PageREVISIONS:Project Name3.520 kW (DC) / 3.202 kW (CEC-AC)PHOTOVOLTAIC SYSTEM MCFADDEN AVE849 E MCFADDEN AVE UNIT 2,SANTA ANA, CA 92707APN: 011-224-15DATE: 03/21/2024DRAWN BY: TY Contractors Signature: PREMIER BUILDERS & HARDSCAPE INC 8832 LA GRAND AVEGARDEN GROVE, CA 92841 PHONE: (714) 467-9018LICENSE: #995068/B,C53 COVER PAGE CONTRACTOR INFORMATION
<br />CONTRACTOR: PREMIER BUILDERS & HARDSCAPE INC
<br />ADDRESS:8832 LA GRAND AVE, GARDEN GROVE, CA 92841
<br />PHONE:(714) 467-9018
<br />LICENSE #/TYPE:#995068/B,C53
<br />TABLE OF CONTENTS
<br />PAGE 1 COVER PAGE
<br />PAGE 2 SITE PLAN
<br />PAGE 3 PLOT PLAN
<br />PAGE 4 SINGLE LINE DIAGRAM
<br />PAGE 5 STRUCTURAL ATTACHMENT DETAIL
<br />PAGE 6 LABELS AND WARNING SIGNAGE
<br />PAGE 7 PV MODULE SPEC SHEET
<br />PAGE 8 INVERTER SPEC SHEET
<br />PAGE 9 UL LISTING
<br />PAGE 10 GROUNDING
<br />PAGE 11 RAPID SHUTDOWN
<br />PHOTOVOLTAIC GENERAL NOTES PROJECT INFORMATION
<br />NAME:MCFADDEN AVE
<br />ADDRESS:849 E MCFADDEN AVE UNIT 2, SANTA ANA, CA 92707
<br />APN:011-224-15
<br />JURISDICTION:SANTA ANA
<br />OCCUPANCY GROUP: R3
<br />CONSTRUCTION TYPE: V-B
<br />SYSTEM INFORMATION
<br />SIZE(kw):3.520
<br />MODULE TYPE: 8 URE SOLAR FAM440E8G-BB
<br />INVERTERS(S): 8 ENPHASE IQ8PLUS-72-2-US
<br />INVERTER TYPE: MICRO-INVERTER
<br />SCOPE OF WORK:
<br />INSTALL
<br />(8) ROOF MOUNTED PV SOLAR MODULES,
<br />(8) ENPHASE IQ8PLUS-72-2-US INVERTER(S)(240V).
<br />(DC) / 3.202 (CEC-AC)
<br />01 OF 11
<br />ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK PERFORMED SHALL
<br />BE IN ACCORDANCE WITH THE FOLLOWING CODES:
<br />- 2022 CBC / 2021 IBC
<br />- 2022 CRC / 2021 IRC
<br />- 2022 CEC / 2020 NEC
<br />- 2022 CMC / 2021 IMC
<br />- 2022 CPC / 2021 IPC
<br />- 2022 CFC / 2021 IFC
<br />- 2022 BUILDING ENERGY EFFICIENCY STANDARDS
<br />ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED
<br />ELECTRICAL TESTING LABORATORY AND L.A. TEST LAB. EQUIPMENT
<br />INSTALLED SHALL BE PER ITS LISTING REQUIREMENTS AND THE
<br />MANUFACTURER'S INSTRUCTIONS. NEC 110.2, 110.3, 690.4(B), 690.12(D).
<br />ALL OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED, INCLUDING ALL ROOF
<br />MOUNTED TRANSITION BOXES AND SWITCHES.
<br />ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN
<br />ACCORDANCE WITH NEC ARTICLE 250.
<br />PV SYSTEM DC CIRCUIT AND INVERTER OUTPUT CONDUCTORS AND
<br />EQUIPMENT SHALL BE PROTECTED AGAINST OVERCURRENT. CIRCUITS
<br />SIZED IN ACCORDANCE WITH 690.8(A)(2) ARE REQUIRED TO BE PROTECTED
<br />AGAINST OVERCURRENT PROTECTIVE DEVICES. EACH CIRCUIT SHALL BE
<br />PROTECTED FROM OVERCURRENT IN ACCORDANCE WITH 690.9(A)(1), (A)(2),
<br />OR (A)(3). [NEC 690.9(A)]
<br />DISCONNECTING MEANS OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN
<br />INITIATION) SHALL BE LOCATED IN A READILY ACCESSIBLE LOCATION WITHIN
<br />THE EQUIPMENT, WITHIN SIGHT OF THE EQUIPMENT, OR REMOTELY WHERE
<br />THE EQUIPMENT DISCONNECTING MEANS. [NEC 690.13(A), 690.15]
<br />RAPID SHUTDOWN EQUIPMENT TO COMPLY WITH NEC 690.12.
<br />ENERGY STORAGE SYSTEM DISCONNECTING MEANS SHALL BE PROVIDED
<br />FOR ALL UNGROUNDED CONDUCTORS AND SHALL BE READILY ACCESSIBLE
<br />AND WITHIN LINE OF SIGHT; WHERE PARTITIONED, AN ADDITIONAL
<br />DISCONNECT SHALL BE PROVIDED WITHIN SIGHT OF THE ESS COMPONENT.
<br />OVERCURRENT PROTECTION SHALL BE PROVIDED. [706.15, 706.31]
<br />UPON LOSS OF PRIMARY SOURCE, THE OUTPUT OF ELECTRIC POWER
<br />PRODUCTION EQUIPMENT SHALL BE AUTOMATICALLY DISCONNECTED FROM
<br />ALL UNGROUNDED CONDUCTORS OF THE INTERCONNECTED SYSTEMS. THE
<br />ELECTRIC POWER PRODUCTION EQUIPMENT SHALL NOT BE RECONNCETED
<br />UNTIL ALL PHASES OF THE PRIMARY SOURCE IS RESTORED. [NEC 705.40]
<br />ALL CONDUCTORS IN EXPOSED OUTDOOR LOCATIONS SHALL BE LISTED AND
<br />IDENTIFIED FOR USE IN DIRECT SUNLIGHT AND FOR THE APPLICATION. [NEC
<br />690.31(C) THROUGH (F), 310.10(D)]
<br />EXPOSED CONDUCTORS WITHIN THE PV ARRAY SHALL BE PV WIRE/CABLE,
<br />OR TYPE USE-2, OR TYPE RHW-2 (UL 4703 & 854 LISTED) [NEC 690.31(C)(1)]
<br />FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND
<br />TERMINALS TO ENSURE A THOROUGHLY GOOD CONNECTION WITHOUT
<br />DAMAGING THE CONDUCTORS. [NEC 110.14(A)]
<br />FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH
<br />TERMINALS, LUGS, DEVICES, OR CONNECTORS THAT ARE IDENTIFIED AND
<br />LISTED FOR SUCH USE. [NEC 690.31(C)(5), 110.14]
<br />ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END AND
<br />GROUPED FOR UNIQUE IDENTIFICATION. [NEC 690.31(B)]
<br />ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN TIGHT AND
<br />APPROVED FOR USE IN WET LOCATIONS. (NEC 314.15)
<br />ALL GROUNDED, (NEUTRAL), CONDUCTORS' INSULATION SHALL BE SOLID
<br />WHITE, GRAY, OR WITH 3-WHITE STRIPES. [NEC 200.6, 200.7, 400.22]; ALL
<br />GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT COVERING,
<br />OR WITH INSULATION OF GREEN OR GREEN WITH YELLOW STRIPES, NEC
<br />250.119 & 400.23. THE COLOR OF UNGROUNDED CONDUCTORS SHALL BE
<br />OTHER THAN FOR GROUNDED, (NEUTRAL), AND GROUNDING CONDUCTORS.
<br />[NEC 310.110(C)]
<br />MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND
<br />OVERCURRENT PROTECTION IS 10FT IN DWELLING UNITS AND 16.5FT IN OTHER
<br />THAN DWELLING UNITS FROM THE POINT OF CONNECTION TO THE SERVICE.
<br />[NEC 705.11(C)]
<br />CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF
<br />THE OTHER SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE PREMISES
<br />SHALL BE IN ACCORDANCE WITH NEC 705.12(B).
<br />DC WIRING INSIDE A BUILDING MUST BE IN METAL RACEWAYS, METAL-CLAD CABLE,
<br />OR METAL ENCLOSURES. [NEC 690.31(D)]
<br />METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS
<br />CONTAINING CIRCUITS OVER 250-VOLTS TO GROUND MUST BE BONDED IN
<br />ACCORDANCE WITH NEC 250.97.
<br />CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE
<br />READILY ACCESSIBLE AND OPERATING AT OVER 30-VOLTS SHALL REQUIRE A TOOL
<br />TO OPEN AND MARKED "DO NOT DISCONNECT UNDER LOAD" OR "NOT FOR
<br />CURRENT INTERRUPTING." [NEC 690.33(C) & (D)(2)]
<br />EQUIPMENT GROUNDING CONDUCTOR (EGC) SMALLER THAN #6-AWG SHALL BE
<br />PROTECTED FROM PHYSICAL DAMAGE BY AN IDENTIFIED RACEWAY OR CABLE
<br />ARMOR, UNLESS INSTALLED WITHIN HOLLOW SPACES OF THE FRAMING MEMBERS
<br />OF BUILDINGS OR STRUCTURES AND WHERE NOT SUBJECT TO PHYSICAL DAMAGE.
<br />[NEC 250.120(C)]
<br />THE INTERCONNECTION POINT SHALL BE ON THE SUPPLY SIDE OF ALL
<br />GROUND-FAULT PROTECTION EQUIPMENT. [NEC 705.32]
<br />CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT
<br />LOCATED UNDER THE MODULES, MUST BE PROTECTED. [NEC 300.4]
<br />FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF
<br />NATURAL GAS, HOT WATER, AND COLD WATER MUST BE PROVIDED. [NEC 250.104]
<br />GROUNDING ROD ELECTRODES SHALL BE INSTALLED 8-FT MINIMUM IN CONTACT
<br />WITH SOIL AND MINIMUM 5/8-INCH DIAMETER. [NEC 250.52(A)(5), 250.53(G)]
<br />THE MARKINGS, "PHOTOVOLTAIC POWER SOURCE", FOR DC RACEWAYS AND CABLE
<br />ASSEMBLIES MUST BE NO MORE THAN 10-FT O.C.; AND IS SEPARATED BY
<br />ENCLOSURES, WALLS, PARTITIONS, CEILINGS, FLOORS, OR BENDS ABOVE OR
<br />BELOW PENETRATIONS. [NEC 690.31(D)(2)]
<br />WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL
<br />EQUIPMENT. [NEC 110.26]
<br />POWER PRODUCTION SYSTEMS, AND ALL ASSOCIATED WIRING AND
<br />INTERCONNECTIONS OPERATING IN PARALLEL WITH A PRIMARY POWER SOURCE
<br />SHALL BE PERFORMED ONLY BY QUALIFIED PERSONS. [NEC 690.4(C), 705.8]
<br />LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND
<br />SHALL BE A MINIMUM HEIGHT OF 3/8" IN WHITE ON A RED BACKGROUND. [NEC
<br />690.31(G)(4)]
<br />IDENTIFICATION OF POWER SOURCE RAPID SHUTDOWN AND LABELING SHALL BE IN
<br />ACCORDANCE WITH NEC 690.56(C).
<br />SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED TO BE
<br />RETROFITTED ONTO THE EXISTING DWELLING AS PER THE 2022 CRC. THESE
<br />SMOKE ALARMS ARE REQUIRED TO BE IN ALL BEDROOMS, OUTSIDE EACH
<br />BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. CARBON
<br />MONOXIDE ALARMS ARE REQUIRED TO BE RETROFITTED OUTSIDE EACH BEDROOM
<br />AND AT LEAST ONE ON EACH FLOOR OF THE HOUSE. (CRC 314,315)
<br />SMOKE ALARMS AND CARBON MONOXIDE ALARMS ARE REQUIRED PER CRC
<br />SECTIONS 314 AND 315 TO BE VERIFIED AND INSPECTED BY THE INSPECTOR IN THE
<br />FIELD.
<br />A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH Cal-OSHA
<br />REGULATIONS, SECURED AND EXTENDING 3-FT ABOVE THE ROOF.
<br />ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL
<br />EQUIPMENT PRIOR TO ANY INSPECTIONS.
<br />PHOTOVOLTAIC MODULES AND PANEL SYSTEMS INSTALLED ON OR INTEGRAL
<br />WITH BUILDINGS, OR TO BE FREESTANDING (NOT ATTACHED TO BUILDINGS)
<br />SHALL BE TESTED, LISTED, AND IDENTIFIED WITH A FIRE CLASSIFICATION
<br />(CLASS C MINIMUM) IN ACCORDANCE WITH UL1703. WHERE CLASS A OR B
<br />ROOFING IS REQUIRED, THE PV SOLAR SYSTEM (PV PANEL & RACK) SHALL
<br />HAVE THE SAME CLASS/TYPE RATING OR BETTER.
<br />The scope of the plans is for the installation of the solar photovoltaic system
<br />only and the approval is subject to compliance with all applicable city and
<br />state codes and regulations regarding construction. The approval of the plans
<br />does not constitute any certification of the accuracy, completeness, or
<br />building permit status of the existing buildings and structures as shown.Bldg# 101119004
<br />Elec# 20182606
<br />
<br />849 E McFadden Ave-
<br />101119004 & 201826064/29/2024
|