Laserfiche WebLink
ELECTRICAL CALCULATIONS <br />ASSUMPTIONS <br />HIGH TEMPERATURE 47 °C <br />LOW TEMPERATURE -2 °C <br />TEMP ADDER FOR ROOF RUN 22 °C <br />TEMP ADDER FOR ATTIC RUN 7 °C <br />DC WIRE SIZING CALCULATIONS <br />AT ARRAY Max Optimizer Current = 15 A, Wire = 10 AWG, 40 A @ 90⁰C <br />125% MAX CURRENT (Max Optimizer Current) x (Continuous Load)[690.8(A)]15 A X 1.25 18.75 A Per 690.8(B)(1) 40 A > 18.75 A <br />DERATED AMPACITY (High Temp)[Table 310(B)(2)(A) x (Conductor Ampacity)[Table <br />310.15(B)(16)] x (Conduit Fill)[Table 310.15(B)(3)(a)]0.58 X 40 A X 1 23.2 A Per. 690.8(B)(2) 23.2 A > 15 A <br />10 AWG PV WIRE OK <br />AFTER JBOX Max Optimizer Current = 15 A, Wire = 10 AWG, 40 A @ 90⁰C <br />125% MAX CURRENT (Max Optimizer Current) x (Continuous Load)[690.8(A)]15 A x 1.25 18.75 A Per 690.8(B)(1) 40 A > 18.75 A <br />DERATED AMPACITY (High Temp)[Table 310(B)(2)(A) x (Conductor Ampacity)[Table <br />310.15(B)(16)] x (Conduit Fill)[Table 310.15(B)(3)(a)]0.58 x 40 A x 0.8 18.56 A Per. 690.8(B)(2) 18.56 A > 15 A <br />10 AWG WIRE OK <br />SYSTEM CHARACTERISTICS CALCULATIONS <br />VMP Inverter Fixed String Voltage 380 V 380 V <br />VOC Max Inverter System Voltage 480 V 480 V <br />IMP (DC System Size)/ VMP 5280 W / 380 V 13.9 A <br />ISC (Optimizer Max Output Current) x (# Strings)15 A x 1 15 A <br />DC DISCONNECT VALUES <br />RATED MAX POWER-POINT CURRENT (IMP) 13.9 A <br />RATED MAX POWER-POINT VOLTAGE (VMP)380 V <br />MAX SYSTEM VOLTAGE (VOC)480 V <br />MAX SHORT CIRCUIT CURRENT (ISC)15 A <br />AC WIRE SIZING CALCULATIONS <br />AFTER INVERTER Wire = 10 AWG, 40 A @ 90⁰C <br />MAX AC OUTPUT CURRENT (Max Inverter Output) x (Continuous Load)[690.8(B)(1)] 16 A X 1.25 20.00 A <br />TOTAL AMPACITY (High Temp)[Table 310(B)(2)(A) x (Conductor Ampacity)[Table <br />310.15(B)(16)] x (Conduit Fill)[Table 310.15(B)(3)(a)]0.82 X 40A X 1 32.80 A <br />20.00 A < 32.8 A Therefore 10 AWG OK <br />OCPD CALCULATIONS <br />MAX AC OUTPUT CURRENT (Max Inverter Output) x (Continuous Load)[690.8(B)(1)]16 A X 1.25 20.00 A <br />20.00 A --> 20 A Overcurrent Protection <br />OPTIMIZER CHARACTERISTICS - P505 <br />RATED INPUT DC POWER 505 W <br />MAX INPUT VOLTAGE 83 V <br />MAX INPUT CURRENT 17.5 A <br />MAX OUTPUT VOLTAGE 85 V <br />MAX OUTPUT CURRENT 15 A <br />SAFETY OUTPUT VOLTAGE/OPTIMIZER 1 V <br />MIN/MAX STRING LENGTH 6 / 25 <br />MAX POWER PER STRING [HD-WAVE] 5700 W <br />MODULE CHARACTERISTICS - MSOLAR HC 144BB-440W <br />MAX POWER (PMAX) @ STC 440 W <br />OPEN CIRCUIT VOLTAGE (VOC)49.9 V <br />SHORT CIRCUIT CURRENT (ISC)11.33 A <br />MAX POWER VOLTAGE (VMP)41.0 V <br />MAX POWER CURRENT (IMP)10.74 A <br />SERIES FUSE RATING 20 A <br />INVERTER CHARACTERISTICS - SOLAREDGE SE3800H-US <br />MAX OUTPUT POWER 3800 W <br />SYSTEM OPERATING VOLTAGE 380 V <br />MAX CONTINOUS OUTPUT CURRENT 16 A <br />MAX INPUT VOLTAGE 480 V <br />SYSTEM SHORT CIRCUIT CURRENT 15 A <br />CEC MAX EFFICIENCY 99 % <br />E-2.0REV: A <br />GARDOT, MARNI <br />1128 W RIVIERA DR <br />SANTA ANA, CA 92706 <br />APN # 5643-820-900 TEL #: ---- <br />CLIENT: <br />CALCS <br />1611 POMONA RD.,STE# 206 <br />CORONA, CA 92878 <br />CSLB # 1043108 <br />PHONE 951.298.9007 <br />CONTRACTOR: <br />3/7/22 <br />1128 W Riviera Dr <br />05/31/22