Loading...
HomeMy WebLinkAboutNS-1416REL: nr ORDINANCE NO. NS-1416 AN ORDINANCE OF THE CITY OF SANTA ANA AMENDING SECTION 8-1 OF THE SANTA ANA MUNICIPAL CODEr PERTAINING TO THE APPLI- CATION AND SCOPE OF CHAPTER 8 THEREOF, AND AMENDING ARTICLE V OF SAID CHAPTER 8 TO ADOPT THE NATIONAL ELECTRICAL CODE, 1975 EDITION, WITH AMENDMENTS AND ADDI- TIONAL REQUIREMENTS. THE CITY COUNCIL OF THE CITY OF SANTA ANA DOES ORDAIN AS FOLLOWS: SECTION 1: Section 8-1 of the Santa Ana Municipal Code is hereby amended to read as follows: Sec. 8-1. Application and scope. If any provision of this chapter conflicts with the regulations of the Commission of Housing and Community Develop- ment adopted pursuant to the State Housing Law (Health and Safety Code Sections 17910 et seq.), such provision shall apply to an activity subject to such regulations only if either the provision was in effect prior to November 23, 1970, or the pro- vision was enacted pursuant to Sections 17958.5 and 17958.7 of the State Housing Law. SECTION 2: That Section 8-667 of the Santa Ana Muni- cipal Code is hereby amended to read as follows: Sec. 8-667. Adoption by reference. There is adopted by the city that certain code known as the National Electrical Code, 1975 Edition, and the whole thereof save and except such portions as are deleted by the amendments set forth in this Article, of which said code not less than three (3) copies have been and are on file in the office of the clerk of the council of the city. The said code is adopted and incorporated as fully as if set forth at length herein, as provided for in Section 419 of the Charter of the City, and, subject to all amendments set forth in this article, shall be in effect within the City of Santa Ana from the effec- tive date of this ordinance. Any provision of this article amending the "Electrical Code" or "National Electrical Code" shall be construed as amending the said adopted code, 1975 Edition, including such provisions enacted prior to the enact- ment of this ordinance and not thereafter repealed. The said adopted code, 1975 Edition, as thus amended, together with all other provisions of this article, shall be known as the Elec- trical Code of the City of Santa Ana. SECTION 3: That the following sections of the Santa Ana Municipal Code are hereby repealed: 8-699, 8-700, 8-710, 8-719, 8-729, 8-741, 8-756, 8-785, 8-797, 8-810, 8-826, 8-837, 8-857, 8-879, 8-896, 8-916, 8-928, 8-940, 8-942, 8-953, 8-969, 8-979, 8-1000, 8-1010, 8-1023, 8-1034, 8-1050, 8-1070, and 8-1090. ORDINANCE NO. NS- 1416 PAGE TWO SECTION 4: That the Santa Ana Municipal Code is hereby amended by adding a Division to be numbered 2 to Article V of Chapter 8, said Division to consist of sections numbered 8-700 through 8-799 inclusive and to read as follows: DIVISION 2. ADMINISTRATION AND ADDITIONAL REQUIREMENTS Sec. 8-700. Enforcement. The director of building safety of the city is vested with the authority to enforce all of the provisions of this code and shall have the right to enter upon any premises at all reasonable hours for the purpose of inspecting the installation and working of all apparatus coming within the terms of this article and no person shall interfere with the director of build- ing safety in making the inspections or refuse to permit the director of building safety or his deputies to enter the premises for such purposes. Sec. 8-705. Penalties. (a) This code shall not be construed to relieve from or lessen the responsibility of any party owning, operating, con- trolling or installing any electric wiring, electric devices or electric materials for damages to persons or property caused by any defect therein, nor shall the jurisdiction be held as assum- ing any such liability by reason of the inspection authorized herein or certificate of inspection issued as herein provided. (b) The director of building safety is authorized to determine the intent and meaning of any provisions of this code. (c) Any person violating any of the provisions of this code shall be guilty of a misdemeanor. (d) Every person violating any of the provisions of this code shall be deemed guilty of a separate offense for each day or portion thereof during which such violation continues. (e) It is unlawful for any person, either as owner, architect, contractor, artisan, or otherwise, to do or knowingly to cause or permit to be done any electrical wiring as defined in this code in such manner that the same shall not conform to all of the provisions of this code. Sec. 8-711. Permits. No electrical equipment shall be installed within or on any building, structure or premises, publicly or privately owned, nor shall any alteration or addition be made in any such existing equipment without first securing a permit therefor from the director of building safety, except for minor repair work, such as the replacement of lamps or the repair and con- nection of portable electrical equipment to suitable permanently installed receptacles. ORDINANCE NO. NS-1416 PAGE THREE Sec. 8-712. Same - issuance. Permits may be issued only to a person, firm or cor- poration licensed by the state in the classification authorized to perfor~ the work and subject to the conditions and limitations of such classification, or to a person, firm, or corporation qualifying under section 8-714, or to an owner qualifying under section 8-715. Sec. 8-713. Same - applications. Applications for electrical permits, describing the work to be done, shall be made in writing to the director of building safety. The application shall be accompanied by such plans, specifications and schedules as may be necessary to deter- mine whether the installations as described will be in conformity with the requirements of the sections in this code pertaining to electricity. If it shall be found that the installation as des- cribed will conform to all legal requirements, and if the appli- cant has complied with the provisions of the sections in this code pertaining to electricity, a permit for such installation may be issued upon receipt of fees therefor, as prescribed in section 8-722. No deviation may be made from the installation described in the permit without the written approval of the director of building safety. Sec. 8-714. Same - annual permits. An annual permit may be issued to any person, firm, or corporation regularly employing a maintenance electrician approved by the director of building safety. The maintenance electrician may install, alter, maintain, or repair electrical wiring in or on buildings or premises owned or occupied by his employer and shall keep a detailed record of all such work. Within fifteen (15) days following the end of each calendar month, the maintenance electrician shall file an application accompanied by regular fees and obtain an electrical permit for all electrical work accomplished during the preceding month. Sec. 8-715. Same - license requirement. As a condition to the issuance of an electrical per- mit, the applicant must s~gn a statement that he is licensed under the provisions of the California Business and Professions Code, Division 3, Chapter 9 (Contractor's License Law) giving the number of the valid license, or, if the applicant is exempt fr~m the provisions of this chapter, the basis for the alleged exemption. Sec. 8-716. Same - commencement of work. No electrical work for which a permit is required shall be commenced in any building or premises until a permit to do such work shall have been first obtained. Sec. 8-717. Same - penalty. Failure to obtain a permit and pay fees therefor before commencing work shall be deemed evidence of violation of the provisions of this code. Double the amount of permit fee shall be assessed for work commenced before a permit is issued. ORDINANCE NO. NS-1416 PAGE FOUR Sec. 8-718. Sa~e - non-transferability. No permit shall be transferable. A permit granted to any one person, firm or corporation shall not authorize any other person, firm or corporation, except an employee of the permittee, to do any electric wiring. Sec. 8-719. Same - temporary working permits. When, in the opinion of the director of building safety, special conditions warrant, a temporary working permit may be issued to allow the permittee to commence the installation of electrical wiring prior to obtaining a regular electrical permit. However, the temporary working permit shall be replaced by a regular electrical permit before the complete rough inspection can be made. Sec. 8-720. Same - expiration. Every permit shall expire and become null and void for any one or more of the following reasons: Whenever the electric wiring authorized by a permit is not commenced within sixty (60) days from the date of issuance of such permit. e Whenever the electric wiring authorized by a permit has been suspended, abandoned or discon- tinued for a continuous period of one hundred twenty (120) days. Whenever the electric wiring done during any continuous period of ninety (90) days amounts to less than ten (10) per cent of the total of the electric wiring authorized by such per- mit. Before rec~mmencing, proceeding with, or doing any electric wir- ing authorized by but not done before expiration of any such permit, a new permit shall be obtained therefor, and the fee for such permit shall be the fee required for a new permit. Sec. 8-721. Same - revocations and suspensions. The director of building safety may suspend or revoke any electrical permit for any of the following reasons: If any reason is found to exist which would have been cause for denial of such permit. Any material misrepresentation or falsity in the application upon which said permit was issued. e For failure to comply with the provisions of the sections in this code pertaining to electricity; after due notice of corrections and the time limit therefor has expired; or for failure to comply with other codes of this jurisdiction that may be related to or appertain to the sections in this code pertaining to electricity. Sec. 8-722. Permit fees. Fees for the processing of permit applications, plan checking, and other administrative services shall be established by resolution of the city council. Such fees must be paid to the Director of Building Safety for each electrical installation for which a permit is required by this code. No permit shall be issued unless all fees are paid in full. ORDINANCE NO. NS-1416 PAGE FIVE Sec. 8-728. Hidden installations. When any part of a wiring installation is to be hidden from view, the person, firm or corporation installing the wiring shall notify the director of building safety and such parts of the wiring installation shall not be concealed until they have been inspected and approved by the director of building safety. Sec. 8-729. Inspections and corrections. Upon completion of the work which has been autho- rized by issuance of any permit, except an annual permit, it shall be the duty of the person, firm, or corporation installing the same to notify the director of building safety who shall inspect the installation as soon thereafter as practicable. If, upon inspection, the installation is not found to be in con- formity with the provisions of this code, the director of build- ing safety shall notify the person, firm, or corporation making the installation, stating the defects which have been found to exist. All defects shall be corrected within ten (10) days after inspection and notification, or within other reasonable time as permitted by the director of building safety. No electrical installation shall be energized until inspected and approved by the director of building safety. Sec. 8-730. Temporary connections. When authorizing the connection and use of temporary or incomplete work, such authorization shall expire at a time to be stated by the director of building safety. Sec. 8-740. Standards for the installation of electrical equipment. Ail electrical installations;industrial, commercial, and residential, within the governmental jurisdiction covered by this chapter shall be in conformity with the provisions of this article, all applicable State laws, and National Fire Pro- tective Association standards for safety to life and property. Sec. 8-741. Approval of equipment. Ail appliances and equipment shall be listed and labeled by a nationally recognized testing laboratory equal to but not limited to Underwriter's Laboratories, Inc., and approved by the director of building safety. Sec. 8-742. Used materials. Previously used materials shall not be re-used without the written approval obtained in advance from the director of building safety. Sec. 8-743. Nameplates. The maker's nameplate, trademark, or other identifi- cation symbol shall be placed on the outside where it is visible at time of inspection on all electrical materials, devices, appliances, fittings and equipment used or installed under the provisior~of this code. ORDINANCE NO. NS-1416 PAGE SIX Sec. 8-747. Underground installations Whenever any property is developed with new or relocated buildings or structures; or whenever floor area in excess of fifty percent (50%) of the existing floor area is added to an existing building; or whenever a resi- dential building or use is converted to any purpose or use other than that which existed at the time of the conversion, all electrical, telephone, community antenna television and similar service wires or cables which provide direct service to the property being developed, added to, or converted, shall, within the exterior boundary lines of such property, be installed underground. Conduits required for telephone or community antenna television shall be installed to utility specifications by the electrical permit holder prior to inspection of electrical conduit. Lots of record as of November 19, 1969, which are developed for R-1 use, are exempted from the requirements of this section. Sec. 8-765. Same change of occupancy classification. When any building or structure, or portion thereof is placed in a different occupancy classification, those portions directly affected by such occupancy change shall be wired in compliance with the provisions of this article for the new occupancy. Sec. 8-769. Relocated buildings Relocated buildings shall conform to the minimum standards as required in this article for new buildings. SECTION 5: That the Santa Ana Municipal Code is hereby amended by adding a Division to be numbered 3 to Article V of Chapter 8, said Division to consist of sections numbered 8-800 through 8-1155 inclusive and to read as follows: DIVISION 3. AMENDMENTS Sec. 8-803. Purpose (Section 90-1(a)) Section 90-1(a) of the National Electrical Code is amended by adding a second sentence to read as follows: To accomplish this purpose, the requirements set forth in this Electrical Code shall be the minimum standard for electrical install- ations. Sec. 8-805. Scope (Section 90-2(a)) Sec. 90-2(a) of the National Electrical Code is amended to read as follows: (a) Covered. This Code shall cover all wiring and equipment installed, used, or maintained except such electrical wiring and equipment expressly exempted from the provisions of this code. ORDINANCE NO. NS-1416 PAGE SEVEN Sec. 8-815. Conductors (Section 110-5) Section 110-5 of the National Electrical Code is amended by adding a second sentence to read as follows: Ail sections of this National Electrical Code allowing the use of aluminum conductors are sub- ject to the limitation that no aluminum conduc- tor smaller than #6 AWG shall be used. Sec. 8-821. Scope of Article 210 (Section 210-1). Section 210-1 of the National Electrical Code is amended by adding paragraphs designated (a) and (b) to read as follows: (a) Accessory uses or other buildings, signs, etc. separately located on the same lot or premises shall have connecting conductors run under- ground. (Agricultural areas excepted.) (b) Where space circuit protective devices are provided or space for future circuit protec- tive devices is provided on the buss in any flush or semi-flush mounted panel, then raceways of sufficient capacity to permit utilization of such space or spaces shall be provided to an approved accessible location. Such accessible location is normally defined as follows: Where sufficient attic space is available or underfloor space is available, a raceway shall terminate conveniently for future use in each such space. Where this condition does not exist or other factors govern, then such terminations shall be approved by the enforcing authority. Sec. 8-823. Conductors - Minimum Ampacity and Size (Section 210-19(c)) The first paragraph of section 210-19(c) of the National Electrical Code is amended to read as follows: (c) Other Loads. Branch-circuit conductors supply- ing loads other than cooking appliances as covered in (b) above and as listed in Section 210.2 shall have an ampacity sufficient for the loads served and shall not be smaller than No. 12. For the supply of current to general appliance and convenience receptacle circuits, no conductor smaller than No. 12 AWG shall be installed. Sec. 8-828. Receptacle Outlets Required (Section 210-25(b)). Section 210-25(b) of the National Electrical Code amended by amending the sixth paragraph thereof to read as follows: is At least one receptacle outlet shall be installed in each basement, garage, and carport. Garages or carports accessory to dwelling units shall be wired with a minimum of one receptacle per each two auto stalls or fractions thereof. Exception: In hotel, motel, and multiple occupancies, garage and carport receptacles may be omitted. ORDINANCE NO. NS-1416 PAGE EIGHT Sec. 8-829. Lighting Outlets Required (Section 210-26(a)). The first sentence of Section 210-26(a) of the National Electrical Code is amended to read as follows: At least one wall switch controlled lighting out- let shall be installed in every habitable room; in hallways, stairways, garages, and carports; and at outdoor entrances. Sec. 8-839. Feeders (Article 215). Article 215 of the National Electrical Code is a~ended by adding a section designated 215-10 thereto to read as follows: 215-10. Raceways. Ail feeder conductors shall be installed in an approved raceway. Sec. 8-843. Branch circuits required (Section 220-3). Section 220-3 of the National Electrical Code is ~mended by adding three sentences to the introductory paragraph thereof to read as follows: No convenience receptacle or appliance receptacle shall be installed or operated on a general light- ing branch circuit at any time in any occupancy. A one-half hot and one-half switched receptacle may be installed on a lighting branch circuit when used as the lighting outlet required for habitable rooms permitted in 210.26(a) Exception NO. 1. A maximum of 12 convenience receptacle outlets or 12 lighting outlets to any one circuit. Sec. 8-854. Wiring Methods for 600 Volts or Less (Section 230-43). Section 230-43 of the National Electrical Code is hereby amended to read as follows: 230-43. Wiring Methods for 600 Volts or Less. Service entrance conductors extending along the exterior or entering buildings or other structures shall be enclosed in rigid metal conduit to the first over current device, or, for circuits not exceeding 600 volts, in wire ways, auxiliary gut- ters, or as busways. Sec. 8-856. Maximum Number of Disconnects (Sec~ tion 230-71). Section 230-71 of the National Electrical Code is a~ended to read as follows: 230-71. Disconnection from service conductors. A single fusible switch or automatic circuit breaker shall be provided to disconnect all un- grounded conductors supplying each separately metered occupancy. ORDINANCE NO. NS-1416 PAGE NINE Sec. 8-863. Made Electrodes (Section 250-83). Section 250-83 of the National Electrical Code is amended to read as follows: 250-83. Made Electrodes. Where electrodes des- cribed in Section 250.81 and 250.82 are not avail- able, the grounding electrode shall consist of not less than 20 feet of bare copper conductor not smaller than No. 4; or not less than 20 feet of No. 4 steel reinforcing bar; or not less than 20 feet of 3/4 inch galvanized steel conduit; or an approved equal installed as follows: The electrode shall be located in the bottom of the foundation footing with minimum con- crete encasement of 3 inches. One end of the electrode shall extend out of the foundation adjacent to the equipment to be grounded to permit the grounding conductor to be secured by an approved method. EXCEPTION: Where the above method is not practical, the following electrodes may be used upon approval of the enforcing authority; (1) Plate Electrodes. Each plate electrode shall present not less than 2 square feet of exterior soil. Electrodes of iron or steel plates shall be at least 1/4 inch in thickness. Electrodes of nonferrous metal shall be at least 0.06 inch in thickness. (2) Pipe Electrodes. Electrodes of pipe or conduit shall be not smaller than of the 3/4 inch trade size and where of iron or steel, shall have the outer surface gal- vinized or otherwise metal-coated for corrosion protection. Minimum of 8 feet to be driven in the ground. (3) Rod Electrodes. Electrodes of rods of steel or iron shall be at least 5/8 inch in diameter. Approved rods of non-ferrous materials or their approved equivalent used for electrodes shall be not less than 1/2 inch in diameter. Minimum of 8 feet to be driven in the ground. Sec. 8-867. Connection to Electrodes (Section 250-115). Section 250-115 of the National Electrical Code is amended by adding thereto a sentence to be designated (e) to read as follows: (e) The service ground clamp shall be readily accessible. ORDINANCE NO. NS-1416 PAGE TEN Sec. 8-913. Mechanical and Electrical Continuity- Conductors (Section 300-13(b)). Section 300-13(b) of the National Electrical Code is a~ended to read as follows: (b) In all circuits the continuity of conductors shall not be dependent upon device connections, such as lampholders, receptacles, etc., where the removal of such devices would interrupt the continuity. Sec. 8-915. Boxes or Fittings - Where required (Section 300-15(b)). Section 300-15(b) of the National Electrical Code is amended by deleting therefrom Exceptions numbers 1 and 5. Sec. 8-933. Metal-Clad Cable (Article 334). Chapter 3 of the National Electrical Code is amended by deleting therefrom Article 334 and all sections therein in- cluded, to wit: Sections 334-1 through 334-13 inclusive. Sec. 8-941. Uses Permitted or Not Permitted (Section 336-3). Section 336-3 of the National Electrical Code is amended to read as follows: 336-3. Uses Permitted or Not Permitted. Non- metallic sheathed cable shall not be used for ex- posed wiring and shall only be used for concealed wiring in one and two family dwellings or multi- family dwellings (apartment houses) not exceeding three floors above grade. (a) Type NM. This type of non-metallic sheathed cable may be installed for concealed work in normally dry locations. It may be installed or fished in air voids in masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness. Type NM cable shall not be installed where exposed to corrosive fumes or vapors; nor shall it be embedded in masonry or concrete and covered with plaster or similar finish. (b) Moisture and Corrosion-Resistant Type NMC. This type of non-metallic sheathed cable may be installed for concealed work in dry, moist, damp or corrosive locations, and in outside and in- side walls of masonry block or tile. Where em- bedded in plaster or run in shallow chase in masonry walls and covered with plaster within 2 inches of the finished surface, it shall be protected against damage from nails by a cover of corrosion-resistant coated steel at least 1/16 inch in thickness and 3/4 inch wide in the chase or under the final surface finish. ORDINANCE NO. NS-1416 PAGE ELEVEN Sec. 8-943. Exposed Work - General (Section 336-6). Article 336 of the National Electrical Code is amended by deleting therefrom Section 336-6. Sec. 8-945. Devices of Insulating Material (Section 336-11). Article 336 of the National Electrical Code is amended by deleting therefrom Section 336-11. Sec. 8-961. Use of Electrical Metal Tubing (Section 348-1). Section 348-1 of the National Electrical Code is amended to read as follows: 348-1. Use. Electrical metallic tubing may be used for both exposed and concealed work. Electrical metal- lic tubing protected from corrosion solely by enamel shall not be used. Electrical metallic tubing shall not be used (1) where during installation or afterwards, it will be subject to severe physical damage; (2) for installation underground or in concrete. Where prac- ticable the use of dissimilar metals throughout the system shall be avoided to eliminate the possibility of galvanic action. (3) Electrical metallic tubing shall not be used where exposed directly to the wea- ther or excessive moisture. Sec. 8-972. Use of Flexible Metal Conduit (Section 350-2). Section 350-2 of the National Electrical Code is amended to read as follows: 350-2. Use. Flexible metal conduit shall not be used (1) in wet locations unless conductors are of the lead-covered type or of other type specifically approved for the conditions; (2) in hoistways, other than as provided in Section 620-21; (3) in storage battery rooms; (4) in any hazardous location other than permitted in Sections 501-4(b), 502-4 and 503-3; nor (5) where rub- ber-covered conductors are exposed to oil, gasoline, or other materials having a deteriorating effect on rubber; (6) for installation underground, exposed to the water, embedded in masonry, concrete, adobe, plas- ter or similar finish; (7) where exposed to physical damage. Sec. 8-1018. Fixtures in Clothes Closets (Section 410-8). Section 410-8 of the National Electrical Code is amended by adding a sentence designated (c) to read as follows: (c) All lighting outlets shall be operated by a wall or door switch (no pull chain lighting fixtures per- mitted). ORDINANCE NO. NS- 1416 PAGE TWELVE Sec. 8-1025. Branch-Circuit Sizing (Section 422-5). Section 422-5 of the National Electrical Code is a~ended by adding a paragraph designated (c) to read as follows: (c) In every dwelling unit fixed appliances, such as food grinders, dishwashers, washing machines, dryers, laundry tray locations, built-in heaters, or any other fixed appliances with 1/4 H.P. motor or larger shall be on a separate branch circuit supplied by a minimum No. 12 AWG Wire. Each dwelling unit shall have installed therein an individual food waste grinder branch circuit. Said circuit shall be supplied with a minimum No. 12 AWG wire and a 15 ampere indicating type switch. Said switch shall be located in the wall adjacent to the sink. Food waste grinder shall be wired with a minimum of No. 16 AWG 3-wire S.P.To -3 thermo-plastic hard finish cord or equal and an approved grounding type, cord grip cap must be used. Sec. 8-1080. Scope of Article 600 (Section 600-1). Section 600-1 of the National Electrical Code is amended by adding a sentence thereto to read as follows: A sign circuit shall be provided and installed to an accessible location at the front of all commercial and store buildings. SECTION 6: If any section, subsection, sentence, clause, phrase or portion of this ordinance is for any reason held to be invalid or unconstitutional by the decision of any court of competent jurisdiction, such decision shall not affect the validity of the remaining portions of this ordinance. The City Council of the City of Santa hereby declares that it would have adopted this ordinance and each section, subsection, sentence, clause, phrase or portion thereof irrespective of the fact that any one or more sections, subsections, sentences, clauses, phrases or portions be declared invalid or unconstitutional. SECTION 7: Neither the adoption of this ordinance nor the repeal hereby of any ordinance shall in any manner affect the pro- secution for violation of ordinances, which violations were com- mitted prior to the effective date hereof, nor be construed as affect- ing any of the provisions of such ordinance relating to the collection of any such license or penalty or the penal provisions applicable to any violation thereof, nor to affect the validity of any bond or cash deposit in lieu thereof, required to be posted, filed or de- posited pursuant to any ordinance and all rights and obligations thereunder appertaining shall continue in full force and effect. PASSED AND ADOPTED by the City Council of the City of Santa Ana at its regular meeting held on the 27th day of June , 197~. ATTEST: FLORENCEI. MALONE MAYOR ORDINANCE NO. PAGE THIRTEEN NS-1416 STATE OF CALIFORNIA ) COUNTY OF ORANGE ) ss CITY OF SANTA ANA ) I, FLORENCE I. MALONE, do hereby certify that I am the Clerk of the Council of the City of Santa Ana; that the fore- going Ordinance was introduced to said Council at its Regular meeting held on the 19th day of 3une , 197 8, and was again considered by sa--~Council at its Regular meeting held on the 27th : day of June , 1978, and was at said meeting passed and adopted by the following vote, to wit: AYES, COUNCILMEN: Brandt, Garthe, 0rtiz, Yamamoto, Ward NOES, COUNCILMEN:Bricken ABSENT, COUNCILMEN: Evans ELORSNCE I. MALON~ CLERK OF THE COUNCIL x ~ \ APPROVED AS TO FORM: KEITH L. GOW, CITY ATTORNEY STATE OF CALI