SHEET #:
<br />G-1
<br />PAINT BOOTH NOTES (CFC 2022- SECTON 24)
<br />SHEET CONTENTS:
<br />COVER SHEET
<br />2404.1 General
<br />The application of flammable or combustible liquids by means of spray apparatus in continuous or intermittent processes
<br />shall be in accordance with the requirements of Sections 2403 and 2404.2 through 2404.9.4.
<br />2404.2 Location of Spray-Finishing Operations
<br />Spray-finishing operations conducted in buildings used for Group A, E, I or R occupancies shall be located in a spray room
<br />protected with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 and separated
<br />vertically and horizontally from the remainder of the building by fire barrier walls and horizontal assemblies with not less
<br />than a 1-hour fire-resistance rating in accordance with the California Building Code. In other occupancies, spray-finishing
<br />operations shall be conducted in a spray room, spray booth or limited spraying space approved for such use.
<br />Exceptions:
<br /> Automobile undercoating spray operations and spray-on automotive lining operations conducted in areas with approved
<br />natural or mechanical ventilation shall be exempt from the provisions of Section 2404 when approved and where utilizing
<br />Class IIIA or IIIB combustible liquids.
<br /> In buildings other than Group A, E, I or R occupancies, approved limited spraying space in accordance with Section
<br />2404.9.
<br /> Resin application areas used for manufacturing of reinforced plastics complying with Section 2409 shall not be required
<br />to be located in a spray room, spray booth or spraying space.
<br />2404.3 Design and Construction
<br />Design and construction of spray rooms, spray booths and spray spaces shall be in accordance with Sections 2404.3.1
<br />through 2404.3.4.1.
<br />2404.3.1 Spray Rooms
<br />Spray rooms shall be constructed and designed in accordance with Section 416 of the California Building Code and
<br />Section 2404.3.2 of this code, and shall comply with Sections 2404.4 through 2404.8 of this code.
<br />2404.3.2 Floor
<br />Combustible floor construction in spray rooms shall be covered by approved, noncombustible, nonsparking material,
<br />except where combustible coverings, including but not limited to thin paper or plastic and strippable coatings, are utilized
<br />over noncombustible materials to facilitate cleaning operations in spray rooms.
<br />2404.3.3 Spray Booths
<br />The design and construction of spray booths shall be in accordance with Sections 2404.3.3.1 through 2404.3.3.6,
<br />Sections 2404.4 through 2404.8 and NFPA 33.
<br />2404.3.3.1 Construction
<br />Spray booths shall be constructed of approved noncombustible materials. Aluminum shall not be used. Where walls or
<br />ceiling assemblies are constructed of sheet metal, single-skin assemblies shall be not thinner than 0.0478 inch (18 gage)
<br />(1.2 mm) and each sheet of double-skin assemblies shall be not thinner than 0.0359 inch (20 gage) (0.9 mm). Structural
<br />sections of spray booths are allowed to be sealed with latex-based or similar caulks and sealants.
<br />2404.3.3.2 Surfaces
<br />The interior surfaces of spray booths shall be smooth; shall be constructed so as to permit the free passage of exhaust air
<br />from all parts of the interior, and to facilitate washing and cleaning; and shall be designed to confine residues within the
<br />booth. Aluminum shall not be used.
<br />2404.3.3.3 Floor
<br />Combustible floor construction in spray booths shall be covered by approved, noncombustible, nonsparking material,
<br />except where combustible coverings, including but not limited to thin paper or plastic and strippable coatings, are utilized
<br />over noncombustible materials to facilitate cleaning operations in spray booths.
<br />2404.3.3.4 Means of Egress
<br />Means of egress shall be provided in accordance with Chapter 10.
<br />Exception: Means of egress doors from premanufactured spray booths shall be not less than 30 inches (762 mm) in width
<br />by 80 inches (2032 mm) in height.
<br />2404.3.3.5 Clear Space
<br />Spray booths shall be installed so that all parts of the booth are able to be accessed for cleaning. A clear space of not less
<br />than 3 feet (914 mm) shall be maintained on all sides of the spray booth. This clear space shall be kept free of any storage
<br />or combustible construction.
<br />Exceptions:
<br /> This requirement shall not prohibit locating a spray booth closer than 3 feet (914 mm) to or directly against an interior
<br />partition, wall or floor/ceiling assembly that has a fire-resistance rating of not less than 1 hour, provided that the spray
<br />booth can be adequately maintained and cleaned.
<br /> This requirement shall not prohibit locating a spray booth closer than 3 feet (914 mm) to an exterior wall or a roof
<br />assembly, provided that the wall or roof is constructed of noncombustible material and the spray booth can be adequately
<br />maintained and cleaned.
<br />2404.3.3.6 Size
<br />The aggregate area of spray booths in a building shall not exceed the lesser of 10 percent of the area of any floor of a
<br />building or the basic area allowed for a Group H-2 occupancy without area increases, as set forth in the California Building
<br />Code.
<br />Exception: One individual booth not exceeding 500 square feet (46 m2).
<br />2404.3.4 Spraying Spaces
<br />Spraying spaces shall be designed and constructed in accordance with the California Building Code, and Section
<br />2404.3.4.1 and Sections 2404.4 through 2404.8 of this code.
<br />2404.3.4.1 Floor
<br />Combustible floor construction in spraying spaces shall be covered by approved, noncombustible, nonsparking material,
<br />except where combustible coverings, such as thin paper or plastic and strippable coatings, are utilized over
<br />noncombustible materials to facilitate cleaning operations in spraying spaces.
<br />2404.4 Fire Protection
<br />Spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system complying with
<br />Chapter 9. Protection shall extend to exhaust plenums, exhaust ducts and both sides of dry filters where such filters are
<br />used.
<br />2404.4.1 Fire Extinguishers
<br />Portable fire extinguishers complying with Section 906 shall be provided for spraying areas in accordance with the
<br />requirements for an extra (high) hazard occupancy.
<br />2404.5 Housekeeping, Maintenance and Storage of Hazardous Materials
<br />Housekeeping, maintenance, storage and use of hazardous materials shall be in accordance with Sections 2403.3, 2403.4,
<br />2404.5.1 and 2404.5.2.
<br />2404.5.1 Different Coatings
<br />Spray booths, spray rooms and spraying spaces shall not be alternately utilized for different types of coating materials
<br />where the combination of materials is conducive to spontaneous ignition, unless all deposits of one material are removed
<br />from the booth, room or space and exhaust ducts prior to spraying with a different material.
<br />2404.5.2 Protection of Sprinklers
<br />Automatic sprinklers installed in flammable vapor areas shall be protected from the accumulation of residue from spraying
<br />operations in an approved manner. Bags used as a protective covering shall be 0.003-inch-thick (0.076 mm) polyethylene
<br />or cello-phane or shall be thin paper. Automatic sprinklers contaminated by overspray particles shall be replaced with new
<br />automatic sprinklers.
<br />2404.6 Sources of Ignition
<br />Control of sources of ignition shall be in accordance with Section 2403.2 and Sections 2404.6.1 through 2404.6.2.4.
<br />2404.6.1 Drying Operations
<br />Spray booths and spray rooms shall not be alternately used for the purpose of drying by arrangements or methods that
<br />could cause an increase in the surface temperature of the spray booth or spray room except in accordance with Sections
<br />2404.6.1.1 and 2404.6.1.2. Except as specifically provided in this section, drying or baking units utilizing a heating system
<br />having open flames or that are capable of producing sparks shall not be installed in a flammable vapor areas.
<br />2404.6.1.1 Spraying Procedure
<br />The spraying procedure shall use low-volume spray application.
<br />2404.6.1.2 Drying Apparatus
<br />Fixed drying apparatus shall comply with this chapter and the applicable provisions of Chapter 30. Where recirculation
<br />ventilation is provided in accordance with Section 2404.7.2, the heating system shall not be within the recirculation air
<br />path.
<br />2404.6.1.2.1 Interlocks
<br />The spraying apparatus, drying apparatus and ventilating system for the spray booth or spray room shall be equipped with
<br />interlocks arranged to accomplish all of the following:
<br /> Prevent operation of the spraying apparatus while drying operations are in progress.
<br /> Where the drying apparatus is located in the spray booth or spray room, prevent operation of the drying apparatus until a
<br />timed purge of spray vapors from the spray booth or spray room is complete. This purge time shall be based on completing
<br />not fewer than four air changes of spray booth or spray room volume or for a period of not less than 3 minutes, whichever is
<br />greater.
<br /> Have the ventilating system maintain a safe atmosphere within the spray booth or spray room during the drying process
<br />and automatically shut off drying apparatus in the event of a failure of the ventilating system.
<br /> Shut off the drying apparatus automatically if the air temperature within the booth exceeds 200°F (93°C).
<br />2404.6.1.2.2 Portable Infrared Apparatus
<br />Where a portable infrared drying apparatus is used, electrical wiring and portable infrared drying equipment shall comply
<br />with the California Electrical Code. Electrical equipment located within 18 inches (457 mm) of floor level shall be approved
<br />for Class I, Division 2, hazardous locations. Metallic parts of drying apparatus shall be electrically bonded and grounded.
<br />During spraying operations, portable drying apparatus and electrical connections and wiring thereto shall not be located
<br />within spray booths, spray rooms or other areas where spray residue would be deposited thereon.
<br />2404.6.2 Illumination
<br />Where spraying spaces, spray rooms or spray booths are illuminated through glass panels or other transparent materials,
<br />only fixed luminaires shall be utilized as a source of illumination.
<br />2404.6.2.1 Glass Panels
<br />Panels for luminaires or for observation shall be of heat-treated glass, wired glass or hammered wire glass and shall be
<br />sealed to confine vapors, mists, residues, dusts and deposits to the flammable vapor area. Panels for luminaires shall be
<br />separated from the luminaire to prevent the surface temperature of the panel from exceeding 200°F (93°C).
<br />2404.6.2.2 Exterior Luminaires
<br />Luminaires attached to the walls or ceilings of a flammable vapor area, but outside of any classified area and separated
<br />from the flammable vapor areas by vapor-tight glass panels, shall be suitable for use in ordinary hazard locations. Such
<br />luminaires shall be serviced from outside the flammable vapor areas.
<br />2404.6.2.3 Integral Luminaires
<br />Luminaires that are an integral part of the walls or ceiling of a flammable vapor area are allowed to be separated from the
<br />flammable vapor area by glass panels that are an integral part of the luminaire. Such luminaires shall be listed for use in
<br />Class I, Division 2, or Class II, Division 2, locations, whichever is applicable, and shall be suitable for accumulations of
<br />deposits of combustible residues. Such luminaires are allowed to be serviced from inside the flammable vapor area.
<br />2404.6.2.4 Portable Electric Lamps
<br />Portable electric lamps shall not be used in flammable vapor areas during spraying operations. Portable electric lamps
<br />used during cleaning or repairing operations shall be of a type approved for hazardous locations.
<br />2404.7 Ventilation
<br />Mechanical ventilation of flammable vapor areas shall be provided in accordance with Section 502.7 of the California
<br />Mechanical Code.
<br />2404.7.1 Operation
<br />Mechanical ventilation shall be kept in operation at all times while spraying operations are being conducted and for a
<br />sufficient time thereafter to allow vapors from drying coated articles and finishing material residue to be exhausted.
<br />Spraying equipment shall be interlocked with the ventilation of the flammable vapor areas such that spraying operations
<br />cannot be conducted unless the ventilation system is in operation.
<br />2404.7.2 Recirculation
<br />Air exhausted from spraying operations shall not be recirculated.
<br />Exceptions:
<br /> Air exhausted from spraying operations is allowed to be recirculated as makeup air for unmanned spray operations,
<br />provided that all of the following conditions exist:
<br /> The solid particulate has been removed.
<br /> The vapor concentration is less than 25 percent of the LFL.
<br /> Approved equipment is used to monitor the vapor concentration.
<br /> When the vapor concentration exceeds 25 percent of the LFL, both of the following shall occur:
<br /> An alarm shall sound.
<br /> Spray operations shall automatically shut down.
<br /> In the event of shutdown of the vapor concentration monitor, 100 percent of the air volume specified in the California
<br />Mechanical Code is automatically exhausted.
<br /> Air exhausted from spraying operations is allowed to be recirculated as makeup air to manned spraying operations where
<br />all of the conditions provided in Exception 1 are included in the installation and documents have been prepared to show
<br />that the installation does not pose a life safety hazard to personnel inside the spray booth, spraying space or spray room.
<br />2404.7.3 Air Velocity
<br />The ventilation system shall be designed, installed and maintained so that the flammable contaminants are diluted in
<br />noncontaminated air to maintain concentrations in the exhaust airflow below 25 percent of the contaminant's lower
<br />flammable limit (LFL). In addition, the spray booth shall be provided with mechanical ventilation so that the average air
<br />velocity through openings is in accordance with Sections 2404.7.3.1 and 2404.7.3.2.
<br />2404.7.3.1 Open-Face or Open-Front Spray Booth
<br />For spray application operations conducted in an open-face or open-front spray booth, the ventilation system shall be
<br />designed, installed and maintained so that the average air velocity into the spray booth through all openings is not less
<br />than 100 feet per minute (0.51 m/s).
<br />Exception: For fixed or automated electrostatic spray application equipment, the average air velocity into the spray booth
<br />through all openings shall be not less than 50 feet per minute (0.25 m/s).
<br />2404.7.3.2 Enclosed Spray Booth or Spray Room With Openings for Product Conveyance
<br />For spray application operations conducted in an enclosed spray booth or spray room with openings for product
<br />conveyance, the ventilation system shall be designed, installed and maintained so that the average air velocity into the
<br />spray booth through openings is not less than 100 feet per minute (0.51 m/s).
<br />Exceptions:
<br /> For fixed or automated electrostatic spray application equipment, the average air velocity into the spray booth through all
<br />openings shall be not less than 50 feet per minute (0.25 m/s).
<br /> Where methods are used to reduce cross drafts that can draw vapors and overspray through openings from the spray
<br />booth or spray room, the average air velocity into the spray booth or spray room shall be that necessary to capture and
<br />confine vapors and overspray to the spray booth or spray room.
<br />2404.7.4 Ventilation Obstruction
<br />Articles being sprayed shall be positioned in a manner that does not obstruct collection of overspray.
<br />2404.7.5 Independent Ducts
<br />Each spray booth and spray room shall have an independent exhaust duct system discharging to the outside.
<br />Exceptions:
<br /> Multiple spray booths having a combined frontal area of 18 square feet (1.67 m2) or less are allowed to have a common
<br />exhaust where identical spray finishing material is used in each booth. If more than one fan serves one booth, fans shall be
<br />interconnected such that all fans will operate simultaneously.
<br /> Where treatment of exhaust is necessary for air pollution control or for energy conservation, ducts shall be allowed to be
<br />manifolded if all of the following conditions are met:
<br /> The sprayed materials used are compatible and will not react or cause ignition of the residue in the ducts.
<br /> Nitrocellulose-based finishing material shall not be used.
<br /> A filtering system shall be provided to reduce the amount of overspray carried into the duct manifold.
<br /> Automatic sprinkler protection shall be provided at the junction of each booth exhaust with the manifold, in addition to
<br />the protection required by this chapter.
<br />2404.7.6 Termination Point
<br />The termination point for exhaust ducts discharging to the atmosphere shall be not less than the following distances:
<br /> Ducts conveying explosive or flammable vapors, fumes or dusts: 30 feet (9144 mm) from the lot line; 10 feet (3048
<br />mm) from openings into the building; 6 feet (1829 mm) from exterior walls and roofs; 30 feet (9144 mm) from
<br />combustible walls or openings into the building that are in the direction of the exhaust discharge; 10 feet (3048 mm)
<br />above adjoining grade.
<br /> Other product-conveying outlets: 10 feet (3048 mm) from the lot line; 3 feet (914 mm) from exterior walls and roofs; 10
<br />feet (3048 mm) from openings into the building; 10 feet (3048 mm) above adjoining grade.
<br />2404.7.7 Fan Motors and Belts
<br />Electric motors driving exhaust fans shall not be placed inside booths or ducts. Fan rotating elements shall be nonferrous
<br />or nonsparking or the casing shall consist of, or be lined with, such material. Belts shall not enter the duct or booth unless
<br />the belt and pulley within the duct are tightly enclosed.
<br />2404.7.8 Filters
<br />Air intake filters that are part of a wall or ceiling assembly shall be listed as Class I or II in accordance with UL 900. Exhaust
<br />filters shall be required.
<br />2404.7.8.1 Supports
<br />Supports and holders for filters shall be constructed of noncombustible materials.
<br />2404.7.8.2 Attachment
<br />Overspray collection filters shall be readily removable and able to be accessed for cleaning or replacement.
<br />2404.7.8.3 Maintaining Air Velocity
<br />Visible gauges, audible alarms or pressure-activated devices shall be installed to indicate or ensure that the required air
<br />velocity is maintained.
<br />2404.7.8.4 Filter Rolls
<br />Spray booths equipped with a filter roll that is automatically advanced when the air velocity is reduced to less than 100 feet
<br />per minute (0.51 m/s) shall be arranged to shut down the spraying operation if the filter roll fails to advance automatically.
<br />2404.7.8.5 Filter Disposal
<br />Discarded filter pads shall be immediately removed to a safe, detached location or placed in a noncombustible container
<br />with a tight-fitting lid and disposed of properly.
<br />2404.7.8.6 Spontaneous Ignition
<br />Spray booths using dry filters shall not be used for spraying materials that are highly susceptible to spontaneous heating
<br />and ignition. Filters shall be changed prior to spraying materials that could react with other materials previously collected.
<br />An example of a potentially reactive combination includes lacquer when combined with varnishes, stains or primers.
<br />2404.7.8.7 Waterwash Spray Booths
<br />Waterwash spray booths shall be of an approved design so as to prevent excessive accumulation of deposits in ducts and
<br />residue at duct outlets. Such booths shall be arranged so that air and overspray are drawn through a continuously flowing
<br />water curtain before entering an exhaust duct to the building exterior.
<br />2404.8 Interlocks
<br />Interlocks for spray application finishes shall be in accordance with Sections 2404.8.1 through 2404.8.2.
<br />2404.8.1 Automated Spray Application Operations
<br />Where protecting automated spray application operations, automatic fire-extinguishing systems shall be equipped with an
<br />approved interlock feature that will, upon discharge of the system, automatically stop the spraying operations and
<br />workpiece conveyors into and out of the flammable vapor areas. Where the building is equipped with a fire alarm system,
<br />discharge of the automatic fire-extinguishing system shall also activate the building alarm notification appliances.
<br />2404.8.1.1 Alarm Station
<br />A manual fire alarm and emergency system shutdown station shall be installed to serve each flammable vapor area. When
<br />activated, the station shall accomplish the functions indicated in Section 2404.8.1.
<br />2404.8.1.2 Alarm Station Location
<br />Not less than one manual fire alarm and emergency system shutdown station shall be provided with ready access for
<br />operating personnel. Where access to this station is likely to involve exposure to danger, an additional station shall be
<br />located adjacent to an exit from the area.
<br />2404.8.2 Ventilation Interlock Prohibited
<br />Air makeup and flammable vapor area exhaust systems shall not be interlocked with the fire alarm system and shall remain
<br />in operation during a fire alarm condition.
<br />Exception: Where the type of fire-extinguishing system used requires such ventilation to be discontinued, air makeup and
<br />exhaust systems shall shut down and dampers shall close.
<br />2404.9 Limited Spraying Spaces
<br />Limited spraying spaces shall comply with Sections 2404.9.1 through 2404.9.4.
<br />2404.9.1 Job Size
<br />The aggregate surface area to be sprayed shall not exceed 9 square feet (0.84 m2).
<br />2404.9.2 Frequency
<br />Spraying operations shall not be of a continuous nature.
<br />2404.9.3 Ventilation
<br />Positive mechanical ventilation providing not fewer than six complete air changes per hour shall be installed. Such system
<br />shall meet the requirements of this code for handling flammable vapor areas. Explosion venting is not required.
<br />2404.9.4 Electrical Wiring
<br />Electrical wiring within 10 feet (3048 mm) of the floor and 20 feet (6096 mm) horizontally of the limited spraying space
<br />shall be designed for Class I, Division 2 locations in accordance with the California Electrical Code.
<br />ENGINEER:
<br />CLIENT:
<br />PROJECT:
<br />INSTALL PAINT
<br />SPRAY BOOTH
<br />CONTRACTOR:
<br />REVISIONS
<br />SCALE: N.T.S.
<br />DATE: 08/24/24
<br />CHECKED BY: M.M.
<br />DRAWN BY: P. A.
<br />NO. DESCRIPTION DATE
<br />ADVANCED FIBERGLASS
<br />CONCEPTS
<br />2907 OAK ST.
<br />SANTA ANA, CA 92707
<br />WARNING: This document is for the use of licensed users
<br />only. Any Unauthorized copying, distribution, or
<br />disclosure of information is a violation of copyright laws.
<br />No reproduction in whole or in part of this document may
<br />be made without the written consent of
<br />MDI Spray Systems.
<br />MDI Spray Systems
<br />888 E. 1st Street
<br />Pomona, CA 91766
<br />www.mdispraysystems.com
<br />LIC.#499372, CLASS B, C-16
<br />EXPIRES: 05/31/25
<br />VICINITY MAP
<br />APPLICABLE CODE DATA
<br />INSTALL PAINT SPRAY BOOTH:
<br />ADVANCED FIBERGLASS CONCEPTS
<br />2907 OAK ST.
<br />SANTA ANA, CA 92707
<br />SCOPE OF WORK
<br />EQUIPMENT INSTALLATION:
<br />1. INSTALL ONE (1) PAINT SPRAY BOOTH.
<br />NOTE: PAINT BOOTH APPROVED BY OCFA UNDER PERMIT #SR 24001435.
<br /> APPLICABLE CODES:
<br />Governing Jurisdiction:
<br />Santa Ana, CA
<br />City of Santa Ana Municipal Code
<br />2022 California Building Code
<br />2022 California Mechanical Code
<br />2022 California Electrical Code
<br />2022 California Plumbing Code
<br />2022 California Fire Code
<br />BUILDING SUMMARY:
<br />APN:
<br />BUILDING FLOOR AREA:
<br />NUMBER OF STORIES:
<br />FIRE SPRINKLERS:
<br />CONSTRUCTION TYPE:
<br />BUILDING HEIGHT:
<br />OCCUPANCY TYPE:
<br />ZONE:
<br />411-031-02
<br />12,400 SF
<br />1
<br />YES
<br />V-B
<br />20'-0" NO CHANGE
<br />B / S-1
<br />M1 - LIGHT INDUSTRIAL
<br />COVER SHEET / VICINITY MAP / PAINT BOOTH NOTES
<br />SITE PLAN & FLOOR PLAN
<br />ROOF PLAN & SCREENING PLAN
<br />LINE OF SIGHT
<br />PAINT SPRAY BOOTH PLAN
<br />EQUIPMENT ASSEMBLY & CONSTRUCTION DETAILS
<br />GENERAL
<br />G-1
<br />ARCHITECTURAL
<br />A-1
<br />A-2
<br />A-3
<br />EQUIPMENT
<br />Q-1
<br />Q-2
<br />SHEET INDEX
<br />BUILDING DATA
<br />NOTE:
<br />NO HAZARDOUS MATERIALS ARE ALLOWED EXCEEDING THE ALLOWABLE
<br />AMOUNT PER TABLE 307.1, CBC 2022.
<br />THE FOLLOWING WELDING "WARNING" AND "NO SMOKING" SIGNS SHALL BE
<br />POSTED IN THE VICINITY OF SPRAYING AREAS, DIPPING OPERATIONS, AND
<br />PAINT STORAGE ROOMS:
<br />EQUIPMENT LISTINGS
<br />PROJECT LOCATION
<br />ETL CERTIFIED, REPORT NO. 103659716CRT-002.
<br />OCFA NOTES
<br />1. OCFA FINAL INSPECTION REQUIRED. PLEASE SCHEDULE ALL FIELD INSPECTIONS AT LEAST 48 HOURS IN
<br />ADVANCE. INSPECTIONS CANCELED AFTER 1 P.M. ON THE DAY BEFORE THE SCHEDULED DATE WILL BE
<br />SUBJECT TO A RE-INSPECTION FEE. CALL OCFA INSPECTION
<br />SCHEDULING AT 714-573-6150.
<br />2. SMOKING SHALL BE PROHIBITED IS SPRAY FINISHING AREAS, MIXING ROOMS, AND IN THE VICINITY OF DIP
<br />TANKS. “NO SMOKING” SIGNS SHALL BE CONSPICUOUSLY POSTED IN SUCH AREAS. CFC 2403.2.6.
<br />3. WELDING WARNING SIGNS SHALL BE POSTED IN THE VICINITY OF SPRAYING AREAS, DIPPING OPERATIONS,
<br />AND PAINT STORAGE ROOMS WITH THE FOLLOWING WARNING: “NO WELDING — THE USE OF WELDING
<br />AND/OR CUTTING EQUIPMENT IN OR NEAR THIS AREA IS DANGEROUS BECAUSE OF FIRE AND EXPLOSION
<br />HAZARDS. WELDING AND CUTTING SHALL BE DONE ONLY UNDER THE SUPERVISION OF THE PERSON IN
<br />CHARGE. ” CFC 2403.2.7.
<br />4. ELECTRICAL WIRING AND EQUIPMENT SHALL BE IN ACCORDANCE WITH CFC 24, NFPA 33, NFPA 70, AND
<br />THE CALIFORNIA ELECTRICAL CODE. CFC 2403.2.1.
<br />5. INTERIOR SURFACES OF SPRAY BOOTHS SHALL BE SMOOTH AND CONTINUOUS WITHOUT EDGES AND
<br />OTHERWISE DESIGNED TO PREVENT POCKETING OF RESIDUE, TO ALLOW FREE PASSAGE OF EXHAUST AIR
<br />FROM ALL POCKETS OF THE INTERIOR, AND TO FACILITATE WASHING AND CLEANING WITHOUT INJURY. CFC
<br />2404.3.2.2.
<br />6. FLOORS SHALL BE OF NONCOMBUSTIBLE MATERIAL OR SHALL BE COVERED WITH A NONCOMBUSTIBLE,
<br />NON-SPARKING MATERIAL OF SUCH CHARACTER TO FACILITATE SAFE CLEANING AND REMOVAL OF RESIDUE.
<br />CFC 2404.3.1.1.
<br />7. WHEN SPRAY BOOTHS ARE ILLUMINATED, FIXED LIGHTING UNITS THAT TRANSMIT LIGHT INTO THE SPRAY
<br />BOOTH THROUGH HEAT-TREATED OR HAMMERED WIRE GLASS SHALL BE USED. GLASS PANELS SHALL BE
<br />ARRANGED TO MINIMIZE BREAKAGE AND SO THAT NORMAL ACCUMULATION OF RESIDUE ON THE EXPOSED
<br />SURFACE OF A PANEL WILL NOT BE RAISED TO 200OF BY THE HEAT FROM THE SOURCE OF THE
<br />ILLUMINATION. CFC 2404.6.2.
<br />8. PORTABLE ELECTRIC LAMPS SHALL NOT BE USED IN SPRAYING AREAS DURING A SPRAYING OPERATION.
<br />CFC 2404.6.2.4.
<br />9. METAL PARTS OF SPRAY BOOTHS, EXHAUST DUCTS, AND PIPING SYSTEMS CONVEYING CLASS I OR CLASS
<br />II LIQUIDS SHALL BE ELECTRICALLY
<br />GROUNDED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. CFC 2403.2.5.
<br />10. SPRAYING AREAS SHALL BE PROVIDED WITH MECHANICAL VENTILATION ADEQUATE TO PREVENT THE
<br />DANGEROUS ACCUMULATION OF VAPORS. CFC 2404.7.
<br />11. MECHANICAL VENTILATION SHALL BE KEPT IN OPERATION AT ALL TIMES WHILE SPRAYING OPERATIONS
<br />ARE BEING CONDUCTED AND FOR A SUFFICIENT TIME THEREAFTER TO ALLOW VAPORS FROM DRYING COATED
<br />ARTICLES AND FINISHING MATERIAL RESIDUE TO BE EXHAUSTED.
<br />CFC 2404.7.1.
<br />12. SPRAYING EQUIPMENT SHALL BE INTERLOCKED WITH THE VENTILATION OF THE SPRAYING AREA SUCH
<br />THAT SPRAYING OPERATIONS CANNOT BE CONDUCTED UNLESS THE VENTILATION SYSTEM IS IN OPERATION.
<br />CFC 2404.8.
<br />13. AUTOMATIC SPRINKLERS INSTALLED IN FLAMMABLE VAPOR AREAS SHALL BE PROTECTED FROM THE
<br />ACCUMULATION OF RESIDUE FROM SPRAYING OPERATIONS IN AN APPROVED MANNER. BAGS USED AS A
<br />PROTECTIVE COVERING SHALL BE 0.003-INCH-THICK POLYETHYLENE OR CELLOPHANE OR SHALL BE THIN
<br />PAPER.
<br />14. RECIRCULATION VENTILATION SYSTEMS SHALL HAVE APPROVED VAPOR DETECTION SYSTEMS. IF THE
<br />APPROVED VAPOR CONCENTRATION IN THE RE-CIRCULATED AIR STREAM EXCEEDS 25 PERCENT OF THE
<br />LOWER FLAMMABILITY LIMIT, THE SYSTEM SHALL AUTOMATICALLY SHUT
<br />DOWN THE SPRAYING OPERATION, SWITCH THE VENTILATION SYSTEM TO 100 PERCENT OUTDOOR EXHAUST
<br />AND SOUND AN ALARM. CFC
<br />2404.7.2.
<br />15. VENTILATION SYSTEMS SHALL BE DESIGNED, INSTALLED AND MAINTAINED SUCH THAT THE AVERAGE AIR
<br />VELOCITY OVER THE OPEN FACE OF THE BOOTH, OR BOOTH CROSS-SECTION, IN THE DIRECTION OF AIRFLOW
<br />DURING SPRAYING OPERATIONS SHALL NOT BE LESS THAN 100 LINEAL FEET PER MINUTE. CFC 2404.7.3.
<br />16. PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED FOR SPRAYING AREAS IN ACCORDANCE WITH THE
<br />REQUIREMENTS FOR AN EXTRA (HIGH) HAZARD OCCUPANCY (E.G., 4-A:40-BC WITHIN 30 FEET OF THE
<br />BOOTH). SEE CFC STANDARD 10-1. CFC 2404.4.1 AND 906.
<br />17. SPRAY BOOTHS AND SPRAYING ROOMS SHALL NOT BE ALTERNATELY USED FOR THE PURPOSE OF
<br />DRYING ARRANGEMENTS WHICH WOULD CAUSE A MATERIAL TO INCREASE THE SURFACE TEMPERATURE OF
<br />THE SPRAY BOOTH OR ROOM UNLESS USED FOR AUTOMOBILE REFINISHING IN ACCORDANCE WITH SECTION
<br />CFC 2404.6.1 AND 2404.6.1.2.2
<br />18. HOUSEKEEPING, MAINTENANCE, STORAGE AND USE OF HAZARDOUS MATERIALS SHALL BE IN
<br />ACCORDANCE WITH SECTIONS 2403.3,
<br />2403.4, 2404.5.1 AND 2404.5.2.
<br />19. WASTE CANS: APPROVED METAL WASTE CANS EQUIPPED WITH SELF-CLOSING LIDS SHALL BE PROVIDED
<br />WHENEVER RAGS OR WASTE ARE IMPREGNATED WITH FINISHING MATERIALS. SUCH RAGS AND WASTE SHALL
<br />BE DEPOSITED THEREIN IMMEDIATELY AFTER BEING UTILIZED. THE CONTENT OF WASTE CANS SHALL BE
<br />PROPERLY DEPOSITED OF AT LEAST ONCE DAILY AND AT THE END OF EACH SHIFT.
<br />20. LIMITED SPRAYING AREAS SHALL BE IN ACCORDANCE WITH CFC 2404.9 AIR MAKEUP AND FLAMMABLE
<br />VAPOR AREA EXHAUST SYSTEMS SHALL NOT BE INTERLOCKED WITH THE FIRE ALARM SYSTEM AND SHALL
<br />REMAIN IN OPERATION DURING A FIRE ALARM CONDITION. EXCEPTION: SUCH VENTILATION TO BE
<br />DISCONTINUED WHERE THE TYPE OF FIRE-EXTINGUISHING SYSTEM USED REQUIRES IT. CFC 2404.8.2.
<br />Digitally Signed 03/18/25.
<br />Bldg #101122374
<br />Mech #40139973
<br />
<br />APPROVALS:
<br />PLNG - C. Santana
<br />BLDG/MECH - CSG
<br />2907 S Oak St
<br />4/24/2025
|