Laserfiche WebLink
Planning & Building Agency - <br />k, :1=i* Building and Safety Division <br />E* 0;322@U 20 Civic Center Plaza <br />5/1 **rd Y. P.O. Box 1988 (M-19)ELECTRICAL SIGN <br />Santa Ana, CA 92702 REQUIREMENTS(714) 647-5800 <br />www. santa-ana.orq <br />fy.»''Dix r.+Pri¢uRS)*WO,Sa>*Tai.FFEPAFF*6#122*laeams'FAS?-35.,ARRAFFS+9-4.yey,;r€a»VEAm,JUN·DIX€·We<11#KiMKm <br />Code references are to the 2010 California Electrical Code (CEC) <br />A. All signs require Planning Department approval. <br />B. All electrical signs require electric plancheck and permit. <br />1. Manufacturer's instructions are required at the time of submittal. <br />C-11: 3-21-2011 <br />2. Submit detailed installation instructions including diagrams to the Building Department <br />for plan review at the time of submittal. Plans must include appropriate items noted by <br />this bulletin. <br />3. Cash or surety bond in the amount of $200.00 is required at time of issuance for each <br />address. The cash or surety bond will be refunded after all required finals. <br />C. A building permit is also required - except for open or highlight neon lighting. <br />* 1.D. Installation Requirements: <br />CONTACT FIELD INSPECTOR PRIOR TO SIGN INSTALLATION. <br />(SEE SECTION G OF THIS BULLETIN) <br />1. Conductors and equipment shall comply with California Electric Code Article 600. <br />2. All metal parts of a sign shall be bonded in ttie manner specified in Article 250. Isolated <br />metal parts are permitted to be bonded by using an external green insulated conductor. <br />Equipment grounding & bonding conductors must be sized by 110.26 and protected from <br />physical damage. Minimum size is 14 AWG. CEC 600.7 <br />3. A listed disconnect switch in the power supply primary, shall be installed within sight of <br />sign or have permanently installed means for locking in an "OFF" position. This is also <br />true for a transformer enclosure. CEC 600.6 <br />4. A listed receptacle or an approved termination device shall be used for each neon <br />electrode. To relieve stress at terminations, tubing shall be supported with listed tube <br />supports in an approved manner within six inches of electrode connection. <br />CEC 600.41 & 600.42 <br />5. Every electric sign of any type shall be listed by an approved testing laboratory and shall <br />be installed in conformance with this listing. That includes "1 of x", "2 of x" labeling for <br />each separate unit of a multi-unit sign. CEC 600.3 <br />6. All "can" letters and transformers housings shall have section labels that are readily <br />visible after installation. CEC 600.4 <br />7. Transformers shall be located where accessible and be securely fastened in place. <br />Page 1 of 2