field
Services adopted fee schedule. Each day that a violation continues after due
notice has been served shall be deemed a separate offense.
(a) Section 110.4.2 Infraction and misdemeanor is hereby added as
follows:
Ordinance No. NS-2981
Page 9 of 33
110.4.2 Infraction and misdemeanor. Persons operating or maintaining
any occupancy, premises or vehicle subject to this code that shall permit
any fire or life safety hazard to exist on premises under their control shall
be guilty of an infraction. Persons who fail to take immediate action to
abate a fire or life safety hazard when ordered or notified to do so by the
chief or a duly authorized representative are guilty of a misdemeanor.
Secs.14-4-14-9. Reserved.
SECTION 17: Section 14-21 is hereby amended as follows:
Sec. 14-21. - Definitions (Section 202).
Chapter 2 Definitions is adopted in its entirety with the following amendment:
Section 202 General Definitions is hereby revised by adding "OCFA" and "Spark
Arrester" as follows:
202 General Definitions
OCFA- Orange County Fire Authority, fire authority having jurisdiction.
SPARK ARRESTER- A listed device constructed of noncombustible material
specifically for the purpose of meeting one of the following conditions:
1. Removing and retaining carbon and other flammable particles/debris
from the exhaust flow of an internal combustion engine in accordance
with California Vehicle Code Section 38366..
2. Fireplaces that burn solid fuel in accordance with California Building
Code Chapter 28.
SECTION 18: Section 14-22 is hereby amended as follows:
Sec. 14-22. - General requirements (Chapter 3).
Chapter 3 General Requirements. Adopt Chapter 3 in its entirety, with the
exception of Sections 308.1.4, 311.5 through 311.5.5, 318, and 319, and with the
following amendments:
(a) Section 304.1.2 Vegetation. Weeds, grass, vines or other growth
that is capable of being ignited and endangering property, shall be cut
down and removed by the owner or occupant of the premises. Vegetation
clearance requirement in urban-wildland interface areas shall be in
accordance with Chapter 49. Type, amount, arrangement, and
maintenance of vegetation in a fuel modification area, interior slope, or
similarly hazardous area shall be in accordance with OCFA Guideline C-
Ordinance No. NS-2981
Page 10 of 33
05 "Vegetation Management Guideline —Technical Design for New
Construction, Fuel Modification Plans, and Maintenance Program."
(b) Section 305.6 Hazardous Conditions is hereby amended as
follows:
305.6 Hazardous conditions. Outdoor fires burning wood or other solid
fuel are not allowed when any of the following conditions applies:
1. when predicted sustained winds exceed 8 MPH and relative
humidity is less than 25%, or a red flag condition has been declared
2. when an official sign was caused to be posted by the fire code
official, or a public announcement is made
No outdoor fires using any fuel type are permitted when predicted sustained
winds exceed 20 MPH or when such fires present a hazard as determined
by the fire code official.
(c) Section 305.7 Disposal of rubbish is hereby added as follows:
305.7 Disposal of rubbish. Rubbish, trash or combustible waste material
shall be burned only within an approved incinerator and in accordance
with Section 307.2.1.
(d) Section 307 OPEN BURNING, RECREATIONAL FIRES AND
PORTABLE OUTDOOR FIREPLACES is hereby revised as follows:
SECTION 307 OPEN BURNING, RECREATIONAL FIRES, FIRE PITS,
FIRE RINGS, AND PORTABLE OUTDOOR FIREPLACES
Section 307.6 Outdoor Fireplaces, fire Pits, Fire Rings, or similar devices
used at Group R Occupancies is hereby added as follows:
307.6 Outdoor Fireplaces, Fire Pits, Fire Rings, or similar devices used at
Group R Occupancies. Outdoor fireplaces, fire pits, fire rings, or similar exterior
devices used at Group R shall comply with this section.
Exception: Barbeques, grills, and other portable devices intended solely for
cooking.
307.6.1 Gas -fueled devices. Outdoor fireplaces, fire pits and similar
devices fueled by natural gas or liquefied -petroleum gas are allowed when
approved by the Building Department and the device is designed to only
Ordinance No. NS-2981
Page 11 of 33
burn a gas flame and not wood or other solid fuel. At R-3 occupancies,
combustible construction shall not be located within three feet of an
atmospheric column that extends vertically from the perimeter of the
device. At other R occupancies, the minimum distance shall be ten feet.
Where a permanent Building Department approved hood and vent is
installed, combustible construction may encroach upon this column
between the bottom of the hood and the vent opening. Where chimneys
or vents are installed, they shall have a spark arrester as defined in
Section 202.
Section 307.6.2 Devices using wood or fuels other than natural gas or
liquefied -petroleum gas is hereby amended as follows:
307.6.2 Devices using wood or fuels other than natural gas or
liquefied -petroleum gas. Permanent outdoor fireplaces burning wood or
other solid fuel shall be constructed in accordance with the California
Building Code with clearance from combustible construction and building
openings as required therein. Fires in a fireplace shall be contained within
a firebox with an attached chimney. The opening in the face of the firebox
shall have an installed and maintained method of arresting sparks.
The burning of wood or other solid fuel in a device is not allowed within 25
feet of combustible structures, unless within an approved permanent
fireplace. Conditions which could cause a fire to spread within 25 feet of a
structure or to vegetation shall be eliminated prior to ignition. Fires in
devices burning wood or solid fuel shall be in accordance with Sections
305, 307, and 308.
Exceptions:
1. Portable fireplaces and fire rings/pits equipped with a device to
arrest sparks shall be located at least 3' from combustible construction at
R-3 occupancies,
2. Portable fireplaces, and fire pits/rings equipped with a device to
arrest sparks, shall be located at least 15 feet from combustible structures
at other R occupancies.
Section 307.6.2.1 Where prohibited is hereby amended as follows:
307.6.2.1 Where prohibited. The burning of wood and other solid fuels shall not
be conducted within a fuel modification zone, Wildfire Risk Area (WRA),
Wildland-Urban Interface Area (WUI), or in locations where conditions could
cause the spread of fire to the WRA or WUI.
Exceptions:
Ordinance No. NS-2981
Page 12 of 33
1. Permanent fireplaces that are not located in a fuel modification
zone
2. Where determined by the Fire Code Official that the location or
design of the device should reasonably prevent the start of a wildfire.
(e) Section 308.1.6.3 Sky lanterns is hereby revised as follows:
308.1.6.3 Sky lanterns. A person shall not ignite, release, or cause to be
released a sky lantern.
(f) Section 309.3.1 Indoor charging of electric carts/cars is hereby
removed.
(g) Section 321 Fuel Modification Requirements for New
Construction is hereby amended as follows:
321 Fuel Modification Requirements for New Construction. All new
structures and facilities adjoining land containing hazardous combustible
vegetation shall be approved and in accordance with the requirements of
OCFA Guideline C-05 "Vegetation Management Guideline — Technical
Design for New Construction Fuel Modification Plans and Maintenance
Program."
(h) Section 322 Clearance of brush or vegetation growth from
roadways is hereby amended as follows:
322 Clearance of brush or vegetation growth from roadways. The fire
code official is authorized to cause areas within 10 feet (3048 mm) on
each side of portions of highways and private streets which are
improved, designed or ordinarily used for vehicular traffic, to be cleared
of flammable vegetation and other combustible growth. Measurement
shall be from the flow -line or the end of the improved edge of the
roadway surfaces.
Exception: Single specimens of trees, ornamental shrubbery or cultivated
ground cover such as green grass, ivy, succulents or similar plants used
as ground covers, provided that they do not form a means of readily
transmitting fire.
(i) Section 323 Unusual Circumstances is hereby amended as
follows:
323 Unusual circumstances. The fire code official may suspend
enforcement of the vegetation management requirements and require
reasonable alternative measures designed to advance the purpose of this
Ordinance No. NS-2981
Page 13 of 33
code if determined that in any specific case that any of the following
conditions exist:
1. Difficult terrain.
2. Danger of erosion.
3. Presence of plants included in any state and federal
resources agencies, California Native Plant Society and
county -approved list of wildlife, plants, rare, endangered
and/or threatened species.
4. Stands or groves of trees or heritage trees.
5. Other unusual circumstances that make strict compliance
with the clearance of vegetation provisions undesirable or
impractical.
(j) Section 324 Use of Equipment is hereby added as follows:
324 Use of equipment. Except as otherwise provided in this section, no
person shall use, operate, or cause to be operated in, upon or adjoining
any hazardous fire area any internal combustion engine which uses
hydrocarbon fuels, unless the engine is equipped with a spark arrester as
defined in Section 202 maintained in effective working order, or the engine
is constructed, equipped and maintained for the prevention of fire.
Exception:
1. Engines used to provide motor power for trucks, truck tractors,
buses, and passenger vehicles, except motorcycles, are not subject to this
section if the exhaust system is equipped with a muffler as defined in the
Vehicle Code of the State of California.
2. Turbocharged engines are not subject to this section if all
exhausted gases pass through the rotating turbine wheel, there is no
exhaust bypass to the atmosphere, and the turbocharger is in good
mechanical condition.
(k) Section 324.1 Use of Equipment and Devices Generating Heat,
Sparks or Open Flames is hereby amended as follows:
324.1 Equipment and devices generating heat, sparks or open
flames. During any time of the year within Wildfire Risk Areas, within or
immediately adjacent to any forest- or brush -covered land or non -irrigated
grass -covered land, no person shall use or operate any welding
equipment, cutting torches, tar pots, grinding devices, or other tools or
Ordinance No. NS-2981
Page 14 of 33
equipment that may produce a spark, fire, or flame that could result in a
wildfire without doing the following:
1. First clearing away all flammable material, including snags,
from the area around such operation for a distance of 30 feet or
other approved method to reduce fire spread into the wildlands. If
30 foot clearing cannot be achieved then an alternate method shall
be approved by the AHJ prior to work starting.
2. Maintain one serviceable round point shovel with an overall
length of not less than forty-six (46) inches and one backpack pump
water -type fire extinguisher fully equipped and ready for use at the
immediate area during the operation.
3. Stop work when winds are 8 MPH during periods when
relative humidity is less than 25%, or a red flag condition has been
declared or public announcement is made, when an official sign
was caused to be posted by the fire code official, or when such fires
present a hazard as determined by the fire code official.
4. Keep a cell phone nearby and call 911 immediately in case
of a fire.
(1) Section 324.2 Spark arresters is hereby added as follows:
324.2 Spark arresters. Spark arresters shall comply with Section 202,
and when affixed to the exhaust system of engines or vehicles subject to
Section 324 shall not be placed or mounted in such a manner as to allow
flames or heat from the exhaust system to ignite any flammable material.
SECTION 19:Section 14-23 is hereby amended as follows:
Sec. 14-23. - Emergency planning and preparedness (Chapter 4).
Chapter 4: Emergency Planning and Preparedness. Only the following
Sections listed below are adopted:
1.
401 — 401.9
2.
402
3.
403.2
4.
403.5 — 403.5.4
5.
403.10.2.1.1
Ordinance No. NS-2981
Page 15 of 33
6. 403.13 — 403.13.3
7. 404.5 — 404.6.6
8. 407
SECTION 20: Section 14-24 is hereby amended as follows:
Sec. 14-24. - Fire service features (Chapter 5).
Chapter 5 Fire Service Features is adopted in its entirety with the following
amendments:
(a) SECTION 501.1 Scope is revised to read as follows:
501.1 Scope. Fire service features for buildings, structures and premises
shall comply with this chapter and, where required by the fire code official,
with OCFA Guideline B-09, "Fire Master Plan for Commercial &
Residential Development." Fire service features for buildings, structures
and premises located in State Responsibility Areas, and Local
Responsibility Areas designated as Very High Hazard Fire Severity Zone
shall also comply with OCFA Guideline B-09a, "Fire Safe Development in
State Responsibility Areas, and Local Responsibility Areas designated as
Very High Hazard Fire Severity Zone".
(b) Section 505.1 Address Identification is revised as follows:
505.1 Address identification. New and existing buildings shall have
approved address numbers, building numbers or approved building
identification placed in a position that is plainly legible and visible from the
street or road fronting the property. These numbers shall contrast with
their background. Where required by the fire code official, address
numbers shall be provided in additional approved locations to facilitate
emergency response. Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall be a minimum of 4 inches (101.6 mm)
high with a minimum stroke width of 0.5 inch (12.7 mm) for R-3
occupancies, for all other occupancies the numbers shall be a minimum of
6 inches high with a minimum stroke width of 1 inch. Where access is by
means of a private road and the building cannot be viewed from the public
way, a monument, pole or other sign or means shall be used to identify
the structure. Address numbers shall be maintained.
(d) Section 510.1 Emergency responder radio coverage in new buildings is revised
to read as follows:
510.1 Emergency responder radio coverage in new buildings. All new
buildings shall have approved radio coverage for emergency responders
within the building based upon the existing coverage levels of the public
Ordinance No. NS-2981
Page 16 of 33
safety communication systems utilized by the jurisdiction measured at the
exterior of the building. This section shall not require improvement of the
existing public safety communication systems. The Emergency
Responder Radio Coverage System shall comply with the Orange County
Sheriff's Department, Communications and Technology Division
guidelines and specifications and, where the functionality or performance
requirements in the California Fire Code are more stringent, this code.
Exceptions:
1.In buildings or structures where it is determined by the fire code
official that the radio coverage system is not needed, including but not
limited to the following:
a. Existing buildings or structures, unless required by the
Building Official and OCFA for buildings and structures undergoing
extensive remodel and/or expansion.
b. Elevators.
C. Structures that meet all of the following:
i. Three stories or less, and
ii. Do not have subterranean storage or parking, and
iii. Do not exceed 50,000 square feet on any single story.
Structures that meet all of the following:
i. Residential structures four stories or less, and
ii. Constructed of wood, and
iii. Do not have subterranean storage or parking, and
iv. Are not built integral to an above ground multi -story parking
structure.
Should a structure that is three stories or less and 50,000 square feet or
smaller on any single story include subterranean storage or parking, then
this ordinance shall apply only to the subterranean areas.
2. In facilities where emergency responder radio coverage is required
and such systems, components or equipment required could have a
negative impact on the normal operations of the facility, the fire code
official shall have the authority to accept an automatically activated
emergency radio coverage system.
(d) Section 510.2 Emergency responder radio coverage in existing
buildings is deleted without replacement.
(e) Section 510.3 Permit required is deleted without replacement.
Ordinance No. NS-2981
Page 17 of 33
(f) Section 510.4.2.2 Technical Criteria is adopted without amendment.
(g) Section 510.5.1 Approval prior to installation is adopted without
amendment.
(h) Section 510.5.2 Minimum qualification of personnel is removed
without replacement.
(i) Section 510.5.3 Acceptance test procedure is adopted without
amendment.
(j) Section 510.6.1 Testing and proof of compliance is adopted
without amendment.
SECTION 21: Section 14-30 is hereby amended to read as follows:
Sec. 14-30. - Fire protection and Life Safety Systems (Chapter 9).
Chapter 9 Fire protection and Life Safety Systems is adopted in its entirety
with the following amendments:
(a) Section 903.2 Where required is hereby amended as follows:
903.2 Where required. Approved automatic sprinkler systems in buildings
and structures shall be provided when one of the following conditions
exists:
New buildings: Notwithstanding any applicable provisions of
Sections 903.2.1 through 903.2.19, an automatic fire -
extinguishing system shall also be installed in all
occupancies when the total building area exceeds 5,000
square feet (465 m2) as defined in Section 202, regardless of
fire areas or allowable area, or is more than two stories in
height.
Exception: Subject to approval by the Fire Code Official, open parking
garages in accordance with Section 406.5 of the California Building Code.
2. Existing Buildings: Notwithstanding any applicable provisions
of this code, an automatic sprinkler system shall be provided in an
existing building when an addition occurs and one of the following
conditions exists:
a. When an addition is 33% or more of the existing building
area, and the resulting building area exceeds 5000 square feet
(465 m2) as defined in Section 202; or
ordinance No. NS-2981
Page 18 of 33
b. When an addition exceeds 2000 square feet (186 m2) and
the resulting building area exceeds 5000 square feet (465 m2)
as defined in Section 202; or
c. An additional story is added above the second floor
regardless of fire areas or allowable area.
Exception: Group R-3 occupancies shall comply with Section
903.2.8.
(b) Section 903.3.5.3 Hydraulically calculated
systems is hereby added as follows:
903.3.5.3 Hydraulically calculated systems. The design of hydraulically
calculated fire sprinkler systems shall not exceed 90% of the water supply
capacity
Exception: When static pressure exceeds 100 psi, and required by the
Fire Code Official, the fire sprinkler system shall not exceed water supply
capacity specified by Table 903.3.5.
Ordinance No. NS-2981
Page 19 of 33
Desl9r.
TABLE 903.3.5.3
HYDRAULICALLY CALCULATED SYSTEMS
1100 110 120 130 140 150 PSI
Ordinance No. NS-2981
Page 20 of 33
SECTION 22: Section 14-31 is hereby amended and added to read as follows:
Sec. 14-31. — Energy Systems (Chapter 12).
Chapter 12 Energy Systems is adopted in its entirety with the following
amendments added:
1201.1.1 Other Systems Where required by the fire code official, other systems
and operations including but not limited to battery systems assembly, battery
reconditioning and storage, research and development of battery storage systems,
electric vehicle manufacturing and testing, and battery charging systems for cars and
carts inside of buildings or structures, shall comply with this chapter.
SECTION 23: Section 14-32 is hereby amended to read as follows:
Sec. 14-32. — Construction requirements for Existing Buildings (Chapter 11).
Chapter 11 Construction Requirements for Existing Buildings: Only the
following Sections and Subsections are adopted:
1103.7
1103.7.3
1103.7.3.1
1103.7.8 — 1103.7.8.2
1103.7.9 — 1103.7.9.10
1103.8 — 1103.8.5.3
1103.9.1
1107
1113
1114
1115
1116
SECTION 24: Section 14-33 is hereby removed as follows:
Sec. 14-33. Reserved.
SECTION 25: Section14-34 is hereby amended to read as follows:
Sec. 14-34. - Lumber Yards and Agro-Industrial, Solid Biomass and
Woodworking Facilities (Chapter 28).
Chapter 28 Lumber Yards and Agro-Industrial, Solid Biomass and
Woodworking Facilities is adopted in its entirety with the following amendments:
Ordinance No. NS-2981
Page 21 of 33
(a) Section 2801.2 Permit is hereby revised as follows:
2801.2 Permit. Permits shall be required as set forth in Section 105.6. and
105.6.29.
(b) Section 2808.2 Storage site is hereby revised as follows:
2808.2 Storage site. Storage sites shall be level and on solid ground, elevated
soil lifts or other all-weather surface. Sites shall be thoroughly cleaned and
approval obtained from the fire code official before transferring products to the
site.
(c) Section 2808.3 Size of piles is hereby revised as follows:
2808.3 Size of piles. Piles shall not exceed 15 feet in height, 50 feet in width and
100 feet in length.
Exception: The fire code official is authorized to allow the pile size to be
increased where a fire protection plan is provided for approval that includes, but is not
limited to, the following:
1. Storage yard areas and materials -handling equipment selection, design
and arrangement shall be based upon sound fire prevention and protection
principles.
2. Factors that lead to spontaneous heating shall be identified in the -plan,
and control of the various factors shall be identified and implemented, including
provisions for monitoring the internal condition of the pile.
3. The plan shall include means for early fire detection and reporting to the
public fire department; and facilities needed by the fire department for fire
extinguishment including a water supply and fire hydrants.
4. Fire apparatus access roads around the piles and access roads to the top
of the piles shall be established, identified and maintained.
5. Regular yard inspections by trained personnel shall be included as part of
an effective fire prevention maintenance program.
Additional fire protection called for in the plan shall be provided and shall be
installed in accordance with this code. The increase of the pile size shall be based
upon the capabilities of the installed fire protection system and features.
(d) Section 2808.4 Pile Separation is hereby added as follows:
Ordinance No. NS-2981
Page 22 of 33
2808.4. Pile separation. Piles shall be separated from adjacent piles by -a
minimum distance of 20 feet. Additionally, piles shall have a minimum separation
of 100 feet from combustible vegetation.
(e) Section 2808.7 Pile fire protection is hereby revised as follows:
2808.7 Pile fire protection. Automatic sprinkler protection shall be provided in
conveyor tunnels and combustible enclosures that pass under a pile.
Combustible conveyor systems and enclosed conveyor systems shall be
equipped with an approved automatic sprinkler system. Oscillating sprinklers with
a sufficient projectile reach are required to maintain a 40% to 60% moisture
content and wet down burning/smoldering areas.
(f) Section 2808.9 Material -handling equipment is hereby revised as follows:
2808.9 Material -handling equipment. All material handling equipment operated
by an internal combustion engine shall be provided and maintained with an
approved spark arrester. Approved material -handling equipment shall be
available for moving wood chips, hogged material, wood fines and raw product
during fire -fighting operations.
(g) Section 2808.11 Temperature control, is hereby added as follows:
2808.11 Temperature control. The temperature shall be monitored and
maintained as specified in Sections 2808.11.1 and 2808.11.2.
(h) Section 2808.11.1 Pile temperature control, is hereby added as follows:
2808.11.1 Pile temperature control. Piles shall be rotated when the internal
temperature readings are in excess of 165 degrees Fahrenheit.
(i) Section 2808.11.2 New material temperature control, is hereby added
as follows:
2808.11.2 New material temperature control. New loads delivered to the
facility shall be inspected and tested at the facility entry prior to taking delivery.
Material with temperature exceeding 165 degrees Fahrenheit shall not be
accepted on the site. New loads shall be monitored to verify that the temperature
remains stable.
0) Section 2808.12 Water availability is hereby added as follows:
2808.12 Water Availability. Facilities with over 2500 cubic feet shall provide a
water supply. The minimum fire flow shall be no less than 500 GPM @ 20 psi for
a minimum of 1 hour duration for pile heights up to 6 feet and 2 hour duration for
pile heights over 6 feet. If there is no water purveyor, an alternate water supply
with storage tank(s) shall be provided for fire suppression. The water supply
tank(s) shall provide a minimum capacity of 2500 gallons per pile (maximum
Ordinance No. NS-2981
Page 23 of 33
30,000 gallons) for piles not exceeding 6 feet in height and 5000 gallons per pile
(maximum 60,000) for piles exceeding 6 feet in height. Water tank(s) shall not be
used for any other purpose unless the required fire flow is left in reserve within
the tank at all times. An approved method shall be provided to maintain the
required amount of water within the tank(s).
(k) Section 2808.13 Tipping area is hereby added as follows:
2808.13 Tipping areas shall comply with the following:
1. Tipping areas shall not exceed a maximum area of 50 feet by 50 feet.
2. Material within a tipping area shall not exceed 5 feet in height at any time.
3. Tipping areas shall be separated from all piles by a 20 foot wide fire
access lane.
4. A fire hydrant or approved fire water supply outlet shall be located within
150 feet of all points along the perimeter of the tipping area.
5. All material within a tipping area shall be processed within 5 days of
receipt.
(1) Section 2808.14 Emergency Contact is hereby added as follows:
2808.14 Emergency Contact. The contact information of a responsible person or
persons shall be provided to the Fire Department and shall be posted at the entrance to
the facility for responding units. The responsible party should be available to respond to
the business in emergency situations
SECTION 26: Section 14-35 is hereby added to read as follows:
Sec. 14-35. Chapter 49
Requirements for Wildland-Urban Interface Fire Areas
Chapter 49 Requirements for Wildland-Urban Interface Fire Areas is adopted
in its entirety with the following amendments:
Section 4906.3 Requirements is hereby revised as follows:
4906.3 Requirements. Hazardous vegetation and fuels around all applicable
buildings and structure shall be maintained in accordance with the following laws
and regulations:
1. Public Resources Code, Section 4291.
Ordinance No. NS-2981
Page 24 of 33
2. California Code of Regulations, Title 14, Division 1.5, Chapter 7,
Subchapter 3, Section 1299 (see guidance for implementation
"General Guideline to Create Defensible Space").
3. California Government Code, Section 51182.
4. California Code of Regulations, Title 19, Division 1, Chapter 7,
Subchapter 1, Section 3.07.
5. OCFA Guideline C-05 "Vegetation Management Guideline — Technical
Design for New Construction Fuel Modification Plans and Maintenance
Program."
Section 4908 Fuel Modification Requirements for New Construction is hereby
added as follows:
4908 Fuel Modification Requirements for New Construction. All new buildings
to be built or installed in a Wildfire Risk Area shall comply with the following:
1. Preliminary fuel modification plans shall be submitted to and
approved by the fire code official prior to or concurrently with the approval of
any tentative map.
2. Final fuel modification plans shall be submitted to and approved by
the fire code official prior to the issuance of a grading permit.
3. The fuel modification plans shall meet the criteria set forth in the Fuel
Modification Section of OCFA Guideline C-05 "Vegetation Management
Guideline — Technical Design for New Construction Fuel Modification Plans
and Maintenance Program."
3.1 The fuel modification plan shall include provisions for the
maintenance of the fuel modification in perpetuity.
4. The fuel modification plan may be altered if conditions change. Any
alterations to the fuel modification areas shall have prior approval from the
fire code official.
5. All elements of the fuel modification plan shall be maintained in
accordance with the approved plan and are subject to the enforcement
process outlined in the Fire Code.
SECTION 27: Section 14-39 is hereby amended as follows:
Sec. 14-39. - Flammable and combustible liquids (Chapter 57).
Flammable and Combustible Liquids (Chapter 57) is adopted in its entirety
with the exception of Section 5707 and with the following amendment:
Ordinance No. NS-2981
Page 25 of 33
Section 5701.1.1 On -Demand Mobile fueling is added as follows:
Section 5701.1.1 On -Demand Mobile fueling. On -demand mobile fueling of
Class I, II, and III liquids into the fuel tanks of vehicles is prohibited.
SECTION 28: Section 14-40 is hereby added as follows:
Sec. 14-40. — Flammable Gases and Flammable Cryogenic Fluids (Chapter
58)
Chapter 58 Flammable Gases and Flammable Cryogenic Fluids is adopted
with the exception of section 5809, in its entirety and with the following amendment:
Section 5801.1 Scope is revised as follows:
Section 5801.1 Scope. The storage and use of flammable gases and
flammable cryogenic fluids shall be in accordance with this chapter, NFPA 2 and
NFPA 55._Compressed gases shall also comply with Chapter 53 and cryogenic
fluids shall also comply with Chapter 55. Flammable cryogenic fluids shall
comply with Section 5806. Hydrogen motor fuel -dispensing stations and repair
garages and their associated above -ground hydrogen storage systems shall also
be designed, constructed and maintained in accordance with Chapter 23. Mobile
fueling of gaseous and liquid hydrogen, compressed natural gas (CNG), and
liquefied natural gas (LNG) into the fuel tanks of vehicles is prohibited.
Exceptions:
1. Gases used as refrigerants in refrigeration systems (see Section
605).
2. Liquefied petroleum gases and natural gases regulated by Chapter
61.
3. Fuel -gas systems and appliances regulated under the California
Mechanical Code and the California Plumbing Code other than
gaseous hydrogen systems and appliances.
4. Pyrophoric gases in accordance with Chapter 64.
SECTION 29: Section 14-41 is hereby amended to read as follows:
Sec. 14-41. - Referenced standards (Chapter 80).
(a) NFPA 13, 2016 Edition, Standard for the Installation of Sprinkler
Systems is hereby amended as follows:
Ordinance No. NS-2981
Page 26 of 33
(1) Section 6.7.3 is hereby amended as follows
6.7.3 Fire department connections (FDC) shall be of an approved type. The
location shall be approved and be no more than 150 feet from a public
hydrant. The FDC may be located within 150 feet of a private fire hydrant
when approved by the fire code official. The size of piping and the number
of 2Y2" inlets shall be approved by the fire code official. If acceptable to the
water authority, it may be installed on the backflow assembly. Fire
department inlet connections shall be painted OSHA safety red or as
approved. When the fire sprinkler density design requires more than 500
gpm (including inside hose stream demand), or a standpipe system is
included, four 2'Y2' inlets shall be provided.
(2) Section 8.3.3.1 is hereby amended as follows:
8.3.3.1. When fire sprinkler systems are installed in shell buildings of
undetermined use (Spec Buildings) other than warehouses (S
occupancies), fire sprinklers of the quick -response type shall be used. Use
is considered undetermined if a specific tenant/occupant is not identified at
the time the fire sprinkler plan is submitted. Sprinklers in light hazard
occupancies shall be one of the following:
Quick -response type as defined in 3.6.4.8
2. Residential sprinklers in accordance with the requirements of
8.4.5
3. Quick response CMSA sprinklers
4. ESFR sprinklers
5. Standard -response sprinklers used for modifications or
additions to existing light hazard systems equipped with standard -
response sprinklers
6. Standard -response sprinklers used where individual standard -
response sprinklers are replaced in existing light hazard systems
(3) Section 8.15.1.2.7 is hereby added and revised as follows:
8.15.1.2.7 Concealed spaces filled with noncombustible insulation shall not
require sprinkler protection when approved by the fire code official.
(4) Section 11.1.1.1 is hereby added as follows:
Ordinance No. NS-2981
Page 27 of 33
11.1.1.1 When fire sprinkler systems are required in buildings of
undetermined use other than warehouses, they shall be designed and
installed to have a fire sprinkler density of not less than that required for
an Ordinary Hazard Group 2 use, with no reduction(s) in density or design
area. Warehouse fire sprinkler systems shall be designed to Figure
16.2.1.3.2 (d) curve "G". Use is considered undetermined if a specific
tenant/occupant is not identified at the time the sprinkler plan is submitted.
Where a subsequent occupancy requires a system with greater capability,
it shall be the responsibility of the occupant to upgrade the system to the
required density for the new occupancy.
(5) Section 11.2.3.1.1.1 is hereby added as follows:
11.2.3.1.1.1 The available water supply for fire sprinkler system design
shall be determined by one of the following methods, as approved by the
Fire Code Official:
1) Subtract the project site elevation from the low water level
for the appropriate pressure zone and multiply the result by
0.433;
2) Use a maximum of 40 psi, if available;
3) Utilize the Orange County Fire Authority water -flow test
form/directions to document a flow test conducted by the
local water agency or an approved third party licensed in the
State of California.
NFPA 13D 2016 Edition, Standard for the Installation of Sprinkler Systems in
One- and Two -Family Dwellings and Manufactured Homes is hereby amended as
follows:
Section 7.1.2 is hereby revised as follows:
7.1.2 The sprinkler system piping shall not have separate control valves
installed unless supervised by a central station, proprietary, or remote
station alarm service one of the following methods:
(1) Central station, proprietary, or remote station alarm service.
(2) Local alarm service that causes the sounding of an audible signal at a
constantly attended location.
(3) Valves that are locked open.
NFPA 14, 2013 Edition, Installation of Standpipe and Hose Systems is
hereby amended as follows:
Ordinance No. NS-2981
Page 28 of 33
Section 7.3.1.1 is hereby is deleted in its entirety and replaced as follows:
7.3.1.1 Class I and III Standpipe hose connections shall be unobstructed
and shall be located not less than 18 inches or more than 24 inches above
the finished floor. Class II Standpipe hose connections shall be
unobstructed and shall be located not less than 3 feet or more than 5 feet
above the finished floor.
NFPA 24, 2016 Edition, Standard for the Installation of Private Fire Service
Mains and Their Appurtenances is hereby amended as follows:
Section 6.2.8.1 is hereby added as follows:
6.2.8.1 All indicating valves controlling fire suppression water
supplies shall be painted OSHA red.
Exceptions:
1. Brass or bronze valves on sprinkler risers mounted to the exterior
of the building may be left unpainted.
2. Where OS&Y valves on the detector check assembly are the only
control valves, at least one OS&Y valve shall be painted red.
Section 6.2.9 is hereby amended as follows:
All connections to private fire service mains for fire protection systems shall be
arranged in accordance with one of the following so that they can be isolated:
(1) A post indicator valve installed not less than 40 ft (12 m) from the
building
(a) For buildings less than 40 ft (12 m) in height, a post
indicator valve shall be permitted to be installed closer than 40 ft
(12 m) but at least as far from the building as the height of the wall
facing the post indicator valve.
(2) A wall post indicator valve
(3) An indicating valve in a pit, installed in accordance with Section 6.4
(4) A backflow preventer with at least one indicating valve not less than
40 ft (12 m) from the building
(a) For buildings less than 40 ft (12 m) in height, a backflow
preventer with at least one indicating valve shall be permitted to be
Ordinance No. NS-2981
Page 29 of 33
installed closer than 40 ft (12 m) but at least as far from the building
as the height of the wall facing the backflow preventer.
(5) Control valves installed in a fire -rated room accessible from the
exterior.
(6) Control valves in a fire -rated stair enclosure accessible from the
exterior.
Section 10.1.5 is hereby added as follows:
10.1.5 All ferrous pipe and joints shall be polyethylene encased per AWWA
C150, Method A, B, or C. All fittings shall be protected with a loose 8-mil polyethylene
tube or sheet. The ends of the tube or sheet shall extend past the joint by a minimum of
12 inches and be sealed with 2 inch wide tape approved for underground use.
Galvanizing does not meet the requirements of this section.
Exception: 304 or 316 Stainless Steel pipe and fittings
Section 10.4.1.1 is hereby revised as follows:
10.4.1.1 All bolted joint accessories shall be cleaned and thoroughly coated with
asphalt or other corrosion -retarding material after installation.
Exception: Bolted joint accessories made from 304 or 316 stainless steel.
Section 10.4.1.1.1 is hereby added as follows:
10.4.1.1.1 All bolts used in pipe -joint assembly shall be 316 stainless steel.
Section 10.4.3.2 is hereby deleted and replaced as follows:
10.4.3.2 Where approved, private fire service mains supplying systems within the
building shall be permitted. to extend more than 10 ft. under the building when all of the
requirements of 10.4.3.2.1 through 10.4.3.2.4 are met. Where fire service mains enter
the building adjacent to the foundation, the pipe may run under a building to a maximum
of 24 inches, as measured from the interior face of the exterior wall to the center of the
vertical pipe. The pipe under the building or building foundation shall be 304 or 316
stainless steel and shall not contain mechanical joints or it shall comply with 10.4.3.2.1
through 10.4.3.2.4.
SECTION 30: Section 14-47 is hereby amended to read as follows:
Sec.14-47. Appendices.
Ordinance No. NS-2981
Page 30 of 33
Appendix A is deleted in its entirety without amendments.
Appendix B is adopted in its entirety with amendments outlined in Guideline 13-
09.
Appendix BB is adopted in its entirety without amendments.
Appendix C is adopted in its entirety without amendments.
Appendix CC is adopted in its entirety without amendments.
Appendix D is deleted in its entirety without amendments.
Appendix E is deleted in its entirety without amendments.
Appendix F is deleted in its entirety without amendments.
Appendix G is deleted in its entirety without amendments.
Appendix H is deleted in its entirety without amendments.
Appendix 1 is deleted in its entirety without amendments.
Appendix J is deleted in its entirety without amendments.
Appendix K is deleted in its entirety without amendments.
Appendix L is deleted in its entirety without amendments.
Appendix M is deleted in its entirety without amendments.
Appendix N is deleted in its entirety without amendments.
Appendix O is deleted in its entirety without amendments.
SECTION 31: All provisions of the Santa Ana Municipal Code which are
repeated herein are repeated solely in order to comply with the provisions of Section
418 of the City Charter. Any such restatement of existing provisions of the Code is not
intended, nor shall it be interpreted, as constituting a new action or decision of the City
Council, but rather such provisions are repeated for tracking purposes only in
conformance with the Charter.
SECTION 32: Neither the adoption of this ordinance nor the repeal hereby of any
ordinance shall in any manner affect the prosecution for violation or ordinances, which
violations were committed prior to the effective date hereof, nor be construed as affecting
any of the provisions of such ordinance relating to the collection of any such license or
Ordinance No. NS-2981
Page 31 of 33
penalty or the penal provision applicable to any violation thereof, nor to affect the validity of
any bond or cash deposit in lieu thereof, required to be posted, filed or deposited pursuant
to any ordinance and all rights and obligations there under appertaining shall continue in full
force and effect.
SECTION 33: If any section, subsection, sentence, clause, phrase, or portion of
this ordinance is for any reason held to be invalid or unconstitutional by the decision of any
court of competent jurisdiction, such decision shall not affect the validity of the remaining
portions of this ordinance. The City Council of the City of Santa Ana hereby declares that it
would have adopted this ordinance and each section, subsection, sentence, clause, phrase
or portion thereof irrespective of the fact that any one or more sections, subsections,
sentences, clauses, phrases, or portions be declared invalid or unconstitutional.
ADOPTED this 17th day of December, 2019
0��/
..
Mayor
APPROVED AS TO FORM:
Sonia R. Carvalho, City Attorney
By. "L�c
Lisa Storck
Assistant City Attorney
AYES: Councilmembers Bacerra, Iglesias, Penaloza, Pulido
Sarmiento, Solorio, Villegas (7)
NOES: Councilmembers None (0)
ABSTAIN: Councilmembers None (0)
NOT PRESENT: Councilmembers None (0)
Ordinance No. NS-2981
Page 32 of 33
CERTIFICATE OF ATTESTATION AND ORIGINALITY
I, DAISY GOMEZ, Clerk of the Council, do hereby attest to and certify that the attached
Ordinance No. NS-2981 to be the original ordinance adopted by the City Council of the
City of Santa Ana on December 17, 2019 and that said ordinance was published in
accordance with the Charter of the City of Santa Ana.
Date: �ZOo2 U
,/Daisy Gomez
Clerk of the Council
City of Santa Ana
Ordinance No. NS-2981
Page 33 of 33