November 14, 2012 SIGN COMPONENTS MANUAL (SAM)122
<br />5. When used in a cord connected product, the need for conducting a leakage current test shall be considered in the end product.
<br />6. When not marked for Dry and Damp Locations Only the power supply primary bracket shall be provided with min. 3.5 threads
<br />and maximum 5 threads tapered for connection to liquid tight conduit fitting. If less than 3.5 threads, the liquid light shall be
<br />provided with watertight fitting Listed (QCRV) 1/2 inch, liquid tight conduit fittings.
<br />7. The suitability of grounding connection shall be determined in the end-use product.
<br />Class 2 power supply, Model 701680,
<br />1. The product shall be installed in compliance with the mounting, spacing, casualty, and segregation requirements of the ultimate
<br />application.
<br />2. These units are provided with a Class 105(A) insulation system.
<br />3. The suitability of the input and output connections shall be determined in each end use application.
<br />4. These power units are intended for dry or damp location use only.
<br />5. Strain Relief on input lead construction and Impact Tests have not been investigated.
<br />6. The polymeric enclosure of each unit has not been evaluated as ultimate enclosure. The flame class of polymeric enclosure of
<br />each unit is V-2, and the necessity of additional fire barriers shall be determined in end product.
<br />7. Multiple power supplies shall be spaced at least 25mm (1 in.) end to end or 102mm (4 in.) in other directions. If lesser spacings
<br />are used, then the Temperature Test shall be conducted in the end use product. For reference the maximum enclosure (case)
<br />temperature on the power supply was 90°C when tested at 58.4° ambient.
<br />Class 2 power supply, Model 701680-MW.
<br />1. These power supplies have been evaluated to Class 2 output requirements for dc circuits with a maximum of one Class 2
<br />output.
<br />2. The load powered by the Class 2 output of the power supplies rated at max 30 VDC or less are suitable for use in dry, damp and
<br />wet locations.
<br />3. In the end product, power supply spacing to other heat produdng components shall be minimum 2 inches spacing to sidewalls,
<br />and minimum 2 inches spacing to top of endosure.
<br />4. These products are provided with the following electrical ratings:
<br />Input Output
<br />Model [Vac A Hz Vdc A
<br />701680-MW |100-240 0.55 50/60 12 1.67
<br />5. These products shall be enclosed in the end product.
<br />6. These power supplies are suitable for use in dry and damp locations.
<br />Class 2 power supply, Model 701681.
<br />1. The product shall be installed in compliance with the mounting, spacing, casualty, and segregation requirements of the ultimate
<br />application.
<br />2. These units are provided with a Class 105(A) insulation system.
<br />3. Input leads are Style 1015, No. 18 AWG, rated VW-1, 600 V, 105°C. Output leads are Style 1430, No. 18 AWG, rated VW-1,
<br />300 V, 105°C. The suitability of the input and output connections shall be determined in each end use application.
<br />4. These power units are intended for dry or damp location use only.
<br />5. Strain Relief and Impact Tests have not been investigated on input lead construction. The suitability of the enclosure as ultimate
<br />endosure shall be determined in the end-use application.
<br />6. The polymeric enclosure of each unit has not been evaluated as ultimate endosure. The flame class of the polymeric enclosure
<br />is V-0 and the necessity of additional fire barriers shall be determined in end product.
<br />7. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls,
<br />and minimum 2 inches spacing to top of endosure.
<br />Class 2 power supplies, Model 701495.
<br />1. These power supplies have been evaluated to Class 2 output requirements for dc drcuits with a maximum of four Class 2
<br />outputs.
<br />2. These power supplies are only suitable for use in dry, damp and wet locations.
<br />3. In the end product, power supply spacing to other heat producing components shall be minimum 2 inches spacing to sidewalls,
<br />and minimum 2 inches spacing to top of endosure.
<br />Class 2 power LED Lighting Strip, 701912-QQXXYYZZZ series, where QQ represents length, XX represents the LED color
<br />temperature, YY represents configuration and ZZZ represents the LED drive current.
<br />1. These products are only suitable for connection to a Class 2 power source, rated 24VDC.
<br />2. These products have not been evaluated for use when connected to a power source that does not comply with Class 2 voltage
<br />and energy limits and which is rated greater than 24VDC.
<br />3. When units are connected to a Class 2 circuit, they are not to draw a total wattage of greater than the secondary or output rating
<br />of the Class 2 supply.
<br />4. These products are suitable for use in dry, damp and wet locations with supply sources rated class 2.
<br />5. These products are not required to be endosed or protected from the weather in the end product.
<br />6. These products may be secured in place in the end product by any means available.
<br />7. When these products are used in applications other than signs or outline lighting, the need to conduct a temperature test shall
<br />be considered.
<br />Class 2 "Dimming Control Knob" potentiometer, Model 701843.
<br />1. These products are only suitable for connection to the output of a UL Listed or Recognized Class 2 power supply rated max 12
<br />VDC.
<br />2. These products are suitable for use in dry and damp locations.
<br />3. These products are suitable for factory wiring only.
<br />4. These products are 1 Kohm potentiometers intended for connection to max 12 VDC Class 2 power supply that drops the voltage
<br />to a 0-10 V signal to feed into the PWM dimmer.
<br />SPARTECH PLASTICS E202184
<br />3454 N DETROIT ST
<br />WARSAW, IN 46580
<br />Rigid sign enclosure systems, designated SunGard, Sungard Plus, PC-2000, DuraGard and PC-2000 Plus.
|