The walls should be designed using a soil-footing coefficient of friction of 0.30 and an equivalent <br />passive pressure of 300 lbs/fti. The structural engineer should incorporate appropriate factors <br />of safety in the design of the retaining walls. <br />The active earth pressure may be used for the design of retaining walls that do not directly <br />support structures or support soils that in turn support structures and which will be allowed to <br />deflect. The at-rest earth pressure should be used for walls that will not be allowed to deflect <br />such as those which will support foundation bearing soils, or which will support foundation loads <br />directly. <br />Where the soils on the toe side of the retaining wall are not covered by a "hard" surface such as <br />a structure or pavement, the upper 1 foot of soil should be neglected when calculating passive <br />resistance due to the potential for the material to become disturbed or degraded during the life <br />of the structure. <br />Seismic Lateral Earth Pressures <br />In addition to the lateral earth pressures presented in the previous section, retaining walls which <br />are more than 6 feet in height should be designed for a seismic lateral earth pressure, in <br />accordance with the 2013 CBC. Based on the current site plan, it is not expected that any walls <br />in excess of 6 feet in height will be required for this project. If any such walls are proposed, our <br />office should be contacted for supplementary design recommendations. <br />Retaining Wall Foundation Design <br />The retaining wall foundations should be supported within newly placed compacted structural <br />fill, extending to a depth of at least 2 feet below proposed foundation bearing grade. <br />Foundations to support new retaining walls should be designed in accordance with the general <br />Foundation Design Parameters presented in a previous section of this report. <br />Backfill Material <br />The near-surface soils encountered at the boring locations generally consist of silty fine sands <br />and fine sandy silt:s. These materials may be used as retaining wall backfill. The deeper soils, <br />which contain moderate to high clay content should not be used as retaining wall <br />backfill. In addition, all backfill material placed within 3 feet of the back wall face should have a <br />particle size no greater than 3 inches. The retaining wall backfill materials should be well graded. <br />It is recommended that a minimum 1 foot thick layer of free-draining granular material (less <br />than 5 percent passing the No. 200 sieve) be placed against the face of the retaining walls. This <br />material should extend from the top of the retaining wall footing to within 1 foot of the ground <br />surface on the back side of the retaining wall. This material should be approved by the <br />geotechnical engineer. In lieu of the 1 foot thick layer of free-draining material, a properly <br />installed prefabricated drainage composite such as the Mira DRAIN 6000XL (or approved <br />equivalent), which is specifically designed for use behind retaining walls, may be used. If the <br />layer of free-draining material is not covered by an impermeable surface, such as a structure or <br />pavement, a 12-inch thick layer of a low permeability soil should be placed over the backfill to <br />SOUTHERN <br />CALIFORNIA <br />1* GEOTECHNICAL <br />G&M Convenience Store #72 - Santa Ana, CA <br />Project No. 16G 123-1R <br />Page 26